Mansions Phase 1-LR 981123 Dallas Fort Wc.d.'~ Dallas. Texas Metro (972) 263-1555
75229 Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page I of 4
Report No: 3137-D7429-335 Sample Date: November 18, 1998
Client: Western Rim Services Report Date: November 23, 1998
I.ocation: Builidng #15 Technician: R. Lovelady
~ Tendon Location Jack Force Gauge Required Elongations Elongations Total Within
No. ('Kips) Pressure Elongations End (1) End (2) Elongations Tolerance
1 S-59 N Side - E to W 33K 55.00 4 5/8 4 1/2 YES
2 B-59 N Side - E to W 33K 5500 4 5/8 4 1/2 YES
3 S-68 N Side - E to W 33K 5500 5 3;8 5 1/2 YES
4 S-96 N Side - E to W 33K 5500 7 1/2 7 3/8 YES
5 S-98.6 N Side - E to W 33K 5500 7 3/4 8 1/4 YES
6 S-98.6 N Side - E to W 33K 5500 7 3/4 7 1/4 YES
7 B-73.6 N Side - E to W 33K 5500 5 5!8 5 1!2 YES
8 S-100 N Side - E to W 33K 5500 7 7/8 7 314 YES
9 S-100 N Side - E to W 33K 5500 7 7/8 8 YES
10 S-l(}0 N Side - E to W 33K 5500 7 718 7 7/8 YES
11 B-73 N Side - E to W 33K 5500 5 5:8 5 1i'2 YES
12 S-96 N Side - E to W 33K 5500 7 1/2 7 3/4 YES
13 S-96 N Side - E to W 33K 5500 7 1/2 7 3i4 YES
14 S-96 N Side - E to W 33K 5500 7 1/2 7 3/4 YES
15 S-96 N Side - E to W 33K 5500 7 1/2 7 1.14 YES
16 S-98.6 N Side - E to W 33K 5500 7 3;4 7 5/8 YES
17 B-71.6 N Side - E to W 33K 5500 5 1/2 5 1/2 YES
18 S-98.6 N Side - E to W 33K 5500 7 3/4 7 1/4 YES
19 S-98.6 N Side - E to W 33K 5500 7 3/4 8 YES
Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014
Equipment Calibration Date: 9/04/98
Comments:
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Nlr. Mike Hodge; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMI'rATIONS: The test resutts presented herein were prepared based upon the specific samples provided for testing. We assume no
responsibility for variation in quality (composition, appearance, performance, etc.) or an)' other feature of similar subject matter provided by
persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom the}' are /txI
addressed.
c:\wpwin'~reports,,D7429-335.98~.ST November 23, 1998
Rone Encjineers, Inc. ~ "'~34 Goodnight L~ne ! Tel. (~72) 241-45~-- RoneEnqineers
Da,as-'Fort Wor[h Dallas, Texas = Metro (972) 263-1555
75229 i Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page 2 of 4
Report No: 3137-D7429-335 Sample Date: November 18, 1998
Client: Western Rim Services Report Date: November 23, 1998
Location: Builidng #1S Technician: R. Lovelady
~ Tendon Location Jack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations End (l } End (2) Elongations Tolerance
20 S-98.6 N Side - E to W 33K 5500 7 3/4 7 5!8 YES
21 B-76 N Side - E to W 33K 5500 6 5 3/4 YES
22 S-12,6 N Side - E to W 33K 5500 718 3/4 YES
23 S-26 N Side - E to W 33K 5500 2 1 7/8 YES
24 S-26 S Side - W to E 33K 5500 2 1 7!8 YES
25 S-26 S Side - W to E 33K 5500 2 1 7/8 YES
26 B-27 S Side - W to E 33K 5500 2 1/8 I 15/16 YES
27 S-27 S Side - W to E 33K 5500 2 1/8 I 15/16 YES
28 S-46 S Side - W to E 33K 5500 3 5/8 3 3/4 YES"
29 B-27 S Side - W to E 33K 5500 2 1:'8 2 1i8 YES
30 B-27 S Side - W to E 33K 5500 2 1/8 2 I/4 YES"
31 B-27 S Side - W to E 33K 5500 2 1/8 2 1/8 YES
32 B-27 S Side - W to E 33K 5500 2 1/8 2 1/8 YES
33 S-55 S Side - W to E 33K 5500 4 4 1/8 YES
34 B-55 S Side - W to E 33K 5500 4 1/4 4 1/4 YES
35 B-65.5 S Side - W to E 33K 5500 5 1/8 5 3/8 YES
36 S-60.6 E Side - S to N 33K 3500 4 3!4 4 5/8 YES
37 S-59.6 E Side - S to N 33K 5500 4 518 4 5/8 YES
38 S-59.6 E Side - S to N 33K 5500 4 5/8 4 5/8 YES
Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 930214
Equipment Calibration Date: 9/04/98
Comax~ents: * No. 28, S-46- covered up, repuiled 11/19; No. 30, B-27- pulled loose, repulled 11/19.
