ELONGATION REPORT
Project: Mansion By The Lake Page 4 of 4
Report No: 3137-D7429-092 Sample Date: March 18, 1998
Client: Western Rim Services Report Date: March 23, 1998
Location: Building//26 Technician: Tim Duke
# Tendon Location /ack Force Gauge Required Elongations Elongations Total Within
No. (Kips) Presaure Elongations End (I) End (2) Elongations Tolerance
58 S-101 WEST SIDE 33K 7800 7 1/4 7 1/2 YES
59 $-101 WEST SIDE 33K 7800 7 7 1/2 YES
60 B-79 WEST SIDE 33K 7800 6 6 YES
61 S-15 WEST SIDE 33K 7800 3/4 3/4 YF_3
62 S-27 WEST SID£ 33K 7800 I 3/4 1 7/8 YES
63 S-27 WEST SIDE 33K 7800 I 7/8 1 7/8 YES
64 B-27 WEST SIDE 33K 7800 I 3/4 I 1/2 YES
~quipment ID: Ram No: 38077 Pump No: 380005 Gauge No: 38077
Equipment Calibration Date: 5/13/97
Comments: