Lam Lee Add-LR000526 (3) CONCRETE INSPECTION AND COMPRESSION TEST REPORT
Client Alice Lee c/oRealty Capital Corporation Work Order Number: 00-1887
Project 00-014 Lam Lee pg i of 2 Report Numbe 00.014.213
SPECIFICATIONS ! PROJECT DATA
Strength (psi): 3000 PSI ~ 28 days IDate of Placement: 5/26/00
Slump(in.): 5.0 Sampled by: i
Air Content(%): N/A Weather: iCloudy,
iConcrete Temp(F): N/A Suppl er/M x: IPioneer / 9327
FIELD DATA SET # ].
Ticket #: 565772 !Time Batched: i ~Time Sampled: 9:30:00 AM
'.Slump (in.): 4.5 iAir Content: ii N/A IUnit Weight (pcf): ~ N/A
,Concrete Temp(F): 84' ~ir Temp (F): I 74° !Yardage 40
iLocation/Remarks: f
SET CYLINDERi DATE ~, AGE MAX LOAD ISTRENGTH TEST [ CYLINDER NOTES
~NO. NO. [ (days) = (psi) RESULT Il SOURCE
I TESTED ' (lbs)
1 01 !6/2/00! 7 i 90500 I 3200 ~
1 02 .6/23/00i 28 I 113000 I 4000
~ I
1 03 ~6/23/00! 28 I 98000 i 3470
I 04 , Discard i i :
FIELD DATA SET #2
Ticket #: 508490 iTime Batched: 11:51:00 AM Time Sampled: 12:15:00 PM
Slump (in.): 5 Air Content: N/A Unit Weight (pcf): N/A
Concrete Temp(F): 88° Air Temp (F): 94° !Yardage: 140
Location/Remarks: East side fire lane - 150 south from center
SET CYLINDER DATE [ AGE MAX LOAD STRENGTH TEST CYLINDER NOTES
NO.: NO. TESTEDI (days) (lbs) (psi) RESULT SOURCE
2 O1 6~2~00 7 88000 3110
2 02 6/23/00 28 107000 3780
2 03 =6/23/00~ 28 108000 ~ 3820
2 04 Discard
NORMAL CYLINDER SIZE: 5X12, AREA:28.27sq. in. UNLESS NOTED HERE: TYPE "A" CONE FRACTURE UNLESS INDICATED OTHERWISE IN NOTES. TEST RESULTS COMPLY
W1TH PROJECT SPECIFICATIONS UNLESS INDICATED "NON-COMPLIANCE" IN NOTES. FIELD TESTS BY SOILTECH ENGINEERING AND TESTING, INC. ARE PER APPLICABLE
ASTM STANDARDS: C138, C143, C172, C231. CYU~ERS MOLDED AND CURED BY SOILTECH ENGINEERING AND TESTING, INC. ARE PER ASTM C31, TESTED PER ASTM
SO~.ffECH Eb~II~ER}/I~~ ANI~ TESTING, INC.
X,J.~es M. Perdue " General Manager
2502 Gravel Drive · Fort Worth, Texas 76118 · 817.595 0064 telephone · 817.589.7279 metro · 817.595,0708 fax
CONCRETE INSPECTION AND COMPRESSION TEST REPORT
Client Alice Lee c/oRealty Capital Corporation Work Order Number: 00-:t887
Project 00-0:[4 Lam Lee PI~ 2 of 2 Report Numbe 00-014.23.3
SPECIFICATIONS PROJECT DATA
Strength (psi): !3000 PSI ~28 Days iDate of Placement: 5~26~00
Slump(in.): ~5 iSampied by: RB
Air Content(%): [N/A iWeather. Cloudy
Temp(F): iN/A [Supplier/Mix: iPioneer / 9327
iConcrete
FIELD DATA SET #3
;Ticket #: 508504 lTime Batched: ;Time Sampled: 2:00:00 PM
;~Slump (in,): ' 7 lair Content: N/A Unit Weight (pcf): N/A
, ~
iConcrete Temp(F): i 89' [Air Temp (F): 92° Yardage: 260
, I
',Location/Remarks: ISoutheast comer of fire lane
SETI CYLINDER DATE AGE MAX LOAD iSTRENGTH! TEST CYLINDER NOTES
NO. i NO. TESTED (days) (lbs) (psi) RESULT SOURCE
3 ' 01 ,6/2/00 7 67000 2370
3 02 !6/23/00' 28 86500 3060
3 03 6/23/00: 28 85000 3000
3 04 Discard
FIELD DATA SET #4
Ticket #: ~*i 535361 ~Time Batched: ~: 1:55:00 PM !Time Sampled: 2:35:00 PM
,Slump (in.): ' 6 3/4 !Air Content: N/A IUnit Weight (pcf): N/A
Concrete Temp(F): 89° iAir Temp (F): 92° Yardage: 300
[ I
!Location/Remarks: i Fire lane - by drain
SET i CYLINDER' DATE AGE MAX LOAD STRENGTHi TEST CYLINDER NOTES
NO. ~ NO. i TESTED i (days) (lbs) (psi) RESULT SOURCE
4 ~ 01 i 6/2/00, 7 57000 2020
4, 02 !6/23/00: 28 77000 2720 IFail
4 03 ~6/23/001 28 72000 2550 ;Fail
4 04 '7/22/00; 56 87500 3100
NORMAL CYLINDER SIZE: 5X12, AREA:28.27sq. in. UNLESS NOTED HERE: TYPE "A" CONE FRACTURE UNLESS INDICATED OTHERWISE IN NOTES. TEST RESULTS COMPLY
W1TH PROJECT SPECIFICATIONS UNLESS INDICATED 'I~ION-COMPLIANCE" IN NOTES. FIELD TESTS BY SOILTECH ENGINEERING AND TESTING, INC. ARE PER APPLICABLE
ASTM STANDARDS: C138, C143, C172, C231, CYLINDERS MOLDED AND CURED BY SOILTECH ENGINEERING AND TESTING, INC. ARE PER AS'tM C31, TESTED PER ASTM
~l~es M. Perdue
General Manai[er
2502 Gravel Drive. Fort Worth, Texas 76118, 817.595 0064 telephone · 817,589.7279 metro · 817.595.0708 fax