REPORT OF
CONCRETE COMPRESSIVE STRENGTH
CUENT: THE KROGEr. CO
Attn: Jeff Kruegar
100 Kroger Drive
Keller, TX 76248 PROJECT NO.: 0903506037
REPORT NO.: 100013
PROJECT: Kroger ~448 DATE OF SERVICE: 5/15/96
Coppell, TX AUTHORIZATION: John
REPORT DATE: 6/12/96
SERVICES: Sample concrete at location of placement, perform required field tests,
prepare and test concrete compressive strength specimens.
PROJECT DATA
CONTRACTOR: David Christopher, Inc. CLASS OF CONCRETE: Hix Number 8273
CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 5/15/96
PLANT: 41 TIME SAMFq ~n: 07: 30A~ BY: Anthony Lively
SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AJR: 78 CONCRETE: 82
STRENGTH: 4000psi @ 28 DAYS TRUCK NO: 453 ~CKET NO: 589834
SLUMP: 4.0" Max AJR CONTENT~): 5.2
AJR: N/A LOCATION OF PLACEMENT:
METHOO OF TEST: ASTM C-39 Parking loc - southeast corner of parking loc
ASTM C-143
REPORT OF TESTS
CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS
CYUNDER MEASURED MAXIMUM COMPRESSIVE
MARKED SLUMP DATE AGE DLNdETER AREA LOAD STRENGTH
SET NO. (inches) TESTED (days} (in.) (sa.in.I (lbs. force) ~sh REMARKS
I i 2.25 5/22/96 7 6.00 28.27 98460 3480
1 2 2.25 6/12/96 28 6.00 28.27 128940 4560
1 3 2.25 6/12/96 28 6.00 28.27 130260 4610
1 4 HOLD HOLD
Technician: Aritho_ny Lively Started: 06:30AM Stopped: ll:30AM
Technic
Report Of Tests Continued On Page 2
1001 LW ~ J?_e~?. a~_cl ,epo_rts .are. ~ ~,..excl.u_~s~e_ ~use or_the cJlem ~to whom lhey .are .ag~lressed ~ sl~l not .be _reproduced except In
,a~.a. ay ~-.1' me sampm m~e~ ana,'m ~nspecm~, ar~ are n~ ~ mine quammes o~ a~arenw I~entlcal ~ similar products.
Tft~. KROGE~ CO REPORT NO. 100013
PROJECT NO; 0~03506037 PAGE 2
CATE OF 8ERvICE: 5/15/96 SET NO. 2
REPORT OF
CONCRETE COMPRESSIVE STRENGTH
(Continued)
PflOdECT DATA
CONTRACTOR: David Christopher, Inc. CLASS OF CONCRETE: Mix Number 8273
CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 5/15/96
PLANT: 41 TIME ~4.MPLED: 10: 00AM BY: A~t:hony Lively
SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AIR: 80 CONCRETE: 83
STRENGTH: 4000psi @ 28 DAYS TRUCK NO: 453 TICKET NO: 590095
SLUMP: 4. O" Max AIR CONTENT(%): 4.0
AIR: I~I/A LOCATION OF PLACEMENT:
METHOD OF TEST: ASTM C-39 Parking lot:-sout:heast: corner of parking lot:
ASTM C-143
REPORT OF TESTS
CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYUNDERS
CYLINDER MEASURED MAXIMUM COMPRESSIVE
MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH
SL=T NO. (inches) TESTED (del/si I'in.) (sa.in.) fibs. force} (os~ REMARKS
2 i 2.00 5/22/96 7 6.00 28.27 106920 3780
2 2 2. O0 6/12/96 28 6.00 28.27 138180 4890
2 3 2. O0 6/12/96 28 6. O0 28.27 129260 4570
2 4 HOLD HOLD
Technician: AnChon_y Lively St:arCed: 06:30AM St:opped: ll:3OAE
Technic lan
Repo~ Distribution: MAXIM TECH.~OUTHWESTERN LABS
(1) THE IOIOGER CO
(11 City of colweLL - Erie. Dept.
(1) City of Colbert - BLdg. lnep. u nerJ. y , C[~J,·
P:oJ act: Manager
1001 LW Our letters and reports are for the exclusive use of_the client.to whom they are addressed ..a!!d. shaJl not be reproduced except In
full without.th~., a,oprov~, of the testl..ng I.aboratory.. i n.e use ~..ouina. me must receive...our .wnnen al~P. ro.~l.. ~ letta.rs.and reRorts
~ only 1o me sample tested and/or ~nspecte~, arm are no[ mcat~ve of the quammes m aooaremp/ lusnacaJ or ~rn~ar ~'o~uc~.