Mansions Phase 1-LR 980504 (7) Dallas:Fort Worth Dallas. Texas . Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page: 1 of 4 Report No: 3137-D7429-146 Sample Date: April 8, 1998 Client: Western Rim Services Report Date: May 4, 1998 Location: Building #37 Technician: T. Duke ff Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 1 B29 North Side 33K 7800 2 1/8 2 1i8 Y 2 S29 North Side 33K 7800 2 1/8 2 1/8 Y 3 S48 North Side 33K 7800 3 518 3 1/2 Y 4 B30 North Side 33K 7800 2 2/8 2 1/4 Y 5 B30 North Side 33K 7800 2 2/8 2 1/2 Y 6 B30 North Side 33K 7800 2 2/8 2 3/8 Y 7 B30 North Side 33K 7800 2 2/8 2 1/4 Y 8 B57 North Side 33K 7800 4 3/8 4 1/2 Y 9 S57 North Side 33K 7800 4 3/8 4 3/8 Y 10 B78 North Side 33K 7800 6 5 3/4 Y 11 S63 West Side 33K 7800 4 7/8 5 Y 12 S62 West Side 33K . 7800 . 4 3/4 4 3/4 Y 13 B62 West Side 33K 7800 4 3/4 4 3/4 Y 14 S62 West Side 33K 7800 4 3/4 4 5/8 Y 15 S62 West Side 33K 7800 4 3/4 5 Y 16 S65 West Side 33K 7800 5 5 Y 17 B65 West Side 33K 7800 5 5 1/4 Y 18 S65 West Side 33K 7800 5 5 Y 19 S61 West Side 33K 7800 4 5;8 4 3/4 Y :quipment ID: Ram No: Pump No: Gauge No: Equipment Calibration Date: Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (i) Mr. Lee Stone; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LLMFFATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or an)' other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they' are addressed. z:\wpwin\reports\D7429-146-98\SH May 4, 199~'~ ~ Rone Engineers, Inc. ~"'~34 Goodnight Lane Tel. (972) 241-45~-''' ineers ! Dallas.-'Fo~ Worn Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page: 2 of 4 Report No: 3137-D7429-146 Sample Date: April 8, 1998 Client: Western Rim Services Report Date: May 4, 1998 Location: Building #37 Technician: T. Duke # Tendon Location Jack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 20 S61 West Side 33K 7800 4 5!8 4 3/4 Y 21 B64 West Side 33K 7800 4 7;8 4 3/4 Y 22 S64 West Side 33K 7800 4 7/8 5 1i8 Y 23 S64 West Side 33K 7800 4 7/8 5 Y 24 S62 West Side 33K 7800 4 3/4 4 7/8 Y 25 S64 West Side 33K 7800 . 4 7/8 4 7/8 Y 26 B64 West Side 33K 7800 4 7/8 4 3/4 Y 27 S62 West Side 33K 7800 4 3/4 5 Y 28 S62 West Side 33K 7800 4 3/4 5 Y 29 B69 West Side 33K 7800 5 1/4 5 1/4 Y 30 S69 West Side 33K 7800 5 1/4 5 1/8 Y 31 S69 West Side 33K 7800 5 I/4 5 3/8 Y 32 S69 West Side 33K 7800 5 1/4 5 1/4 Y 33 B69 West Side 33K 7800 5 I/4 5 Y 34 S69 West Side 33K 7800 5 1/4 5 1/8 Y 35 S69 West Side 33K 7800 5 1/4 5 Y 36 569 West Side 33K 7800 5 114 5 U8 Y 37 S61 West Side 33K 7800 4 5/8 5 Y Equipment ID: Ram No: Pump No: Gauge No: Equipment Calibration Date: Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMrrATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject maUer provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. z:~.wpwin\reports\D7429-146-98\SH May 4, 1998 Oal,as..'Fort Wo~h Dallas, Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page: 3 of 4 Report No: 3137-D7429-146 Sample Date: April 8, 1998 Client: Western Rim Services Report Date: May 4, 1998 Location: Building//37 Technician: T. Duke # Tendon Location lack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 S32 West Side 33K 7800 2 3/8 2 3/8 Y 40 S61 South Side 33K 7800 4 5/8 4 1/2 Y 41 B61 South Side 33K 7800 4 5/8 4 9/16 Y 42 S70 South Side 33K 7800 5 3/8 5 3/8 Y 43 S98 South Side 33K 7800 7 5/8 7 5/8 Y 44 S101 South Side 33K 7800 7 7/8 8 Y 45 S101 South Side 33K 7800 7 7/8 7 5/8 Y 46 1t75 South Side 33K 7800 5 3/4 5 3/4 Y 47 S102 South Side 33K 7800 7 7/8 8 Y 48 S102 South Side 33K 7800 7 7/8 8 114 Y 49 S102 South Side 33K 7800 7 7/8 8 Y 50 B76 South Side 33K 7800 5 7/8 5 3/4 Y 51 598 South Side 33K 7800 7 5/8 7 3/4 Y 52 S98 South Side 33K 7800 7 5/8 7 1;2 Y 53 S98 South Side 33K 7800 7 5/8 7 1/2 Y 54 S98 South Side 33K 7800 7 5/8 7 1/2 Y 5.5 S101 South Side 33K 7800 7 7/8 7 3/4 Y 56 B74 South Side 33K 7800 5 3/4 5 1/2 Y 57 Sl01 South Side 33K 7800 7 7/8 7 3/4 Y Equipment ID: Ram No: Pump No: Gauge No: Equipment Calibration Date: Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Seawices (1) Mr. Larry Davis; City of Copper (I) Mr. Lee Stone; Ci.ty of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LRVlITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are tbr the exclusive use of the clients to whom they are addressed. ¢:',wpwin\reports\D7429-146-98\SH May 4, 1998 Rone Engineers, Inc. "'-"'34 Goodnight Lane Tel. (972) 241-45'"'" R°neEnalineersl Da~las,-'For~ Worth Dallas, Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansions By The Lake Page: 4 of 4 Report No: 3137-D7429-146 Sample Date: April 8, 1998 Client: Western Rim Services Report Date: May 4, 1998 Location: Building #37 Technician: T. Duke # Tendon Location Jack Force Gauge Required Elongations Elongations Total Wi{hin No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 58 SI01 South Side 33K 7800 7 7/8 7 3/4 Y 59 SI01 South Side 33K 7800 7 7/8 7 7/8 Y 60 B79 South Side 33K 7800 6 1/8 6 3/8 Y 61 S15 South Side 33K 7800 1 1 Y 62 S27 South Side 33K 7800 2 2 Y 63 S27 South Side 33K 7800 2 2 Y 64 B27 South Side 33K 7800 2 2 Y Equipment ID: Ram No: Pump No: Gauge No: Equipment Calibration Date: Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City. of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMFFATIONS: The test results presented herein sa, ere prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:\wpwin\reports\D742998\SH May 4, 1998