Mansions Phase 1-LR 990112 (4) Rone Englneers, Inc. '1 ~ ~4 Goodnlght Lane Tel. (972) 241-451-7_ ineers Dallas,-'Forl Worm Da,as. Texas Metro (972) 263-1565 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 1 of 4 Report No: 3137-D7429-355 Sample Date: December 28, 1998 Client: Western Rim Services Report Date: January 12, 1999 Location: Building//12 Technician: Leo Ruiz tt Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongatiom End (1) End (2) Elongatiom Tolerance I B-29 South Side Edge 33K 7700 2.125 2.0 YES 2 S-29 South Side Edge 33K 7700 2.125 2.0 YES 3 S-48 * 33K 7700 3.625 0 N/A 4 B-30 ** 33K 7700 2.125 1.75 YES 5 S-101 *** 33K 7700 7.50 7.0 NO 6 B-30 South Side Edge 33K 7700 2.125 2.125 YES 7 B-30 South Side Edge 33K 7700 2.125 2.125 YES 8 B-30 ** 33K 7700 2.125 1.75 NO 9 B-30 East Side Edge 33K 7700 2.125 2.125 YES 10 B-57 East Side Edge 33K 7700 4.375 4.250 YES 11 S-57 East Side Edge 33K 7700 4.375 4.375 YES 12 B-78 ** 33K 7700 6.0 5.375 NO 13 S-62 East Side Edge 33K 7700 4.875 4.875 YES 14 S-62 East Side Edge 33K 7700 4.75 5.00 YES 15 S-62 East Side Edge 33K 7700 4.75 4.625 YES 16 S-62 East Side Edge 33K 7700 4.75 4.50 YES 17 S-62 East Side Edge 33K 7700 4.75 4.75 YES 18 S-65 East Side Edge 33K 7700 5.0 5.0 YES 19 S-65 East Side Edge 33K 7700 5.0 4.875 YES Equipment ID:Ram No: 97-267 Pump No: 03196C Gauge No: 97-267 Equipment Calibration Date: 12/11/98 Comments: *Cable strand S-48 does not exist in slab. **Observed cable pulled to 8000 PSI, as requested by Superintendent. ***Cable has two live ends. i Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (I) Mr. Doyle Damron; C. D. Construction Consultihg LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matler provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are c:\wpwin\repom\D7429-355-98\ST January 13, 1999 ~ I~one l~nsln.er~, Inc;. 1~ ~'~4 aoodn~ght Lane TeL (97 ) 24 -4s 7- RoneEnaineers Dallas/Fart Wash Dallas. Texas Metro (972) 263-15,55 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 2 of 4 Report No: 3137-D7429-355 Sample Date: December 28, 1998 Client: Western Rim Services Report Date: January 12, 1999 Location: Building//12 Technician: Leo Ruiz # Tendon Location Jack Force Gauge Required Elongadom Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 20 S-65 East Side Edge 33K 7700 5.00 4,875 YES 21 S-61 East Side Edge 33K 7700 4.625 4.50 YES 22 S-61 East Side Edge 33K 7700 4.625 4.375 YE~ 23 B-64 East Side Edge 33K 7700 4.875 4.625 YES 24 S-64 East Side Edge 33K 7700 4,875 5.00 YES 25 S-64 East Side Edge 33K 7700 4,875 5.00 YES 26 S-62 East Side Edge 33K 7700 4.75 4.75 YES 27 S-64 East Side Edge 33K 7700 4.875 5.00 YES 28 B-64 East Side Edge 33K 7700 4.875 5.00 YES 29 S-62 East Side Edge 33K 7700 4.75 4,875 YES 30 S-62 East Side Edge 33K 7700 4.75 5.00 YES 31 B-69 East Side Edge 33K 7700 5.25 5.375 YES 32 S-69 East Side Edge 33K 7700 5.25 5.375 YES 33 S-69 East Side Edge 33K 7700 5.25 5.375 YES 34 S-69 East Side Edge 33K 7700 5.25 5.00 YES 35 B-69 East Side Edge 33K 7700 5.25 5.125 YES 36 S-69 East Side Edge 33K 7700 5.25 5.125 YES 37 S-69 East Side Edge 33K 7700 5.25 5.375 YES 38 S-69 East Side Edge 33K 7700 5.25 5.25 YES Equipment ID: Ram No: 97-267 Pump No: 03196C Gauge No: 97-267 Equipment Calibration Date: 12/11/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulffng LIMITATIONS: The test results prmemed herein were prepared based upon the specific samples provided for tesl~ng. We assume no respomibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persom or conditions over which we have no control. Our letlers and reports are for the exclusive use of the clients to whom they are c:\wpwin\reports\D7429-355-98\ST January 13, 1999 Da~las.