Loading...
Mansions Phase 1-LR 980331 Rone Engineers, Inc. ~ .34 Goodnight Lane Tel. (972) 241-45. RoneEngineers Dallas;Fort Worth Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5~,74 ELONGATION REPORT Project: Mansion By The Lake Page 1 of 4 Report No: 3137-D7429-113 Sample Date: March 25, 1998 Client: Western Rim Services Report Date: March 31, 1998 Location: Building//27 Technician: Tim Duke # Tendon Location Jack Fom¢ Gauge Required Elongations Eloagations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance I B-29 SOUTH SIDE 33K 7800 2 1/8 2 YES 2 S-29 SOUTH SIDE 33K 7800 2 1/8 2 YES 3 S-48 SOUTH SIDE 33K 7S00 3 5/8 3 1/2 YES 4 15-30 SOUTH SIDE 33K 7800 2 2/8 2 YES 5 B-30 SoLFrH SIDE 33K 7800 2 2/8 2 1/2 YES 6 B-30 SOUTH SIDE 33K 7800 2 2/8 2 1/4 YES 7 B-30 SOUTH SIDE 33K 7800 2 2/8 2 1/4 YES 8 B-57 SOUTH SIDE 33K 7800 4 3/8 4 1/4 YES 9 S-57 SOUTH SIDE 331( 7800 4 3/8 4 1/2 YES I0 B-78 SOUTH SIDE 33K 7800 6 5 1/2 YES 11 S-63 EAST SIDE 33K 7800 4 7/8 5 1/8 YES 12 S-62 EAST SIDE 33K 7800 4 3/4 5 1/4 YES 13 15-62 EAST SIDE 33K 7800 4 3/4 5 1/4 YES 14 S-62 EAST SIDE 33K 7800 4 3/4 5 1/4 YES 15 S-62 EAST SIDE 33K 7800 4 3/4 4 7/8 YES 16 S-65 EAST SIDE 33K 7800 5 4 3/4 YES 17 B-65 EAST SIDE 33K 7800 5 5 YES 18 S-65 EAST SIDE 33K 7800 5 4 7/8 YES 19 $-61 EAST SIDE 33K 7800 4 5/8 4 5/8 YES ~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077 Equipment Calibration Date: 5/13/97 Comments: Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City of Coppell (I) Mr. Tony Martin; Newport Classic (I) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The lest results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c:\wpwin\reports\D7429-113-gg~ST March 31, 1998 (~/lt.~ Rone Engineers, Inc. 1 .._54 Goodnight Lane Tel. (972) 241-45'1. ineers Dallas/Fort Wodh Dallas. Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansion By The Lake Page 2 of 4 Report No: 3137-D7429-113 Sample Date: March 25, 1998 Client: Western Rim Services Report Date: March 31, 1998 Location: Building//27 Technician: Tim Duke # Tendon Location Jack Force Gauge Required Elongations Elongations Total Wid~in No. (Kips) Pressure Elongations End (I) End (2) Elongations Tolerance 20 S-61 EAST SIDE 33K 7800 4 5/8 4 9/16 YES 21 B-64 EAST SIDE 33K 7800 4 7/8 5 1/8 YES 22 S-64 EAST SIDE 33K 7800 4 718 4 13/16 YES 23 S-64 EAST SIDE 33K 7800 4 7/8 4 7/8 YES 24 S-62 EAST SIDE 33K 7800 4 3/4 4 3/4 YES 25 S-64 EAST SIDE 33K 7800 4 718 4 13/16 YES 26 B-64 EAST SIDE 33K 7800 4 7/8 5 1/8 YES 27 S-62 EAST SIDE 33K 7800 4 3/4 4 5/8 YES 28 S-62 EAST SIDE 33K 7800 4 3/4 4 15/16 YES 29 B-69 EAST SIDE 33K 7800 5 1/4 5 1/2 YES 30 S-69 EAST SIDE 33K 7800 5 1/4 5 1/2 YES 31 S-69 EAST SIDE 33K 7800 5 1/4 5 3/8 YES 32 S-69 EAST SIDE 33K 7800 5 1/4 5 5/8 YES 33 B-69 EAST SIDE 33K 7800 5 1/4 5 1/4 YES 34 S-69 EAST SIDE 33K 7800 5 114 5 1/8 YES 35 S-69 EAST SIDE 33K 7800 5 1/4 5 1/8 YES 36 S-69 EAST SIDE 33K 7800 5 1/4 5 1/4 YES 37 S-61 EAST SIDE 33K 7800 4 5/8 4 7/8 YES 38 B-32 EAST SIDE 33K 7800 2 3/8 2 1/4 YES ~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077 Equipment Calibration