Loading...
Mansions Phase 1-LR 980526 (2) ~on~ ~ng{n=~:rs, ~nc. '~ '~,-1-q4 Goodnight Lane ,' TeL (972/ 241-45~ 7--. RoneEnnineers Dallas..'Fort Worth Dallas, Texas Metro (972) 263-1 75229 Fax (972) 241-5174 Concrete Cylinder Test Report Prolect Mansion By The Lake P~rc.qase Order Number 3137-D7429-119 Date of Observation 3.,'27/98 Report Date 05:26;98 To Western Rim Services Location BUILDING //40, NORTHEAST END, 10' WEST, 4' SOUTH Contractor Supplier LATTIMORE Plant 6 ]Truck454 Ticket 6068997 Time Sampled 7:30 Time Batched 7:20 Weather Condition C'.oudy..'Rain Concrete Temperature (°F) 62 Ambient Temperature (;'F) 72 Mix Number ; 4 Mix Description 4.50 SACKS W/R Unit Weight Water Aoded NONE Physical Data ACT UAL SPECI FI CATI O NS SLUMP (in.) 5.0 Concrete Cylinder Test(s) No. (Days) Test Date (lbs.) Strength (psi) Strength Required (psi) 66A 7 4/03 39500 1400 3000/28 DAYS B 28 4/24 62000 2190' C 28 4/24 69000 2440* D 56 5/22 92500 3270 ASTM C 31 ASTM C 39 Area 28.27 sq. in. Signature: Mike Fuller //'~ Supervisor, CMT Remarks and/or Distributio Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Mike Hodge; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS. The test results presented herein; were prebared aased upon the specific samples provided for testing. We assume no responsibility for variation in quaiity icomposition, abpearance, performance, etc.) or an~,. other featbre of simp.ar subject matter provided by persons or conditions over which we have oo control. Obr letters and reports are for the exclusive [Ise of the ciieots to w~om they are a(]dressed. c:'.vpw.~treports.D7429-1;9-98'ST May 26. ;998