Mansions Phase 1-LR 981006 (2) Dahas.-Fo~ Worth ~: Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 Concrete Cylinder Test Report Project Mansions By The Lake Purchase Order Number 3137-D7429-249 I Date of Observation 9/21,;98 Report Date 10...'06.-.'98 To Western Rim Services Contractor Supplier LATTIMORE Plant 6 I Truck 806 I Ticket 6080566 Location B,UILDING #17 - 25' EAST, 40' SOUTH FROM NORTHWEST CORNER OF BUILDING Time Sampled 8:05 Time Batched 7:55 Weather Condition CLEAR Concrete Temperature (°F) 83 Ambient Temperature (°F) 74 Mix Number 51 Mix Description Unit Weight Water Added NONE Physical Data ACTUAL SPECIFICATIONS SLUMP (in.) 4 1/2 Concrete Cylinder Test(s) No. (Days) (lbs.) Strength (psi) Strength Required (psi) 109A 7 9/28 76000 2690 3000/28 DAYS B 28 10/19 C 28 10/19 D H I I Curing Method I Test Method I Standard 6" x 12" Engineer/Technician R. LOVELADY ASTM C 31 I ASTM C 39_ I Area 28.27 sq. in. S~gnature: Mike Fuller, AET (Ir) Supervisor, CMT Remarks and/or Distribution -- Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting L:MITATIONS: The test results presented hereto were prepared based upon the specific samples prowded for testing. We assume no responsibility for variation in quaiity (composition, appearance, performance, etc.) or any other feature of s~milar subject matter provided by persons or conditions over ,,'vh~ch we have no control. Our letters and reports are for the exci[;swe rise of ;he clients to whom they are adcressee. c:'.wp',;,m-.reports.D7429-249-98'.ST October 6, ~ 998