Loading...
Northlake 635(2)-LR 970515 (2)TECHNOLOGIES INC REPORT OF DRILLED pIER INSPECTION CLIENT: Lincoln Property Co. 500 N. AKARD, SUITE 3300 ATTN: LARRY MOON Dallas, TX 75201 PROJECT: COPPELL BUSINESS CENTER WRANGLER DR AND BELTLINE RD COPPELL TX PROJECT NO.: 0903~ REPORT NO.: 11657 DATE OF SERVICE: 5 AUTHORIZATION: On REPORT DATE: 5 / 1 SERVICES: Perform Drilled Pier Inspection. REPORT OF INSPECTION On this date, a Maxim Technologies representative arrived o scheduled to perform a Drilled Pier Inspection. See attach results of the inspection. Technician Time: 7:00am to 5:30pm Page 1 of 2 Technician: Rusty Bowers Technician Report Distribution: MA~ C (1) O'BRIE_R AS,~3ClATE~ INC. b/La~n.c~ · Tech. Southwestern Labs ;75 Lone S~r Dr. P.O. Box 224227 D.It~% Texas 75222 Telephone: (214) 631-2700 FAX: (214) 920-1891 105034 8 /12/97 going 5/97 n site as ~d report for ~ABS ~Br~cken, B.S. Ch.E. ~ject Manager TECHNOLOGIES INC LINCOLN PROPERTY CO. Project N":0903605034 Service Date:05~12~97 2575 Lone Star Drive * P.O. Box 224227 · Dalla~, Texas 75222 (214) 631-2700 · Fax (214) DI~ILLED pIIZR INSPECTION (STRAIGHT SHAFT) Report N°: 116578 Page 2 of 3 Date Drilled:O5/12/97***OBSERVATION OF DRILLED FOUNDATION CONSTRUCTION*** Pier identification H.4-9 G.9-9 H.6-9 J-8.4 J-8 Pier diameter(in)/Type 24 24 24 ~.0 24 Depth of pier from surface(ft) 37.0 37.2 36.0 37.6 Depth of bearing stratum from surface(ft) 30.5 30.5 30.0 29.5 31.5 Required penetration(ft) 6.0 6.0 6.0 6.0 6.0 Actual penetration(fO * 6.5 6.7 6.0 6.5 6.1 Condition of bottom{wet/dry) 2" Water 3" Water Trace 2" Water 2" Water Plumb within tolerance(yes/no) yes yes yes yes yes Casing diameter(in)/Length(ft) N/R N/R N/R N/R N/R # of bars/Reinforcing bar size{#) 6/#6 6/#6 6/#6 6/#6 6/#6 Length of reinforcing steel(ft) 38.3 35.7 37.0 35.2 36.6 Time drilling was completed(am/pm) 10:17am 11:04am 1:47pm 1:10pm 3:03pm Time concrete was placed(am/pm) 10:40am 11:27am 1:59pm 1:25pm 3:18pm Depth of pier from top of concrete(ft) 38.8 36.2 37.5 35.7 37.1 Elevation:Surface (ft}* · 96.2 96.5 96.5 96.3 96.5 Elevation:Top of pier (ft)** 98.0 95.5 98.0 96.0 96.0 Elevation:Bottom pier (ft) °* 59.2 59.3 60.5 60.3 58.9 Elevation:Top of bearing stratum(fi)** 65.7 66.0 66.5 6618 65.0 Bearing stratum (Description) Dark gray unweathered shale. NOTE: SEE REPORT # 116579 FOR COMPRESSIVE STRENGTH TEST SPECIMENS. * ADDITIONAL PENETRATION NOT REQUESTED UNLESS NOTED. ** ELEVATION BY OTHERS TIME: 7:00 A.M. TO 5:30 P.M. Our letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproc uced except in full without the approvaJ of the testing laboratory. The use of our name must receive prior written approvaJ of Maxim TechnoJog es, Inc. Letters and reports apply only to the sample tested and/or inspected and are not indicative of the quantity of apparently identical or similar )roducts. TECHNOLOGIES INC LINCOLN PROPERTY CO. Project N~:0903605034 Service Date: 05/12/97 2575 Lone Star Drive * P.O. Box 224227 s Dallas (214) 631-2700 · Fax (214) 920-189 DRILLED PIER INSPECTION (STRAIGHT SHAFT) Texas 75222 Report N°: 116578 Page 3 of 3 Date DrilIed:O5/12/97***OBSERVATION OF DRILLED FOUNDATION Pier identification J-8.6 Pier diameter(in)/Type 24 36.2 Depth of pier from surface(ft) Depth of bearing stratum from surface(ft) Required penetration(ft) Actual penetration(ft) * Condition of bottom(wet/dry) Plumb within tolerance(yes/no) 30.0 Length of reinforcing steel(R) Time drilling was completed(am/pm) Time concrete was placed(am/pm) Depth of pier from top of concrete(ft) Elevation:Surface (ft)* ° Elevation:Top of pier (ft)** Elevation:Bottom pier fit) ° ° Elevation:Top of bearing stratum{ft)ss 6.0 6.2 1" Water yes Casing diameter(in)/Length(ft) N/R //of bars/Reinforcing bar size(//) 6/#6 34.9 Bearing stratum (Description) 4:02pm 4:16pm 35.4 96.8 96.0 60.6 66.8 Dark gray unweathered CONSTRUCTION*** hale. NOTE: TIME: SEE REPORT # 116579 FOR COMPRESSIVE STRENGTH TEST SPECIMENS. ADDITIONAL PENETRATION NOT REQUESTED UNLESS NOTED. ELEVATION BY OTHERS 7:00 A.M. TO 5:30 P.M. Our letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reprodu approval of the testing laboratory. The use of our name must receive prior written approval of Maxim Technologic only to the sample tested and/or inspected and ars not indicative of the quantJW of apparently identical or similar ced exce~ in full without the s, Inc. Letters and reports apply ,roducts.