Mansions Phase 1-LR 980423 (3) .one Engineers, Inc. 1 ~-'~4 Goodnight Lane Tel. (972) 241-451''~'''. RoneEnc ineers
J
Dallas/Fort Worth Dallas, Texas Metro (972) 263-1555
75229 Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page: 1 of 4
Report No: 3137-D7429-140 Sample Date: April 7, 1998
Client: Western Rim Services Report Date: April 23, 1998
Location: Building #44 Technician: T. Duke
# Tendon Location Jack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance
I B29 East Side 33K 2 1/8 2 ti16 Y
2 529 East Side 33K 2 1/8 2 1/8 Y
3 S48 East Side 33K 3 5/8 3 1/2 Y
4 B30 East Side 33K 2 2/8 2 I/2 Y
5 B30 East Side 33K 2 2/8 2 I/4 Y
6 B30 East Side 33K 2 2/8 2 3/8 Y
7 B30 East Side 33K 2 2/8 2 1/2 Y
8 B57 East Side 33K 4 3/8 4 1/2 Y
9 $57 East Side 33K 4 3/8 4 1/8 Y
10 B78 East Side 33K 6 5 3/4 Y
11 S63 North Side 33K 4 7/8 4 3/4 Y
12 S62 North Side 33K 4 3/4 4 5/8 Y
13 1562 North Side 33K 4 3/4 4 3/4 Y
14 S62 North Side 33K 4 3/4 4 5/8 Y
15 S62 North Side 33K 4 3/4 4 7/8 Y
16 S65 North Side 33K 5 5 1/4 Y
17 B65 North Side 33K 5 5 Y
18 S65 Noah Side 33K 5 5 1/8 Y
19 S61 North Side 33K 4 5/8 4 3/4 Y
~quipment ID: Ram No: Pump No: Gauge No:
Equipment Calibration Date:
Comments: Cable's were already pulled, so no visual was performed on buildings//44, 42, 34, 43 & 29.
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Lee Stone; City. of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no
responsibility for variation in quality (composition, appearsnee, performance, em.) or any other feature of similar subject matter provided by
persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are
addressed.
c:\wpwin\reports\D7429-14098\SH April 23, 1998 ~('~"~J
Rone Engineers, Inc. 1~'-'~4 Goodn,ght Lane Tel. (972) 241-451'~" RoneEnaineers
Dallas/Fort Worth Dallas, Texas Metro (972) 263-1555
75229 : Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page: 2 of 4
Report No: 3137-D7429-140 Sample Date: April 7, 1998
Client: Western Rim Services Report Date: April 23, 1998
Location: Building//44 Technician: T. Duke
# Tendon Ix)cation Jack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance
20 S61 North Side 33K 4 5/8 4 9/16 Y
21 B64 North Side 33K 4 7/8 4 3/4 Y
22 S64 North Side 33K 4 7/8 5 Y
~-3 S64 North Side 33K 4 7/8 4 7/8 Y
24 S62 North Side 33K 4 3/4 4 7/8 Y
°_5 S64 North Side 33K 4 7/8 4 9/16 Y
26 B64 North Side 33K 4 7/$ 4 3/4 Y
27 S62 Notxh Side 33K 4 3/4 4 7/8 Y
28 S62 North Side 33K 4 3/4 5 Y
29 B69 North Side 33K 5 1/4 5 1/4 Y
30 s69 Notch Side 33K 5 1/4 5 1/4 Y
31 S69 North Side 33K 5 1/4 5 1/2 Y
32 S69 North Side 33K 5 1/4 5 3/4 Y
33 B69 Nooh Side 33K 5 1/4 5 3/8 Y
34 S69 Noilh Side 33K 5 1/4 5 1/2 Y
35 S69 North Side 33K 5 1/4 5 1/8 Y
36 869 Not*.h Side 33K 5 1/4 5 1/4 Y
37 S61 No~h Side 33K 4 5/8 4 3/4 Y
38 B32 North Side 33K 2 3/8 2 1/4 Y
Equipment ID: Ram No: Pump No: Gauge No:
Equipment Calibration Date:
Comments:
Distribution:
(1) Mr. Richard E. Simmons; West. em Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Lee Stone; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no ;ontrol.
