Mansions Phase 1-LR 981009 Rone Engineers. In(:. I ~--'t Goodnight Lane Tel. (972} 24i-451 Da;,as-For: '¢,~o.-'1n Dallas. Texas Metro (972) .-'~3-,555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 1 of 4 Report No: 3137-D7429-279 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 9, 1998 Location: Building # 23 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 1 S-59 So.West Comer 33K 5500 4 5/8 4 3/8 YES 2 B-59 West to East 33K 5500 4 5/8 4 1/4 YES 3 $-68 West to East 33K 5500 5 3/8 5 1/4 YES 4 $-96 West to East 33K 5500 7 I/2 7 1/4 YES 5 S-98.6 West to East 33K 5500 7 3/4 8 1/8 YES 6 S-98.6 West to East 33K 5500 7 3/4 7 3/4 YES 7 B-73.6 West to East 33K 5500 5 5/8 5 3/4 YES 8 S-100 West to East 33K 5500 7 718 7 5.."8 YES 9 S-100 West to East 33K 5500 7 7[8 7 3i4 YES 10 S-100 West to East 33K 5500 7 7/8 7 5i8 YES 11 B-73 West to East 33K 5500 5 5i8 5 5t'8 YES 12 S-96 West toEast 33K 5500 7 1/2 7 1/4 YES 13 S-96 West to East 33K 5500 7 I/2 7 I14 YES 14 S-96 West to East 33K 5500 7 1/2 7 1/2 YES 15 S-96 West to East 33K 5500 7 1/2 7 1/2 YES 16 S-98.6 West to East 33K 5500 7 3/4 7 5i8 YES 17 B-71.6 West to East 33K 5500 5 1,"2 5 5/8 YES 18 S-98.6 West to East 33K 5500 7 3/4 7 5/8 YES 19 S-98.6 West to East 33K 5500 7 3/4 7 3/4 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: * 9 Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; CiD' of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LI.\-IITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. Vee assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other l~ature of similar subject matter provided by persons or conditions over which we have no control. Our letters and repons are for the exclusive use of the clients to whom they are addressed. c:'..wpwin\reports\D7429-279-98'.PW October 12, 1998 Rone Engineers, Inc. 11 '-t Goodn,ght Lane Tel. RoneEncfineers J Da,las'Fo,1 Wc,z.h Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 2 of 4 Report No: 3137-D7429-279 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 12, 1998 Location: Building # 23 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 20 S-98.6 North South 33K 5500 7 3/4 7 1/4 YES 21 B-76 North South 33K 5500 6 6 3/4 YES 22 S- 12.6 North South 33K ~, 5500 7;8 1 1/8 YES 23 $-26 North South 33K 5500 2 2 YES 24 5-26 North South 33K 5500 2 2 1/4 YES 25 S-26 North South 33K 5500 2 1 7i8 YES 26 B-27 N.E. Comer 33K 5500 2 1/8 2 YES 27 S-27 East West 33K 5500 2 1/8 Z 7/8 YES 28 S-46 East West 33K 5500 3 5/8 3 318 YES 29 B-27 East West 33K 5500 2 1/8 2 YES 30 B-27 East to West 33K 5500 2 1/8 2 YES 31 B-27 East to West 33K 5500 2 I/8 2 YES 32 B-27 East to West 33K 5500 2 1/8 2 1/4 YES 33 $-55 East to West 33K 5500 4 1/4 3 7/8 YES 34 B-55 East to West 33K 5500 4 1/4 4 1/8 YES 35 B-65.5 East to West 33K 5500 5 1/8 4 3/4 YES 36 S-60.6 N.W. Comer 33K 5500 4 3/4 4 3/4 YES 37 $-59.6 North to South 33K 5500 4 5/8 4 5/8 YES 38 5-59.6 North to South 33K 5500 4 5/8 4 9/16 YES Equipment iD: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein *,'ere prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and repons are for the exclusive use of the clients to whom they are addressed. c:\wpwiw, repons~D7429-279-98'.PW October 12, 1998 Rone Eng'ineers. Inc. '' '--~ Goodn,ght Lane Te,. ~972) 241-45i---' RoneEnaineers i 2, a~.as..¢o,~ '.¢,/om- Dallas. Texas Me.:ro (9721! ~¢,'~ 1 .~ ~.'~- 75229 Fax (972) 241-517" ELONGATION REPORT Project: Mansions By The Lake Page 3 of 4 Report No: 3137-D7429-279 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 12, 1998 Location: Building # 23 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 B-59.6 North to South 33K 5500 4 5/8 4 5/8 YES 40 $-59.6 North to South 33K 5500 4 5/8 4 1/2 YES 41 $-62.6 North to South 33K ~_. 5500 4 7.:8 4 5/8 YES 42 $-62.9 North to South 33K 5500 4 7i8 4 5/8 YES 43 B-62.9 North to South 33K 5500 4 7/8 4 5/8 YES 44 $-59 North to South 33K 5500 4 5/8 4 1,:2 YES 45 S-59 North to South 33K 5500 4 5/8 4 5i8 YES 46 S-61.6 North to South 33K 5500 4 3/4 4 7..'8 YES 47 B-61.6 North to South 33K 5500 4 3/4 4 7/8 YES 48 S-61.6 North to South 33K 5500 4 3/4 4 7/8 YES 49 S-59.6 North to South 33K 5500 4 5/8 4 3/4 YES 50 S-61.6 North to South 33K 5500 4 3/4 5 YES 51 S-61.6 North to South 33K 5500 4 3/4 4 5/8 YES 52 S-59.6 North to South 33K 5500 4 5/8 4 5/8 YES 53 S-59.6 North to South 33K 5500 4 5/8 4 9."16 YES 54 S-67 North to South 33K 5500 5 1/4 5 1/2 YES 55 B-67 North to South 33K 5500 5 1/4 5 YES 56 S-67 North to South 33K 5500 5 1/4 4 7i8 YES 57 S-67 North to South 33K 5500 5 1/4 4 7/8 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (i) Mr. Tony Martin; Next-port Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMrFATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject maUer provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:\wpwin\reports\D7429-279-98',.PW October 12, 1998 Rone E'n~ineers. Inc. '..~ -- $ Goodnight Lane Tel. (972) 24'~-451--- ineers Da~,as. For: '/¢onr' Dallas. Texas Metro (972) '-'~q 40~-/bb.~ 75229 Fax' ~;241 ~97/j -5174 ELONGATION REPORT Project: Mansions By The Lake Page 4 of 4 Report No: 3137-D7429-279 Sample Date: October 8, 1998 Client: Western Rim Service Report Date: October 12, 1998 Location: Building # 23 Technician: R. Lovelady # Tendon Location .lack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1)' End (2) Elongations Tolerance 58 $-67 North to South 33K 5500 5 1/4 5 YES 59 B-67 North to South 33K 5500 5 1/4 5 1/4 YES 60 $-67 North to South 33K __ . 5500 5 1/4 4 15/16 YES 61 $-67 North to South 33K 5500 5 1/4 5 1/8 YES 62 $-59 North to South 33K 5500 4 5/8 4 1/2 YES 63 $-29.6 North to South 33K 5500 2 1/4 2 3/16 YES 64 B-29.6 North to South 33K 5500 2 1/4 2 3/16 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Sen'ices (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of CoppeLl (1) Mr. Tony Martin; Ne~v~ort Classic (1) Mr. Doyle Damron; C. D. Construction Consulting L~-IITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:".wpwin\reports~,D7429-279-98'.PW October 12, 1998