Lakeside V2-LR 960417 Maxim Tech.~ Southwestern Labs 2575 Lone Star Dr. · P.O. Box 224227 Dallas, Texas 75222 T E C H N O L O G I E S I N C Telephone: (214) 631-2700 FAX: (214) 920-1891 REPORT OF CONCRETE COMPRESSIVE STRENGTH CMENT: THE KROGER CO Attn: Jeff Kruegar 100 Kroger Drive Keller, TX 76248 PROJECT NO.: 0903506037 --- REPORT NO.: 39040 PROJECT: Kroger 0448 DATE OF SERVICE: 3/20/96 AUTHORIZATION: John Coppell Tx. REPORT DATE: 4/17/96 SERVICES: Sample concrete at location of placement, perform required field tests, prepare and test concrete compressive strength specimens. PROJECT DATA CONTRACTOR: David Christopher, Inc. CLASS OF CONCRETE: Mix Number 8273 CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 3/20/96 PLANT: 30 ~ME SAMPLED: 08: 20AM BY: Burl Thomas SPECIFICATION REQUIREMENTS TEMPERATURE ('~ -/MR: 38 CONCRETE: 58 STRENGTH: 4000psi @ 28 DAYS TRUCK NO: 417 TICKET NO: 556739 SLUMP: 1-4" AIR CONTENT(%): 5.50 AIR: 4-6~ LOCATION OF PLACEMENT: METHOD OF TEST: ASTM C-39 Paving, 30' south of building southwest ASTM C- 143 corner REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. (inches) TESTED (days) (in.) (scl.in.) (lbs. fome) (os~ REMARKS 1 1 7.00 3/27/96 7 6.00 28.27 56610 2000 1 2 7.00 4/17/96 28 6.00 28.27 100830 3570** 1 3 7. O0 4/17/96 28 6.00 28.27 102260 3620** 1 4 HOLD HOLD Technician: Burl Thomas Started: 06:00AM Stopped: 01:00PM ** Does not comply with specified strength. Report Of Tests Continued On Page 2 1001 LW Our letters and reports are for the exclusive use of_the client.to w~om they are addressed and shall not he reproduced except in full .wffho. ut the approval of the testlni3 laboratory: ,ne use o~ ourname mus.t receive our wt. itten apDroval. Our letters and reports apply only to the sample tested and/Or inspectea, aha are not Incllcatlve of me quantities or apparently identical or similar products. THF. KROGER CO REPORT NO. 39040 PROJECT NO. 0903506037 PAGE 2 DATE OF SERVICE: 3/20/96 SET NO. 2 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) PROJECT DATA CONTRACTOR: David Christopher, Inc. CLASS OF CONCRETE: Mix Number 8273 CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 3/20/96 PLANT: 30 TIME SAMPLED: 09: 20AM BY: Burl Thomas SPECIFICATION REQUIREMENTS TEMPERATURE ('F) -AIR: 39 CONCRETE: 58 STRENGTH: 4000psi @ 28 DAYS TRUCK NO: 215 TICKET NO: 556842 SLUMP: 1-4" AIR CONTENT(%): 5.0 AIR: 4-6% LOCATION OF PLACEMENT: METHOD OF TEST: ASTM C-39 Paving: 30' south of centerline of south wall ASTM C-143 of building REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. (inches1 TESTED (days) (in.} (sa.in.) (lbs. force} (os~3 REMARKS 2 1 7. O0 3/27/96 7 6. O0 28.27 94240 3330 2 2 7. O0 4/17/96 28 6. O0 28.27 109740 3880** 2 3 7.00 4/17/96 28 6.00 28.27 99400 3520** 2 4 HOLD HOLD Technician: Burl Thomas Started: 06:00AM Stopped: 01:OOPM ** Does not comply with specified strength. Report Of Tests Continued On Page 3 1001 LW Our letters and reports are for the exclusive use of_the client .to whom they are addressed and shall not be reproduced except In full .witho. ut the.approva.I of the testing laboratory., i n.e use ~ .ou..rname m.ust, receive..our wt. Itten al3P. roya. I..Our letters..ancl rep. orts apply omy to me sample tested ancl/or