MOISTURE DENSITY RELATIONSHIP REPORT
Test Report Date: August 28, 1995 Project No: C-95-0196
Client: City of Coppell Report No.: 1
Sample Date: June 9, 1995
Project: 6.0 Million Gallon Ground Water Storage Tank
Coppell, Texas
Identification: Moisture Density Relationship
Test Procedure: ASTM D698
Test Results:
Method .............................. A
Optimum Moisture Content .................. 14.6 percent
Maximum Density ........................ 112.1 pounds per cubic foot
Rammer Type .......................... Manual
Material Description ....................... Select Fill: reddish brown clayey sand
Material Origin .......................... On Site
Moisture Preparation Procedure ................ Air Dry
Liquid Limit ........................... 19
Plastic Limit ........................... 15
Plasticity Index ....... · ................... 4
Percent Passing a No. 200 U.S. Sieve ............ 32