Loading...
WA9302-LR 951205 (7)UEOTECHNICALE IGEE Consultants, Inc. E iNVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 · Fax (214) 620-9794 REPORT OF CONCRETE MIX INSPECTION Report Date: December 5, 1995 Date Concrete Placed: November 10, 1995 Standard 6"x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank Concrete Report No.: 47 Contractor: N atgun Construction Project No.: 95-0196 concrete Supplier and Plant: RediMix Concrete - Plant #1 Location of Placement: Piers H. 5 - 1 and L. 5 - 1 MATERIALS ~ ...., ~,,t~l~ ~s. INSPECTION DATA Description (Lbs./Ct~ .Yd) Mix Number: 686 Time Sample Batched: 10:33 am Cement: Time Sampled: 11: 10 am Sample Location: Pier No. L.5-1 Fly Ash: Track/Ticket No: 14472 Coarse Aggregate: Temperature: Intermediate Aggregate: Ambient Range: 65°F Fine Aggregate: Concrete Range: 55°F Slump Range (inches): 5.5" Admixtures: Weather Conditions: Overcast 1 Time Sutrted: 7:00 am 2 Time Completed: 1:30 pm Added Water: Sample Air Content (%): No Test Total Cubic Yards Placed: 7.75 C.Y. Required Strenglh (Lbs./sq.in.): 4,000 Specimen Measured Age Date Total Lead Compresslye Strength Remarks Number Sirerip (hi.) (Days) Tested (Lbs.) (Lbs./Sq.ln.) CWT 189 5.5" 7 11/11/95 111,000 3,930 CWT 190 5.5" 7 11/11/95 108,400 3,830 CWT 191 5.5" 28 12/07/95 CWT 192 5.5" 28 12/07/95 Test Methods Utilized Fracture Reguktr Cylinders Made By: P. Chen ASTM C-31,C-39,C-143 (Unless Noted Otherwise) Remarlcs andjor Distribution: cc: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendficks - Shimek, Jacobs and rinklea fiRM Consultants, Inc. Reviewed by: {~'~ &/