Loading...
WA9302-LR 951009 (3) I'~'EOTECHNICAL E GEE Consultants, inc. E I NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 · Fax (214) 620-9794 REPORT OF CONCRETE MIX INSPECTION Report Date: October 9, 1995 Date Concrete Placed: September 6, 1995 Standard 6"x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank Concrete ReportNo.: 5 Contractor: Natgun Construction Project No.: 95- 0196 Concrete Supplier and Plant: RediMix Concrete - 12 1 Plant Location of Placement: P i e r s REVI S ED MATER IAL S s ...../ Batch wt,. Description (lbs./0.075 C.V> INSPECTION DATA Mix Number: #686 Time Sample Batched: 10:15 am Cement: Time Sampled: 11:20 am Fly Ash: Sample Location: Pier T.2-11.4 Truck/Ticket N o: 116! 19924 Coarse Aggregate: Temperature: Intermediate Aggregate: Ambient Range: 68°F Fine Aggregate: Concrete Range: 74°F Admixtures: Slump Range (inches): 3~" Weather Conditions: Partly Cloudy 1 Time Started: 7:30 am 2 Time Completed: 5:45 pm Added Water: 10 gal. Sample Air Content (%): No Test Total Cubic Yards Placed: 15.0 C.Y. Required Strength (Lbs./sq.in.): 4,000 Specimen Measured Age Date Total Load Compressive Strength Remarks Number Slump (in.) (Days) Tested (Lbs.) (Lbs./Sq.ln.) CWT 21 3~ 7 09/13/95 102,420 3,620 CWT 22 3~ 7 09/13/95 107,900 3,820 CWT 23 3~ 28 10/04/95 130,620 4,620 CWT 24 33~ 28 10/04/95 138,460 4,900 Test Methods Utilized Fracture Regular Cylinders Made By: Geetha ASTM C-31,C-39,C-143 (Unless Noted Otherwise) Remarks and/or Distribution: cc: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendricks - Shimek, Jacobs and Finklea Mr. Gary Herron - RediMix Concrete '/~J A GEE Consultants, Inc, Reviewed by: - All letmrs and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced without the full approval of GEE Consultants, Inc. The use of our name must receive our prior written approval. Our letters and reports apply only to the sample tested and/or inspected and are not necessarily indicative of the quantities of apparently identical or similar products.