Loading...
Mansions Phase 1-LR 981009 (7) 3a:.as For: Wcrl,' Dallas, Texas ,Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 1 of 4 Report No: 3137-D7429-278 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 9, 1998 Location: Building # 1 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (I) End (2) Elongations To'.eranc¢ I S-59 North West 33K 5500 4 5;8 4 7/16 YES 2 B-59 North South 33K 5500 4 5/8 4 7/8 YES 3 S-68 North South 33K 5500 5 3/8 5 3/4 YES 4 S-96 North South 33K 5500 7 1/2 7 YES 5 S-98.6 North South 33K 5500 7 3/4 8 5/16 YES 6 S-98.6 North South 33K 5500 7 3/4 7 13/16 YES 7 B-73.6 North South 33K 5500 5 5/8 5 1/2 YES 8 S-100 North South 33K 5500 7 7/8 8 3/8 YES 9 S-100 North South 33K 5500 7 7/8 8 1/8 YES 10 S-100 North South 33K 5500 7 7/8 8 1/8 YES 11 17-73 North South 33K 5500 5 5/8 5 5/8 YES 12 S-96 North South 33K 5500 7 1/2 6 15/16 YES 13 S-96 North South 33K 5500 7 1/2 6 15/16 YES 14 S-96 North South 33K 5500 7 1/2 7 1/2 YES 15 S-96 North South 33K 5500 7 1/2 7 558 YES 16 S-98.6 North South 33K 5500 7 3/4 7 5i16 YES 17 B-71.6 North South 33K 5500 5 1/2 5 7."8 YES 18 $-98.6 North South 33K 5500 7 3/4 8 YES 19 S-98.6 North South 33K 5500 7 3;4 7 3;4 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific, samples provided for testing. We assume no responsibility for variation in qnality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:',.wpwin".reports'..D7429-278-98',PW October 12, 1998 · '°' RoneEn ineers Rone Engineers. Inc. ] ~, "- Goodmgh[ Lane TeL ~.~72j 24~-45;7 Oa,'as. For, Won', Dallas, Texas Metro (972) 263-i 555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 2 of 4 Report No: 3137-D7429-278 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 12, 1998 Location: Building # 1 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within [ No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 20 S-98.6 North South 33K 5500 7 3/4 7 3/8 YES 21 B-76 North South 33K 5500 6 6 YES 29-. S-12.6 North South 33K __. 5500 7/8 1 YES ~ S-26 North South 33K 5500 2 2 YES 24 S-26 North South 33K 5500 2 2 I/4 YES 25 S-26 North South 33K 5500 2 2 YES 26 B-27 South East 33K 5500 2 1/8 I 15/16 YES 27 S-27 South North 33K 5500 2 1/8 1 15i16 YES 28 S-46 South North 33K 5500 3 5/8 3 3/4 YES 29 B-27 South North 33K 5500 2 1/8 2 YES 30 B-27 South North 33K 5500 2 1/8 2 1/4 YES 31 B-27 South North 33K 5500 2 1/8 2 1/4 YES 32 B-27 South North 33K 5500 2 1/8 2 YES 33 5-55 South North 33K 5500 4 1/4 3 15/16 YES 34 B-55 South North 33K 5500 4 1.,'4 4 3/8 YES 35 B-65.5 South North 33K 5500 5 1/8 5 1...'8 YES 36 $-60.6 North East 33K 5500 4 3;4 5 YES 37 $-59.6 East West 33K 5500 4 5/8 4 5/8 YES 38 S-59.6 East West 33K 5500 4 5/8 4 5/8 YES Equipment iD: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Cormnents: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; Cit3,' of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LLMrrATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar su~ect matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom ~ey are addressed. c:',wpwin\reports\D7429-278-98:.PW October 12, 1998 RoneEn ineers Bone Engineers. Inc. i ~, --' '. Goodn~gnt Lane lei. ~c~ ~-. 2_--1.1-45 ;- Da,,as ~or:. 'A/oq~ Dallas. Texas Metro (972) 263-1555 75229 Fax {972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 3 of 4 Report No: 3137-D7429-278 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 12, 1998 Location: Building # 1 Technician: R. Lovelady # Tendon Location Jack Fore Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 B-59.6 East West 33K 5500 4 5/8 5 YES 40 S-59.6 East West 33K 5500 4 5/8 4 5/8 YES 41 S-62.6 East West 33K ~.. 5500 4 7/8 5 YES 42 S-62.9 East West 33K 5500 4 7/8 4 7/8 YES 43 B-62.9 East West 33K 5500 4 7/8 4 718 YES 44 S-59 East West 33K 5500 4 5i8 5 1/16 YES 45 S-59 East West 33K 5500 4 5/8 5 1/16 YES 46 $-61.6 East West 33K 5500 4 3/4 5 1/8 YES 47 B-61.6 East West 33K 5500 4 3/4 5 1/4 YES 48 $-61.6 East West 33K 5500 4 3/4 5 1/4 YES 49 $-59.6 East West 33K 5500 4 5/8 5 YES 50 S-61.6 East West 33K 5500 4 3/4 4 5/8 YES 51 S41.6 East West 33K 5500 4 3/4 5 1/4 YES 52 S-59.6 East West 33K 5500 4 5/8 5 1i8 YES 53 S-59.6 East West 33K 5500 4 5/8 4 7/8 YES 54 $-67 East x3,'est 33K 5500 5 1/4 4 15i16 YES 55 B-67 East x. Vest 33K 5500 5 1/4 5 1/2 YES 56 S-67 East West 33K 5500 5 1/4 5 1/2 YES 57 S-67 East West 33K 5500 5 1,:4 5 1/4 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Sec'ices (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City, of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LLMrrATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom the3' are addressed. c:w,.pwin'..reports~,D7429-278-98~..pw October 12, 1998 I~one I~ngmeers, Inc. -, a.e RoneEnqineers Ca,ms F-c,~ W'c-~ Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 4 of 4 Report No: 3137-D7429-278 Sample Date: October 8, 1998 Client: Western Rim Services Report Date: October 12, 1998 Location: Building # 1 Technician: R. Lovelady # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 58 S-67 East West 33K 5500 5 1/4 5 1/4 YES 59 B-67 East West 33K 5500 5 1/4 5 YES 60 S-67 East West 33K ~, 5500 5 1,'4 5 1/4 YES 61 $-67 East West 33K 5500 5 1i4 5 1/4 YES 62 S-59 East West 33K 5500 4 5/8 4 7/8 YES 63 $-29.6 East West 33K 5500 2 1/4 2 1/4 YES 64 B-29.6 East West 33K 5500 2 1/4 2 5/8 YES Equipment ID: Ram No: 93014 Pump No: 381996 Gauge No: 93014 Equipment Calibration Date: 9/4/98 Comments: Distribution: (I) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; CiD' of Coppell (i) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (i) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom lhey are addressed. c:X.wpwin~.reports\D7429-278-98'.PW October 12, 1998