Northlake 635(2)-LR 970603 (2)Maxi
25'
TECHNOLOGIES INC
CLIENT:
PROJECT:
REPORT OF
CONCRETE COMPRESSIVE STRENGTH
Lincoln Property Co.
500 N. AKARD, SUITE 3300
ATTN: LARRY MOON
Dallas, TX 75201 PROJECT NO.: 0903
REPORT NO.: 11633
COPPELL BUSINESS CENTER DATE OF SERVICE: -=
WRANGLER DR AND BELTLINE RD AUTHORIZATION: O
COPPELL TX REPORT DATE: 6/C
PAGE i OF 1
SERVICES: Sample concrete at location of placement, perform require
prepare and test concrete compressive strength specimens.
CONTRACTOR: BUTLER CONSTRUCTION
CONCRETE SUPPLIER: Pioneer
PLANT: 22
SPECIFICATION REQUIREMENTS
STRENGTH: 4000psi @ 28
SLUMP: 5-7"
METHOD OF TEST
SAMPLING: ASTM C-172
MOLDING & CURING: ASTM C31
SLUMP: ASTM C143
TEMPERATURE: ASTM C1064
AIR CONTENT: ASTM C231
UNIT WEIGHT: N/A
CAPPING/PADS: ASTM C617
TESTING: ASTM C39
DAYS
AiR: N/A
CYLINDER
MARKED
SET NO.
2
3
PROJECT DATA
CLASS OF CONCRETE: Mix
DATE OF PLACEMENT: 5/C
TIME SAMPLED: 02: 51PM
TEMPERATURE (DegF) - AIR: 8
TRUCK NO: 122
MEASURED SLUMP {in.): 5.
AIR CONTENT(%): I. 9
LOCATION OF PLACEMENT:
Pier A-4.5
REPORT OF TESTS
CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS
MAXIMUM COMPRESSIVE
DATE AGE DIAMETER AREA LOAD STRENGTH
TESTED (days) (in.) (sq.in.) (lbs. force) (psi~ F
5/13/97 7 6.00 28.27 101070 3570 CC
6/03/97 28 6.00 28.27 119530 4230 CC
6/03/97 28 6.00 28.27 128640 4550 CC
1 4 HOLD
ADDITIONALCOMMENTS:
Technician time recorded on report number 116318
Technician: Rusty Bowers
Technician
Report Distribution:
(, u.~. ~, co. MAXIM TEC
(. Bu'n.m CO,$~,uC~ON ,NCO...
(, BaocK~'re^~,~O~E. ,NC.
(11 ~E ClR OF COm~ /
(ll O'BRIEN ~ClATES, INC. /
(11 A.E.C.C.
O~ I~ ~ r~ Je for t~
1001 LW ~y ~ to h ~m tm~ ~/u i~, ~ Je ~ i~ic~ve of t~ q~itl ~ ~j~ ~cd ~ I
~ Tach. · Southwestern Labs
r5 Lone Star Dr. · P.O. Box 224227
Dallas. Texas 75222
Telephone: (214) 631-27OO
FAX: (214} 920-1891
~05034
9
/06/97
going
3/97
d field tests,
Number 9349
6/97
BY: Rusty Bowers
5 CONCRETE: 89
TICKET NO: 376190
0
ACTURE TYPE REMARKS
NE
NE & SPLIT
NE
~d excep~ in
:er~ and r~
mil~