-'Forl VVorth Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 3 of 4 Report No: 3137-D7429-355 Sample Date: December 28, 1998 Client: Western Rim Services Report Date: January 12, 1999 Location: Building//12 Technician: Leo Ruiz # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 S-61 East Side Edge 33K 7700 4.625 4.625 YES 40 B-32 East Side Edge 33K 7700 2.375 2.25 YES 41 S-32 East Side Edge 33K 7700 2.375 2.375 YES 42 S-61 Nor& Side Edge 33K 7700 4.625 4.50 YES 43 B-61 Nor& Side Edge 33K 7700 4.625 4.750 YES 44 S-70 Nor& Side Edge 33K 7700 5.375 5.50 YES 45 S-98 Nor& Side Edge 33K 7700 7.625 7.50 YES 46 S-101 Nor& Side Edge 33K 7700 7.875 7.75 YES 47 B-75 Nor& Side Edge 33K ./700 5.75 5.625 YES 48 S-101 North Side Edge 33K 7700 7.875 7.875 YES 49 S-102 Nor& Side Edge 33K 7700 7.875 7.875 YES 50 S-102 Nor& Side Edge 33K 7700 7.875 7.875 YES 51 S-t02 Nor& Side Edge 33K 7700 7.875 8.00 YES 52 B-76 ** 33K 7700 5.875 4.25 YES 53 S-98 Nor& Side Edge 33K 7700 7.625 7.50 YES 54 S-98 Nor& Side Edge 33K 7700 7.625 7.625 YES 55 S-98 Nor& Side Edge 33K 7700 7.625 7.625 YES 56 S-98 Nor& Side Edge 33K 7700 7.625 7.75 YES 57 S-101 Nor& Side Edge 33K 7700 7.875 7.375 YES Equipment ID: Ram No: 97-267 Pump No: 03196C Gauge No: 97-267 Equipment Calibration Date: 12/11/98 Comments: **Observed cable pulled to 8000 PSI, as requested by Superintendent. Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Darm'on; C. D. Construction Consulti_hg LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, ~nc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are c:\wpwin\reports\D7429-355-98\ST January 13, 1999 ~.~,~ I~§i~4~, I~e. 'l 'lar~4 Q,s~d~;,g~,( L~ .. Tgi. (g72) 241-4517-- Da,~.s.'Fo,~ Worm Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 4 of 4 Report No: 3137-D7429-355 Sample Date: December 28, 1998 Client: Western Rim Services Report Date: January 12, 1999 Location: Building//12 Technician: Leo Ruiz # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongatiom End (1) End (2) Elongations Tolerance 58 B-74 North Side Edge 33K 7700 5.75 5.875 YES 59 S-101 **** 33K 7700 7.875 7.00 NO 60 S-101 North Side Edge 33K 7700 7.875 7.50 YES 61 S-101 North Side Edge 33K 7700 7.875 7.50 YES 62 B-74 North Side Edge 33K 7700 6.125 5.94 YES 63 S-15 North Side Edge 33K 7700 I 1.0 YES 64 S-27 North Side Edge 33K 7700 2 2.0 YES 65 S-27 North Side Edge 33K 7700 2 1.875 YES 66 B-27 North Side Edge 33K 7700 2 2.0 YES Equipment ID: Ram No: 97-267 Pump No: 03196C Gauge No: 97-267 Equipment Calibration Date: 12/11/98 Comments: ****Cable S-101, anchor failed. Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Copper (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consultihg LIMITATIONS: The test resul~ presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject manor provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are adcbessed. c:\~win\reports\D7429-355-98\ST January 13, 1999