inspectea, ana are not ,na~catlve oT me quarto[les OT a,oparen[ly ~aentical or sim,ar proaucts. THE KROGER CO REPORT NO. 39040 PROJECT NO. 0903506037 '"; PAGE 3 DATE OF SERVICE: 3/20/96 SET NO. 3 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) PROJECT DATA CONTRACTOR: David Christopher, inc. CLASS OF CONCRETE: Mix Number 8273 CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 3/20/96 PLANT: 30 TIME SAMPLED: 10: 30AM BY: Burl Thomas SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AIR: 42 CONCRETE: 62 STRENGTH: 4000psi @ 28 DAYS TRUCK NO: 367 TICKET NO: 557016 SLUMP: 1-4" .' AIR CONTENT(%): 4.5 AIR: 4-6% LOCATION OF PLACEMENT: METHOD OF TEST: ASTM C-39 Paving: 30' south, 40' west of center building ASTM C-143 southeast corner REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. (inches) TESTED (days) tin.) (sa.in.) ~lbs. force) ~osi) REMARKS 3 1 6.50 3/27/96 7 6.00 28.27 120620 4270 3 2 6.50 4/17/96 28 6.00 28.27 112150 3970 Ave -- 4000 PSI 3 3 6.50 4/17/96 28 6.00 28.27 113920 4030 3 4 HOLD HOLD Technician: Burl Thomas Started: 06:00AM Stopped: 01:00PM Average compressive strength of two 28 day cylinders complies with specified strength. Report Of Tests Continued On Page 4 1001 LW Our letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced except in full withqut the approval of the_testing laboratory.. The use of ourna_m.e m~st receive our .written aDDroval. Ou.r lette.rs and rep. orts apply omy to the sample testea and,'or inspecte(~, and are not incllca~ve ot the quamltles o* apparently Ider~lca~ or s~mllar proaucts. THE K_ROGER CO REPORT NO. 39040 PROJECT NO. 0903506037 PAGE 4 DATE OF SERVICE: 3/20/96 SET NO. 4 : REPORT OF ': CONCRETE COMPRESSIVE STRENGTH (Cont i hued) PROJECT DATA CONTRACTOR: David Christopher, Inc. CLASS OF CONCRETE: Mix Number 8273 CONCRETE SUPPLIER: TXI DATE OF PLACEMENT: 3/20/96 PLANT: 3~ 3]ME SAMPLED: 11: 25AM BY: Burl Thomas SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AIR-' 43 CONCRETE: 62 STRENgtH: 4000psi @ 28 DAYS TRUCK NO: 558 ~CKET NO: 557118 SLUMP: '1~4" AIR CONTENT(%): 5.0 AIR: 4-6% LOCATION OF PLACEMENT: METHOD OFTEST: ASTM C-39 Paving: 30' south, 42' east of bldg. southeast ASTM C-143 corner REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. (inches) TESTED (days) (in.) (sa.in.} (lbs. force} (psi} REMARKS 4 1 6.00 3/27/96 7 6.00 28.27 82810 2930 4 2 6.00 4/17/96 28 6.00 28.27 114910 4060 4 3 6.00 4/17/96 28 6.00 28.27 112220 3970 Ave - 4015 PSI 4 4 HOLD HOLD Average compressive strength of two 28 day cylinders complies with specified strength. Technician: Burl Thomas Started: 06:00AM Stopped: 01:00PM Report Distribution: MAXIM TECH.eSOUTHWESTERN LABS (1) THE KROGER CO (1) David Christopher, ]nc. (1) Cit~ of Coppe[L - Eng. Oept. (1) City of CoppeLt - Bldg. Insp. Arthur Etherly III, CET Project Mana§er 1001 LW Our letters and reports are for the exclusive use of_the client ~o whom they are addressed and shall not .be _reproduced ex. cept in full without the approval of the testing laboratory. I ne use CT ourname must receive our written abl=roval. .uur letters eno reports apply only to the sample tested and/or inspectei:l, and are not Innicative of the quantities of apparently Identical or similar products.