WA9302-LR 950915 (7)['~'EOTECHNICAL E GEE Consultants, Inc. ! E I NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 · Fax (214) 620-9794 PIER INSPECTION REPORT Report Date: September 15, 1995 Inspection Date: August 30, 1995 Client: City of Coppell Pier Inspection Report No.: 2 Project: 6.0 million gallon water storage tank Page Number: Page 1 of 1 Identification: Straight Shaft Piers Project Number: 95-0220 Method of Test: Visual Observation Pier Shaft Depth to Req.d Actual Total Bearing Casing # Size Bearing Strata Pent. Pent. Depth Material Depth Remarks A-10.5 24" 24' 7" 11' 6" 12' 1" 36' 8" Gray shale 26' 4" Clean, dry, 4" out of plumb A-12.5 24" 26' 8" 11' 6" 11' 7" 38' 3" Gray shale 26' 4" Clean, dry, 2" out of plumb cc: Mr. Larry Davis - City of Coppell ~U~ Mr. Bob Barbarisi - Natgun Corporation Mr. Gary Hendricks - Shimek, Jacobs and Finklea Our letters and reports are for the exclusive use of the client to whom they are addressed. The use of our name must receive our prior written approval. Our letters and reports apply only to the sample tested and/or inspected, and are not necessarily indicative of the quantities of apparently identical or similar products.