Lakeside V2-LR 960212 Maxim Tech., Southwestern Labs 2575 Lone Star Dr. · P.O. Box 224227 Dallas, Texas 75222 T E C H N O I. O G I t $ I N C Telephone: (214) 631-2700 FAX; (214) 920-1891 REPORT OF CONCRETE COMPRESSIVE STRENGTH CMENT: THE KROGER CO Attn: Jeff Kruegar 100 Kroger Drive Keller, TX 76248 PROJECT NO.: 0903506037 REPORT NO.: 36219 PROJECT: Kroger DATE OF SERVICE: 1/16/96 AUTHORIZATION: REPORT DATE: 2/12/96 SERVICES: Test compressive strength specimens prepared by others and picked up at the project site. PROJECT DATA CONTRACTOR: David Christopher, Inc, CLASS OF CONCRETE: i~/A CONCRETE SUPPLIER: N/A DATE OF PLACEMENT: 1/15/96 PLANT: N/A TIME SAMPLED: N/A BY: Contractor SPECIFICATION REQUIREMENTS TEMPERATURE ('F) - AIR: N/A CONCRETE: N/A STRENGTH: Not Provided TRUCK NO: N/A TICKET NO: N/A SLUMP: N/A AIR CONTENT(%): N/A AIR: N/a LOCATION OF PLACEMENT: METHOD OF TEST: ASTM C-39 5 X 5 Junction box northwest corner ASTM C- 143 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. ~inches) TESTED (days) (in.) (sa.in.) (lbs. force) (psi) REMARKS 1 1 NOT 1/22/96 7 6.00 28.27 133960 4740 PROVIDED 1 2 1/22/96 7 6.00 28.27 132400 4680 1 3 2/12/96 28 6.00 28.27 179800 6360 1 4 2/12/96 28 6.00 28.27 182780 6460 ADDITIONAL COMMENTS: ALL INFORMATION OTHER THAN TEST RESULTS IS FURNISHED AND ASSUMED TO BE CORRECT. Technician: James Gray CME Technician Report Distribution: (1) THE KROGER CO MAXIM TECH.,~OUTHWESTERN LABS (1) David Christopher, Inc. (1) City of CoppeLt : Arthur Etherly III, CRT 1CC1 LW Our letters and reports are for the exc us ve use of the cent to whom they are addressed and shall not be reproduced except In fuil wrthout the approval of ,'he test nq aboratory The use o.f ourname must receive our .written apl3roval. Our letters and reports apply only to the sample tested and/Or ~nsDecte~l, and are not in(~icatlve of the quantities o~ apparently identical or similar products,