Date: 5/13/97 Comments: Distribution: (1) Mr. Richard E. Simmons; Westera Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: Thc mst results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, crc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of thc clients to whom they arc addressed. c:\wpwin\reports\D7429-113-98\5T March 31, 1998 Dallas/Forl Worth Dallas, Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansion By The Lake Page 3 of 4 Report No: 3137-D7429-113 Sample Date: March 25, 1998 Client: Western Rim Services Report Date: March 31, 1998 Location: Building//27 Technician: Tim Duke # Tendon Location Jack Force Oauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance 39 S-32 EAST SIDE 33K 7800 2 3/8 2 1/4 YES 40 S-61 NORTH SIDE 33K 7800 4 5/8 4 3/4 YES 4] B-61 NORTH SIDE 33K 7800 4 5/8 4 3/4 YES 42 S-70 NORTH SIDE 33K 7800 5 3/8 5 I/2 YES 43 S-98 NORTH SIDE 33K 7800 7 5/8 7 7/8 YES 44 S-101 NORTH SIDE 33K 7800 7 7/8 8 YES 45 S-101 NORTH SIDE 33K 7800 7 7/8 8 YES 46 B-75 NORTH SIDE 33K 7800 5 3/4 6 YES 47 S-102 NORTH SIDE 33K 7800 7 7/8 7 1/2 YES 48 S-102 NORTH SIDE 33K 7800 7 7/8 8 1/2 YES 49 S-I02 NORTH SIDE 33K 7800 7 7/8 8 1/8 YES 50 B-76 NORTH SIDE 33K 7800 5 7/8 6 YES 51 S-98 NORTH SIDE 33K 7800 7 5/8 7 I/4 YES 52 S-98 NORTH SIDE 33K 7800 7 5/8 7 1/2 YES 53 S-98 NORTH SIDE 33K 7800 7 5/8 7 1/2 YES 54 S-98 NORTH SIDE 33K 7800 7 5/8 7 9/16 YES 55 S-101 NORTH SIDE 33K 7800 7 7/8 7 1/2 YES 56 B-74 NORTH SIDE 33K 7800 5 3/4 5 3/8 YES 57 S-101 NORTH SIDE 33K 7800 7 7/8 7 5/8 YES ~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077 Equipment Calibration Date: 5/13/97 Comments: *CABLE//2, S-29, IS MISSING Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and repo~s are for the exclusive use of the clients to whom they are addressed. c:\wpwin\repons\D7429-113-98~5T March 31, 1998 Rone Engineers, Inc. 1 34 Goodnight Lane Tel. (972) 241-45', RoneEngineers Dallas/Fort Worth Dallas, Texas Metro (972) 263-1555 75229 Fax (972) 241-5174 ELONGATION REPORT Project: Mansion By The Lake Page 4 of 4 Report No: 3137-D7429-113 Sample Date: March 25, 1998 Client: Western Rim Services Report Date: March 31, 1998 Location: Building//27 Technician: Tim Duke # Tendon Location lack Force Gauge Required Elongations Elongations Total Within No. (Kips) Pressure Elongations ~d (1) End (2) Elongations Tolerance 58 S-101 NORTH SIDE 33K 7800 7 7/8 7 1/2 YES 59 S-101 NORTH SIDE 33K 7800 7 7/8 6 3/4 YES 60 B-79 NORTH SIDE 33K 7800 6 1/8 6 I/4 61 S-15 NORTH SIDE 33K 7800 I 1 62 S-27 NORTH SIDE 33K 7800 2 2 YES 63 S-27 NORTH SIDE 33K 7800 2 2 1/8 YES 64 B-27 NORTH SIDE 33K 7800 2 I 7/8 YES ~.~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077 Equipment Calibration Date: 5/13/97 Comments: *CABLE//2, S-29, IS MISSING Distribution: (1) Mr. Richard E. Simmons; Western Rim Services (1) Mr. Larry Davis; City of Coppell (1) Mr. Lee Stone; City of Coppell (1) Mr. Tony Martin; Newport Classic (1) Mr. Doyle Damron; C. D. Construction Consulting LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed. c :\wpwin\reports\D7429-113-98\ST March 31, 1998