Lakeside V2-LR 960314MAXIM TECHNOLOGIES, INC.
l~atm'~nls. Envlronmenlai and Cleolm:lmlr. al ~on~nllal~on. ~mndamenlal Tmtin[ and ~.nalyl~ai ~
P.O. Box 224227 * 2575 Lone SI~' Drive * I:~,Jam, Tm 75212 * 214/e31 --2700 Meizo 2e3,--11~3
REPORT NO: 38820
CLIENT: The Kroger Company
DATE: March 14, 1996
PROJECT: Kroger Store #448, Coppell, Texas
CLIENT NO: 09035O6O37
PAGE I of 2
A FLOOR SURFACE ANALYSIS
LOCATION SURVEYED :Slab on Grade, E.5 to J.8 and 8 to 10
Placement 2
APPROXIMATE AREA : 7,875 sf
ASTM STANDARD : ASTM E 1155
INSTRUMENT USED :"Dipstick", manufactured by Face Technologies;
Norfolk, Virginia
SAMPENG METHOD : Point elevations were measured at regular 12 inch intervals along
straight lines up to 54 feet in length. The elevation differences between all adjacent reading points, the
arithmetic differences between all adjacent 12 inch elevation differences, and the elevation differences
between all points separated 10 feet were t~en calculated. Estimates of the floor's flatness and level-
ness F-Numbers (Ff & Fi) were obtained tnrough a statistical analysis of these calculated profile values.
The tabular data is available upon request.
COMBINED OVERALL VALUE RESULTS: PLACEMENT 1
90% Conf. Range 90% Conf. Range
Ff - + FI -
31.3 2~.4 33.3 20.4 ~.0 2~.g
· Based upon the nurnbe~ of samples taken, there is a 90% certaint7 that the actual F- Numbers of the sudaces surveyed WILL fall within lhe ranges
which Iollow the respeclJve eslJn",aled Fla~ess ancl Levelness F-Numbers.
SPECIFIED LIMITS:
specified.Overall-Value: Ff 25
Specified Overall Value: FI: 20
COMMENTS: The Composite F-Flatness and F- Levelness Numbers on this placement are
SUPERIOR to the specified limits.
TECHNICIAN: L. BRACKEN Maxim Technologies, Inc.
Construction Materials Engineering Division
MAXIM TECHNOLOGIES INC.
REPORT NO'. 38820
CLIENT: The Kroger Company
DATE: March 14, 1996
PROJECT: Kroger Store #448, Coppell, Texas
CLIENT NO: 0903506037
PAGE 2 of 2
A FLOOR SURFACE ANALYSIS
LOCATION SURVEYED : Slab on Grade, E.5 to J.8 and 8 to 10
Placement 2
APPROXIMATE AREA ' 7,875 s.f.
PLACEMENT DATE 03/13/96 90% Conf. Range 90% Conf. Range
Survey Line Pts. Ff - + ! FI - +
I- I 54 30.56 25.31 35.81 i 25.01 20.71 29.31
I- 2 54 36.42 30.16 42.68 ! 20.59 17.05 24.13
I- 3 54 30.46 25.23 35.69 ; 16.30 13.50 19.10
I- 4 54 34.60 28.65 40.55 , 32.75 27.12 38.38
I- 5 54 36.20 29.98 42.42
i 21.86 18.10 25.62
I- 6 54 25.03 20.73 29.33 16.76 13.88 19.64
OVERALL AREA Pts. Ff - + FI - +
COMBINED: 324 31.3 29.40 33.30 20.4 19.00 21.90
* Based upon the number ot sample~ taken, ther~ is a 90% certainty that the actual F-Numbem ~ the surface~ su~ey~d ~/ILL fall
within the ranges which follow the respective estimated Fla~ne~s and Levelness F-Numbem.
SPECIFIED LIMITS · - ....
a. FlatneSs F-:Number: spebified~.oVere~li..:Value (S0v)i~F'~251'' :.".-: