Loading...
WA9302-LR 950913 I'~'EOTECHNICAL E GEE Consultants, Inc. E [NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-979] · Fax (2]4) 620-9794 REPORT OF CONCRETE MIX DESIGN Repon Date: September 13, 1995 Date Concrete Placed: AuguSt 28, 1995 Standard 6"x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank Concrete Report No.: 2 Contractor: Natgun Construction Project No.: 95 - 0196 Concrete Supplier and Plant: RediMix Concrete - 121 Plant Location of Placement: Piers B-13, A. 5-14.2, A. 2-13.4 MATERIALS s ..../ aatch W,,. INSPECTION DATA Description (Ibs./0.075 C.Y) Mix Number: //686 Time Sample Batched: 2:10 pm Cement: Time Sampled: 3: 10 pm Fly Ash: Sample Location: Pier B-13 Truck/Ticket No: 124/19377 Coarse Aggregate: Temperature: Intermediate Aggregate: Ambient Range: 100°F Fine Aggregate: Concrete Range: 95°F Admixtures: Slump Range (inches): 4th'' Weather Conditions: Clear 1 AEA Time Started: 1:00 pm 2 Time Completed: 6:00 pm Added Water: 15 gal. Sample Air Content (%): No Test Total Cubic Yards Placed: 9.0 C.Y. Required Strength (Lbs./sq.in.): 4,000 specimen Measured Age Date Total Load Compresslye Strength Remarks Number Slump (in.) (Days) Tested (Lbs.) (Lbs./Sq.ln.) CWT 1 4~ 3 08/31/95 119,940 3,250 CWT 2 4~ 3 08/31/95 89,500 3,170 CWT 3 4~ 5 09/02/95 91,180 3,230 CWT 4 4~ 5 09/02/95 98,240 3,480 CWT 5 4~ 8 09/05/95 103,200 3,650 CWT 6 4~ 8 09/05/95 104,280 3,690 CWT 7 4~ 28 09/25/95 CWT 8 4~ 28 09/25/95 Test Methods Utilized Fracture Regular Cylinders Made By: D.S. ASTM C-31,C-39,C-143 (Unless Noted Otherwise) Remarks and/or Distribution: CC: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendricks - Shimek, Jacobs and Finklea Mr. Gary Herron - RediMix Concrete ~ ~ i GEE Consultants, lnc, Reviewed by: All letters and reports are for the exclusive use of the client to whom they arc addressed and shall not be reproduced without the full approval of GEE Consultants, Inc. The use of our name must receive our prior written approval. Our letters and reports apply only to the sample tested and/or inspected and are not necessarily indicative of the quantities of apparently identical or similar products.