Loading...
Mansions Phase 1-LR 981030 (4) ,.o7;; Ro eEn inee ...... n rs Dallas.-'Fo~ Wo,ln Dallas. Texas Metro (972) .-6~-155; , 75229 Fax (972) 241-5174 Concrete Cylinder Test Report Project Mansions By The Lake Purchase Order Number 3137-D7429-272 r Date of Observation 10/01/98 Report Date 10/30/98 To Western Rim Services Contractor Location SLAB ON GRADE, BUILDING #31 - 20' EAST, 5' NORTH FROM SOUTHWEST CORNER OF BUILDING Time Sampled 10:00 Time Batched 9:00 Weather Condition PT CLOUDY Concrete Temperature (OF) 83 Ambient Temperature (°F) 83 Mix Number 51 Mix Description Unit Weight Water Added NONE Physical Data ACTUAL SPECIFICATIONS SLUMP (in.) 6 1/2 Concrete Cylinder Test(s) Speo menI Age I,estDatel*Otal,oadl Compressive No. (Days) (lbs.) Strength (psi) Strength Required (psi) 120A 7 10/08 67500 2390 3000/28 DAYS B 28 10/29 98500 3480 C 28 10/29 95000 3360 D H Curing Method I Test Method I Standard 6" x 12" I Engineer/l'echnician R. LOVELADY ASTM C 31 ASTM C 39 Area 28.27 sq. in. Signature: Mike Fuller, AET Supervisor, CMT ¢~ Remarks and/or Distribution Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for -*.esting. We assume no responslbdity for variation m quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:\wpwin\reports",D7429-272-98\ST October 30, 1998