Loading...
WA9302-LR 950929 (5) 'EOTECHNICAL E GEE Consultants, Inc. E [ NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 · Fax (214) 620-9794 REPORT OF CONCRETE MIX INSPECTION Report Date: September 2 9, '199S Date Concrete Placed: August 28, 3_995 Standard 6'x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank Concrete Repo~No.: 1 Contractor~ Nat~un Construction Proj~c~ No.: 95- 0196 Concrete Supplier and P]antz RediMix Concrete - 121 Plant Location of P|acement: Piers B-13, A.5-14.2, A.2-13.4 REVISED MAT ER IAL S s ..... / Batch Wt~. ~scriptio. <,bs./0.07s c.¥> INSPECTION DATA Mix Number: #686 Time Sampl~ Batched: 2:]0 pm Cement: Time Sampled: 3: 10 pm Fly Ash: Sample Location: Pier B-13 Truck/Ticket No: 124/19377 Coarse Aggregate: Temperature: Intermediate Aggregate: Ambient Range: 100°F Fine Aggregate: Concrete Range: 95°F Admixtures: Slump Range (inches): 4'/~" Weather Conditions: Clear 1 AEA Time Started: 1:00 pm 2 Time Completed: 6:00 pm Added Water: 15 gal. Sample Air Content (%): No test Total Cubic Yards Placed: 9.0 C.Y. Required Strength (Lbs./sq.in.): 4,000 specimen Measured Age Date Tota~ Load Compressive Strength Remarks Number Slump (in.) (Days) Tested (Lbs.) (Lbs./Sq.h'h) CWT 1 4~ 3 08/31/95 119,940 3,250 CWT 2 45~ 3 08/31/95 89,500 3,170 CWT 3 4~ 5 09/02/95 91,180 3,230 CWT 4 45~ 5 09/02/95 98,240 3,480 CWT 5 45~ 7 09/05/95 103,200 3,650 CWT 6 4~ 7 09/05/95 104,280 3,690 CWT 7 ~ 4x~ 28 09/25/95 122,080 4,320 ~ CWT 8 45~ 28 09/25/95 130,880 4,630 Test Methods Utilized Fracture Regular ASTM C~31,C-39,C-143 (Unless Noted Otherwise) Cylinders Made By: D.S. Remarks and/or Distribution: cc: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendricks - Shimek, Jacobs and Finklea Mr. Gary Herron - RediMix Concrete ~{/C}~/__./ GEE Consultants, Inc. Reviewed by: All letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced without the full approval of GEE Consultants, Inc. The use of our name must receive our prior written approval. Our letters and reports apply only to the sample tested and/or respected al~ are not necessarily indicative of the quantities of apparently identical or similar products,