Our letters and repons are for the exclusive use of the clients to whom they are addressed.
c:\wpwin\rcpons\D7429-14098\SH April 23, 1998
, i
!' Rone Engineers, Inc. 1 ~-'~4 Gooclnight Lane Tel. (972) 241-451"~" RoneEnaineers
Dallas/Fort Worlh Dallas, Texas Metro (972) 263-1555
75229 Fax (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page: 3 of 4
Report No: 3137-D7429-140 Sample Date: April 7, 1998
Client: Western Rim Services Report Date: April 23, 1998
Location: Building #44 Technician: T. Duke
# Tendon Location Jack Forge Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations ~nd (1) End (2) Elongations Tolerance
39 $32 North Side 33K 2 3/8 2 3/8 Y
40 S61 West Side 33K 4 5/8 4 3/4 Y
41 1161 West Side 33K 4 5/8 4 5/8 Y
42 S70 West Side 33K 5 3/8 6 Y
43 S98 West Side 33K 7 5/8 8 1/4 Y
44 SI01 West Side 33K 7 7/8 8 1/4 Y
45 S101 West Side 33K 7 7/8 7 3/4 Y
46 B75 West Side 33K 5 3/4 6 1/2 Y
47 S102 West Side 33K 7 7/8 8 3/8 Y
48 S102 West Side 33K 7 7/8 8 1/4 Y
49 S102 West Side 33K 7 7/8 8 1/2 Y
50 B76 West Side 33K 5 7/8 6 Y
51 S98 West Side 33K 7 5/8 ** See note
52 S98 West Side 33K 7 5/8 ** See note
53 S98 West Side 33K 7 5/8 ** Sec note
54 S98 West Side 33K 7 5/8 ** See note
55 S101 West Side 33K 7 718 ** Sc¢ note
56 B74 West Side 33K 5 3/4 ** See note
57 S101 West Side 33K 7 7/8 ** See note
Equipment ID: Ram No: Pump No: Gauge No:
Equipment Calibration Date:
Comments: ** Under concrete drive.
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Lee Stone; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or :onditions over which we have no control.
Our letters and reports are for thc exclusive use of the clients to whom they are addressed.
c:\wpwin\repor~s\D7429-14098\SH April 23, 1998
Rone Engineers, Inc. 1 ~"~4 Goodnight Lane Tel. (972) 241-451~ ineers
Dallas;Fort Worth Dallas, Texas Metro (972) 263-1555
75229 F~ (972) 241-5174
ELONGATION REPORT
Project: Mansions By The Lake Page: 4 of 4
Report No: 3137-D7429-140 Sample Date: April 7. 1998
Client: Western Rim Services Report Date: April 23, 1998
Location: Building//44 Technician: T. Duke
# Tendon Location Jack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolcranc~
58 S101 West Side 33K 7 7/8 ** See note
59 S101 West Side 33K 7 7/8 7 3/4 Y
60 B79 West Side 33K 6 1/8 6 1/8 Y
61 S15 West Side 33K I I Y
62 S27 West Side 33K 2 I 15/16 Y
63 S27 West Side 33K 2 2 1/16 Y
64 B27 West Side 33K 2 2 Y
Equipment ID: Ram No: Pump No: Gauge No:
Equipment Calibration Date:
Comments: ** Under concrete drive.
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Copper
(1) Mr. Le~ Stone; City of Copper
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting
LIMITATIONS: Tho test results presented herein were prepared based upon the specific samplos provided for testing. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control.
Our letters and reports are for the exclusive usc of tho clients to whom they are addressed.
c:\wpwin\reports\D742998\SH April 23, 1998