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Mike Hodge; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no
responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject maner provided by
persons or conditiotts over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are
addressed.
c:\'~,,pwin',reports:D7429-335-98',ST November 23, 1998
rto,-,~ ¢,-,~ .... ~, t,-,¢. , --,~4 Qood,-,tght {_~ne To(. (~72i 241-45~-' RoneEnqineers
Dallas 'roq Worth Dallas. Texas Metro (972) 263-1555
75229 Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page 3 of 4
Report No: 3137-D7429-335 Sample Date: November 18, 1998
Client: Western Rim Services Report Date: November 23, 1998
Location: Builidng/915 Technician: R. Lovelady
Jack Force Gauge Required [ Elongations Elongations Total Wilhin
Tendon
Location
No. (Kips) Pressure Elongations End (I) End (2} Elongations Tolerance
39 B-59.6 E Side - S to N 33K 5500 4 5;8 4 1/2 YES
40 S-59.6 E Side - S to N 33K 5500 4 5/8 4 1/2 YES
41 S-62.6 E Side ~ S to N 33K 5500 4 7/8 5 1:8 YES
42 S-62.9 E Side - S to N 33K 5500 4 7/8 4 5/8 YES
43 B-62.9 E Side - S to N 33K 5500 4 7;8 4 3/4 YES
44 S-59 E Side - S to N 33K 5500 4 5;8 4 1/2 YES
45 S-59 E Side - S to N 33K 5500 4 5/8 4 1/2 YES
46 S-61.6 E Side - S to N 33K 5500 4 3/4 4 5/8 YES
47 B-61.6 E Side - S to N 33K 5500 4 3/4 4 5/8 YES
48 S-61.6 E Side - S to N 33K 550{} 4 3/4 4 5i8 YES
49 S-59.6 E Side - S to N 33K 550{} 4 5.."8 4 3/4 YES
5{} S-61.6 E Side - S to N 33K 5500 4 3/4 4 5.~8 YES
51 S-61.6 E Side - S to N 33K 5500 4 3/4 4 5/8 YES
52 S-59.6 E Side - S to N 33K 5500 4 5/8 4 314 YES
53 S-59.6 E Side - S to N 33K 5500 4 5/8 4 1i2 YES
54 S-67 E Side - S to N 33K 5500 5 1/4 5 1/2 YES
55 B-67 E Side - S to N 33K 5500 5 1/4 5 3/8 YES
56 S-67 E Side - S to N 33K 5500 5 1/4 5 YES
57 S-67 E Side - S to N 33K 5500 5 !14 5 1/4 YES
Equipment ID: Rain No: 93014 Pump No: 381996 Gauge No: 93014
Equipment Calibration Date: 9/04/98
Comments:
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Mike Hodge; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no
responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by
persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to who~n they are
addressed.
c:',wpwin~.reports~.D7429-335-98'~ST November 23, 1998
Da,~as-Foq Wont, ' Dallas, Texas Metro (972) 263-1555
75229 Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page 4 of 4
Report No: 3137-D7429-335 Sample Date: November 18, 1998
Client: Western Rim Services Report Date: November 23, 1998
Location: Builidng #15 Technician: R. Lovelady
# Tendon Location Jack Force Gauge Required Elongatir, ns [ EIo~,gations Total Within
No. (Kips') Pressure Elongations End ( I ) End f2) Elongations Tolerance
58 S-67 E Side - S to N 33K 5500 5 1:4 5 1/4 YES
59 B-67 E Side - S to N 33K 5500 5 1/4 5 1/4 YES
60 S-67 E Side - S to N 33K 5500 5 1/4 5 9/16 YES
61 S-67 E Side - S to N 33K 5500 5 1!4 5 1!2 YES
62 S-59 E Side - S to N 33K 5500 4 5/8 4 1/2 YES
63 S-29.6 E Side - S to N 33K 5500 2 114 2 I/8 YES
64 B-29.6 E Side - S to N 33K 5500 2 1,.'4 2 3/16 YES
Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014
Equipment Calibration Date: 9/04/98
Conunents:
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Mike Hodge; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test resuhs presented herein were prepared based upon the specific samples provided for testing· We assume no
respozbibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject mal~er provided by
persoits or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are
addressed.
c:'wvpwin',.reports',D7429-335-98\ST November 23, 1998