Mansions Phase 1-LR 980917 (4) Rone Engineers, Inc. 1123/~-~oodnight Lane Tel. (972) 241-4517 -- RoneEnQineers Dadas.'Foc Wo"lh Dallas, Texas Metro f(~72j' 263-I 555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 1 of 4 Report No: 3137-D7429-240 Sample Date: September 10, 1998 Client: Western Rim Services Report Date: September 17, 1998 Location: Slab on Grade//19 Technician: K. Mustafa # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (I) End (2) Elongations Tolerance I S-27 South 33K 5500 2 I/8 I 3/4 NO 2 S-27 South 33K 5500 2 1/8 1 3/4 NO 3 B-27 South 33K 5500 2 1/8 1 7/8 NO 4 B-29 North 33K 5500 2 1/4 1 3/4 NO 5 S-29 North 33K 5500 2 1/4 1 3/4 NO 6 S-48 North 33K 5500 3 3/4 3 5/8 YES 7 B-30 North 33K 5500 2 3/8 I 3/4 NO 8 B-30 North 33K 5500 2 3/8 1 3/4 NO 9 B-30 North 33K 5500 2 3/8 2 NO 10 B-30 North 33K 5500 2 3/8 2 NO 11 B-57 West 33K 5500 4 1/2 3 3/4 NO 12 $-57 West 33K 5500 4 1/2 4 1/4 YES 13 B-78 North 33K 5500 6 1/8 4 1/2 NO 14 S-63 West 33K 5500 4 7/8 3 7/8 NO 15 S-62 West 33K 5500 4 7/8 4 1/8 NO 16 S-62 West 33K 5500 4 7/8 4 3/4 YES 17 S-62 West 33K 5500 4 7/8 4 3/4 YES iR [ 3-62 West 33K 5500 4 7/8 4 3/4 YES 19 Is-65 west 33K 5500 5 I/8 4 3/4 YES Equipment ID: Ram No: 94016 Pump No: 380794 Gauge No: 940375 Equipment Calibration Date: 8/24/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LLMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no covaxol. Our letters and reports are for the exclusive use of the clie.nts to whom they are addressed. ~ c:',wpwin\reports\D7429-240-98\ST September 17, 1998 ' Bone Engineers, Inc. 1127~goodn,ght Lane : Tel. (972) 241-4517 -- RoneEnaineers i oa,~as..'ro¢, woc, n Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 2 of 4 Report No: 3137-D7429-240 Sample Date: September 10, 1998 Client: Western Rim Services Report Date: September 17, 1998 Location: Slab on Grade//19 Technician: K. Musrafa I # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongatiom End (1) End (2) Elongatiom Tolerance 20 5-65 West 33K 5500 5 1/8 4 314 YES 21 B-65 West 33K 5500 5 1/8 4 3/4 YES 22 S-6! West 33K 5500 4 314 4 1/2 YES 23 S-61 West 33K 5500 4 3/4 4 1/2 YES 24 B-64 West 33K 5500 5 Blew Out 25 S-64 West 33K 5500 5 Blew Out 26 S-64 West 33K 5500 5 4 7/8 YES 27 $-62 West 33K 5500 4 7/8 4 314 YES 28 S-64 West 33K 5500 5 4 3/4 YES 29 B-64 West 33K 5500 5 4 1/2 YES 30 S-62 West 33K 5500 4 7/8 4 1/2 YES 31 S-62 West 33K 5500 4 7/8 4 3/4 YES 32 B-69 West 33K 5500 5 3/8 5 YES 33 S-69 West 33K 5500 5 3/8 5 YES 34 S-69 West 33K 5500 5 3/8 5 YES 35 S-69 West 33K 5500 5 3/8 5 YES 36 B-69 West 33K 5500 5 3/8 5 YES 37 S-69 West 33K 5500 5 3/8 5 YES I 38 S-69 West 33K 5500 5 3/8 5 I YES Equipment ID: Ram No: 94016 Pump No: 380794 Gauge No: 940375 Equipment Calibration Date: 8/24/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (I) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Dam. ton; C. D. Construction Consulting LIMITATIONS: The test results presenu~d herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are address~. c:\wpwin\reports\D7429-240-98\ST September 17, 1998 Rone Engineers, Inc. l123~oodnight Lane TeL (972) 241-4517 -- RoneEn_qineers Da!ias-For:. Wcr:,.~ Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 3 of 4 Report No: 3137-D7429-240 Sample Date: September 10, 1998 Client: Western Rim Services Report Date: September 17, 1998 Location: Slab on Grade #19 Technician: K. Mustafa # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 S-69 West 33K 5500 5 3/8 4 1/2 NO 40 S-61 West 33K 5500 4 3/4 4 I/2 YES 41 B-32 West 33K 5500 2 1/2 2 NO 42 S-32 West 33K 5500 2 1/2 2 NO 43 S-6I South 33K 5500 4 3/4 4 1/2 YES 44 B-61 South 33K 5500 4 3/4 Blew Out 45 S-70 South 33K 5500 5 1/2 5 1/4 YES 46 S-98 South 33K 5500 7 518 6 314 NO 47 S-101 South 33K 5500 7 7/8 7 3/8 YES 48 S-101 South 33K 5500 7 7/8 7 3/8 YES 49 B-75 South 33K 5500 5 7/8 5 1/2 YES 50 S-102 South 33K 5500 8 7 NO 51 S-102 South 33K 5500 8 7 NO 52 S-102 South 33K 5500 8 7 1/8 NO 53 B-76 South 33K 5500 6 5 3/4 YES 54 S-98 South 33K 5500 7 5/8 6 3/4 NO 55 S-98 South 33K 5500 7 5/8 6 3/4 NO 56 S-98 South 33K 5500 7 5/8 6 3/4 NO 57 S-98 South 33K 5500 7 5/8 6 3/4 NO Equipment ID: Ram No: 94016 Pump No: 380794 Gauge No: 940375 Equipment Calibration Date: 8/24/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presenmd herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:\wpwin\reports\D7429-240-98\ST September 17. 1998 'R~ne I~ngineers, Inc. 1123"--%oodnight Lane Tel. (972) 241-4517 -- RoneEnc ineers Dal,,:-s..'For: VVodh Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page 4 of 4 Report No: 3137-D7429-240 Sample Date: September 10, 1998 Client: Western Rim Services Report Date: September 17, 1998 Location: Slab on Grade//19 Technician: K. Mustafa # Tendon Locadon Jack Force Gauge Required Elongations Elongadons Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 58 S-101 South 33K 5500 7 7/8 5 1/2 NO 59 B-74 South 33K 5500 5 3/4 7 1/8 NO 60 S-101 South 33K 5500 7 7/8 7 1/2 YES 61 S-101 South 33K IS500 7 7/8 7 1/2 YES 62 S-101 South 33K 5500 7 7/8 7 1/2 YES 63 B-79 South 33K 5500 6 118 5 118 NO 64 S-15 East 33K 5500 I I/8 3/4 NO Equipment ID: Ram No: 94016 Pump No: 380794 Gauge No: 940375 Equipment Calibration Date: 8/24/98 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (I) Mr. Larry Davis; City of Coppell (i) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no contxol. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:'~wpwin\reports\D7429-240-98\ST September 17, 1998