ELONGATION REPORT
Project: Mansion By The Lake Page 4 of 4
Report No: 3137-D7429-092 Sample Date: March 18, 1998
Client: Western Rim Services Report Date: March 23, 1998
Location: Building #25 Technician: Tim Duke
# Tendon Location Jack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Pressure Elongations End (1) End (2) Elongations Tolerance
58 S-101 EAST SIDE 33K 7800 7 7/8 7 1/4 YES
59 S-101 EAST SIDE 33K 7800 7 7/8 7 YES
60 B-79 EAST SIDE 33K 7800 6 1/8 6 YES
61 S-15 EAST SIDE 33K 7800 I 3/4 YES
62 S-27 EAST SIDE 33K 7800 2 I 3/4 YES
63 S-27 EAST SIDE 33K 7800 2 I 7/8 YES
64 B-27 EAST SIDE 33K 7800 2 I 3/4 YES
~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077
Equipment Calibration Date: 5/13/97
Comments:
Distribution:
(1) Mr. Richard E. Simmons; Western Rim Services
(1) Mr. Larry Davis; City of Coppell
(1) Mr. Lee Stone; City of Coppell
(1) Mr. Tony Martin; Newport Classic
(1) Mr. Doyle Damron; C. D. Construction Consulting