Loading...
WA9302-LR 951020 (02) ]~'EOTECHNICAL E GEE Consultants, Inc. E [NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 * Fax (214) 620-9794 REPORT OF CONCRETE MIX DESIGN Report Date: October 20, 1995 Date Concrete Placed: September 15, 1995 Standard 6"x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank Concrete ReportNo.: 1 Contractor: Natgun Construction Project No.: 95- 0196 Concrete Supplier and Plant: RediMix Concrete 121 Plant Location of Placement: GEE Consultants, Inc. Laboratory Confirmat ion Cylinders MATE R IAL S s .... / Batch Win. Description (lbs./C.Y) INSPECTION DATA Mix Number: Dome Ring, Dome Slots Mix//687 Time Sample Batched: 5:10 am Cement: TXI Type I/II 658 Time Sampled: 5:25 am Fly Ash: -0- -0- Sample Location: GEE Consultants, Inc. Truck/Ticket No: N/A Coarse Aggregate: No. 67 1,200 Temperature: Intermediate Aggregate: -0- -0- Ambient Range: 93°F Fine Aggregate: Sand 1,615 Concrete Range: 89°F Admixtures: Slump Range (inches): 3" Weather Conditions: Partly Cloudy 1 Monex NW (C494(A)) 20.0oz/yd. Time Started: N/A 2 Monex Air 30 (C260) 3.5oz/yd. Time Completed: N/A Water: 35.5 gals. Sample Air Content ( % ): 2 V~ % Total Cubic Yards Placed: 1.5 C.Y. Required Strength (Lbs./sq.in.): 5,000 Specimen Measured Age Date Total Load Compressive Strength Remarks Number Slump (in.) (Days) Tested (Lbs.) (Lbs./Sq.ln.) CWT DR 1 3" 3 09/18/95 124,060 4,390 Unit weight: 144.4 lbs/cu.ft. CWT DR 2 3" 3 09/18/95 123,720 4,380 CWT DR 3 3" 7 09/22/95 137,900 4,880 CWT DR 4 3" 7 09/22/95 138,960 4,920 CWT DR 5 3" 28 10/13/95 150,100 5,310 CWT DR 6 3" 28 10/13/95 153,220 5,420 Test Methods Utilized Fracture Regular ASTM C-31,C-39,C-143 (Unless Noted Otherwise) I Cylinders Made By: D.S./W.I. Remarks and/or Distribution: cc: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendricks - Shimek, Jacobs and Finklea Mr. Gary Herron - RediMix Concrete ~EE Consultants, Inc. Reviewed by: All letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced without the full approval of GEE Consultants, Inc. The use of our name must receive our prior written approval. Our letters and reports apply only to the sample tested and/or impected and are not necessarily indicative of the quantities of apparently identical or similar products.