Lakeside V2-LR 960212 Maxim Tech., Southwestern Labs
2575 Lone Star Dr. · P.O. Box 224227
Dallas, Texas 75222
T E C H N O I. O G I t $ I N C Telephone: (214) 631-2700
FAX; (214) 920-1891
REPORT OF
CONCRETE COMPRESSIVE STRENGTH
CMENT: THE KROGER CO
Attn: Jeff Kruegar
100 Kroger Drive
Keller, TX 76248 PROJECT NO.: 0903506037
REPORT NO.: 36219
PROJECT: Kroger DATE OF SERVICE: 1/16/96
AUTHORIZATION:
REPORT DATE: 2/12/96
SERVICES: Test compressive strength specimens prepared by others and picked up at the
project site.
PROJECT DATA
CONTRACTOR: David Christopher, Inc, CLASS OF CONCRETE: i~/A
CONCRETE SUPPLIER: N/A DATE OF PLACEMENT: 1/15/96
PLANT: N/A TIME SAMPLED: N/A BY: Contractor
SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AIR: N/A CONCRETE: N/A
STRENGTH: Not Provided TRUCK NO: N/A TICKET NO: N/A
SLUMP: N/A AIR CONTENT(%): N/A
AIR: N/a LOCATION OF PLACEMENT:
METHOD OF TEST: ASTM C-39 5 X 5 Junction box northwest corner
ASTM C- 143
REPORT OF TESTS
CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS
CYLINDER MEASURED MAXIMUM COMPRESSIVE
MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH
SET NO. ~inches) TESTED (days) (in.) (sa.in.) (lbs. force) (psi) REMARKS
1 1 NOT 1/22/96 7 6.00 28.27 133960 4740
PROVIDED
1 2 1/22/96 7 6.00 28.27 132400 4680
1 3 2/12/96 28 6.00 28.27 179800 6360
1 4 2/12/96 28 6.00 28.27 182780 6460
ADDITIONAL COMMENTS:
ALL INFORMATION OTHER THAN TEST RESULTS IS FURNISHED AND ASSUMED TO BE
CORRECT.
Technician: James Gray
CME Technician
Report Distribution:
(1) THE KROGER CO MAXIM TECH.,~OUTHWESTERN LABS
(1) David Christopher, Inc.
(1) City of CoppeLt :
Arthur Etherly III, CRT