ELONGATION REPORT
Project: Mansions By The Lake Page 1 of 1
Report No: 3137-D7429-360 Sample Date: May 4, 1999
Client: Western Rim Services Report Date: May 17, 1999
Location: Building//12- Restress Technician: T. Duke
# Tendon Locadon Jack Force Gauge Required Elongations Elongations Total Within
No. (KiI~) Pressure Elongations End (1) End (2) Elongations Tolerance
4 B-30 South Side 2.125 1.75 .25 2.0 YES
5 S-101 South Side 7.5 7.0 .5 7.5 YES
8 B-30 East Side 2.125 1.75 0 1.75 *N/C
52 B-76 North Side 5.875 4.25 0 4.25 *N/C
59 S-101 North Side 7.875 7.0 .5 7.5 YES
B-78 East Side 6.0 5.375 0 5.375 *
Equipment ID: Ram No: 38077 Pump No: .380005 Gauge No: 380005
Equipment Calibration Date: 1/20/99
Comments: *Contractor pulled cable to 8200 PSI, N/C (No Change) was noted.