Lakeside V2-LR 960403MAXIM TECHNOLOGIES, INC.
P.O. Box 224227 * 2575 Lone Star D~b'® * Dala., Texa~ 75212 ° 214/631 - 2700 Melro 2~3-1133
REPORT NO: 39620
CLIENT: The Kroger Company
DATE: April 3, 1996 '
PROJECT: Kroger Store #448, Coppell, Texas
CEENT NO: 0903506037
PAGE I of 2
A FLOOR SURFACE ANALYSIS
LOCATION SURVEYED : Slab on Grade, E.5to J.5 and 17 to 21
Placement 5
APPROXIMATE AREA : 6,181 sf
ASTM STANDARD : ASTM E 1155
INSTRUMENT USED : "Dipstick", manufactured by Face Technologies;
Norfolk, Virginia
SAMPUNG METHOD : Point elevations were measured at regular 12 inch intervals along
straight lines up to 29 feet in length. The elevation differences between all adjacent reading points, the
arithmetic differences between all adjacent 12 inch elevation differences, and b~e elevation differences
between all points separated 10 feet were then calculated. Estimates of the floor's flatness and level-
ness F-Numbers (Fl & FI) were obtained through a statistical analysis of these calculated profile values.
The tabular data is available upon request.
COMBINED OVERALL VALUE RESULTS: PLACEMENT 5
90% Cont. Range 90% Conf. Range
Ff - + FI - +
31.8 2g.4 34.3 21.7 m., 23.8
' Based upoo the numbe~ of samples taken, the~® is & 90% certainty thai the actual F-Numbers of the surlaces surveyacl WILL fall within the ranges
which follow Ne respective es~mated Flalne~l~ and Levelness F--Numbers.
spECIFIED'U'Mi'rS'?~'i ' :..:!i.:":~.--..-'.:.'.:: ~ .... '.: ' ' i '.i ..: - ::.' . '. ~ ~'..:'."
. .?':'. '::..~:::i-:~-:.Spe6ified.~&ali!Vai~eii.Ff:2~.::-.: ;: :: ..: . .-....:.....:... :.: .. . .--::..:: .
i::..':~:;.!'i':":' :$iS&Cifi~.-O~er~li'V~lL~:'i:i~i~:: 'ii:::~'~:':i.-."-:;.' .-:::. :--:~i-i:~.:. ~.'?;;::i..-:??'i:i:. ========================================= :
C. OMMENTS: The Composite F-Flatness and F-Levelness Numbers on this placement are
'SUPERIOR'." to the specified limits.
TECHNICIAN: L. BRACKEN Maxim Tecfixsologies, Inc.
ARTHUR ETHERLY III, CET
Construction Materials Engineering Division
MAXIM TECHNOLOGIES INC.
REPORT NO: 39620
CLIENT: The Kroger Company
DATE: April 3, 1996
PROJECT: Kroger Store #448, Coppell, Texas
CLIENT NO: 0903506037
PAGE 2 of 2
A FLOOR SURFACE ANALYSIS
LOCATION SURVEYED : Slab on Grade, E.5 to J.5 and 17 to 21
Placement 5
APPROXIMATE AREA : 6,181 s.f.
PLACEMENT DATE 04102/96 90% Conf. Range 90% Conf. Range
Survey Line Pts. Ff - + FI - +
1- I 29 25.40 19.41 31.39 41.96 32.07 51.85
I - 2 29 28.21 21.56 34.86 16.27 12.43 20.11
1- 3 29 22.91 17.51 28.31 13.10 10.01 16.19
1 - 4 29 30.27 23.13 37.41 32.34 24.71 39.97
I - 5 29 64.21 49.07 79.35 21.58 16.49 26.67
1 - 6 29 49.17 37.58 60.76 52.56 40.17 64.95
I - 7 29 52.11 39.82 64.40 31.97 24.43 39.51
I - 8 29 30.97 23.67 38.27 20.27 15.49 25.05
OVERALL AREA Pts. Ff - + FI - +
COMBINED: 232 31.8 29.40 34.30 21.7 19.60 23.80
° Based upon the number o~ samples taken, them is a g0% certainty that the actuaJ F-Numbers o1' the surfaces surveyed WILL fall
within the range~ which follow the m~e ,~tJmated Flatne~ and Levelness F-Numbem.
' .'~.-:: :':":. ~:'.'i~latiiei~'~!"F~NU~ber:i ":.~::' ."" Specifi6d Ov~rall:'Value':'!(S~.::FF:':25"
'.b. Eevelness;F~Numb'er:--.-:::: ;SPeCified Overali-Value"(SOV)'"-'FL:20-..":'-~':'i::