Loading...
Northlake 635(2)-LR 970425 (5)Maxim 2575 TECHNOLOGIES INC CLIENT: PROJECT: SERVICES: REPORT OF CONCRETE COMPRESSIVE STRENGTH Lincoln Property Co. 500 N. AKARD, SUITE 3300 ATTN: LARRY MOON Dallas, TX 75201 COPPELL BUSINESS CENTER WRANGLER DR. & BELTLINE RD. COPPELL, TX PAGE i OF 8 PROJECT NO.: 090360 REPORT NO.: 115568 DATE OF SERVICE: 4/1 AUTHORIZATION: Char! REPORT DATE: 4/25/ Test compressive strength specimens prepared in conjunction inspection. CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM MOLDING & CURING: ASTH SLUMP: ASTM TEMPERATURE: ASTM AIR CONTENT: N/.A UNIT WEIGHT: N/A CAPPING/PADS: ASTM TESTING: ASTM CYLINDER MARKED DATE SET NO. TESTED 1 i 4/25/97 1 2 4/25/97 1 3 5/16/97 C-172 C31 C143 C-138 PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 05= 15~ TEMPERATURE (DegF) - AIR: 48 TRUCK NO: 133 MEASURED SLUMP (in.): 8.00 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: A/7.8 to 8 C617 C39 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH- 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH (days) {in.) (sq.in.) (lbs. force) (Psi) FRAC 7 6.00 28.27 98410 3480 CON~ 7 6.00 28.27 94140 3330 CON~ 28 1 4 5/16/97 28 ADDITIONAL COMMENTS: Note= Visual check on concrete. slump, too high, superintendent electe~ Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 2 i'ech. ·Southwestem Labs · one Star Dr. · P.O. Box 224227 Dallas, Texas 75222 Telephone: (214) 631-2700 FAX: (214) 920-1891 i034 8/97 ie 97 with concrete 97 BY: Phillip L. Forrest CONCRETE: 72 TICKET NO: 366815 UNIT WEIGHT(pcf): N/A TURE TYPE REMARKS to place full without the eplxevid of the telL]n0 !M)MMMy. ina tie m.(~r...f~me mu~t rectors, our written M~'.o.val.. u.ur 1001 LW e~l~ly ofdy to the eamlde teated and/or m~, arid are not mdtcat~ve of the qL, ent)tme of ~perent~y tdentie.~ or Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM C31 SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 CYLINDER MARKED DATE SET NO. TESTED PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 06'. 35AM TEMPERATURE {DegF) - AIR: 51 TRUCK NO: 756 MEASURED SLUMP (in.): 5.00 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: B.s/8.s REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH {days) Iin.) , (sa.in.) Ilbs. force) (rmi) FRA~ 2 i 4/25/97 7 2 2 4/25/97 7 2 3 5/16/97 28 6.00 28.27 126670 4480 6.00 28.27 127290 4500 CON 2 4 5/16/97 28 Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 3 REPORT NO. 115568 PAGE 2 OF 8 SET NO. 2 97 BY: Phillip L. Forrest CONCRETE: 70 TICKET NO: 366834 UNIT WEIGHT(pcf): N/A ;TURE TYPE REMARKS 1001 LW apply only to the lamlde teeted andlm ~na~eeted, Ind ate not ~ndlcltsve of the quant~t~l of ~lrently identical Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM C31 SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/.A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 CYLINDER MARKED DATE SET NO. TESTED PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18 TIME SAMPLED: 08: 40AM TEMPERATURE (DegF) - AIR: 58 TRUCK NO: 760 MEASURED SLUMP (in.): 5.25 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: D/6.3 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH (days) [in.) (sq.in.) (lbs. force) (psi) FRA 3 1 4/25/97 7 3 2 4/25/97 7 3 3 5/16/97 28 6.00 28.27 127480 4510 CO~ 6.00 28.27 127270 4500 CO5 3 4 5/16/97 28 ADDITIONAL COMMENTS: Eight gallons of water added at site. Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 4 REPORT NO. 115568 PAGE 3 OF 8 SET NO. 3 '97 BY: Phillip L. Forrest CONCRETE: 73 TICKET NO: 366863 UNIT WEIGHT(pcf): N/A :TURE TYPE REMARKS E full without the I~l~'ovll Of th~ t~lting Ilbo~ltor/. The tel ol ~ ~ mu~ room, ~ 1 O01 LW e;plv only to the aamlde te~ted attd/or ina~ected, and are not indicative of the qu~ of a~l~atefltly icl~cM ot ~il ~ila~ ~'oductl. Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: AS'I~ C31 SLUMP: AS~ C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/A UNIT WEIGHT: N/A CAPPING/PADS: AS/M C617 TESTING: ASTM C39 CYLINDER MARKED .. DATE SET NO. TESTED . PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 09:32~[ TEMPERATURE (DegF) - AIR: 67 TRUCK NO: 100 MEASURED SLUMP (in.): 5.25 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: E/6.3 to E/6.7 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH {days) lin.) ~ ~lbs. force) (Del! FR A.._._J~ 4 1 4/25/97 7 4 2 4/25/97 7 4 3 5/16/97 28 6.00 28.27 107970 3820 CO~ 6.00 28.27 114320 4040 COW 4 4 5/16/97 28 ADOmONALCOMMENTS[ Five (5) gallons of water added at site. Technician: Phillip L. Forres/ Technician Report Of Tests Continued On Page 5 :EPORT NO. 115568 'AGE 4 OF 8 ;ET NO. 4 97 BY: Phillip L. Forrest CONCRETE: 74 TICKET NO: 344150 INIT WEIGHT(pcf): N/A URE TYP_ E REMARKS 1001 LW IH)ply e~ly to the ml~e te~ted Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 REPORT OF CONCRETE COMPRESSIVE STRENGTH ( C ont i hued ) CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM C31 SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/.A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 CYLINDER MARKED DATE SET NO. TESTED PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 10'- 30AM TEMPERATURE {DegF) - AIR: 70 TRUCK NO: 551 MEASURED SLUMP (in.): 4.75 AIR CONTENT{%): N/A LOCATION OF PLACEMENT: E.S/7.0 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH (days) (in.) (sq.in.) (lbs. force) (psi) FRA( 5 1 4/25/97 7 5 2 4/25/97 7 5 3 5/16/97 28 6.00 28.27 115840 4100 CON] 6.00 28.27 118480 4190 CO~ S 4 5/16/97 28 ADDITIONAL COMMENTS: Five (5) gallons of water added at site. Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 6 iEPORT NO. 115568 'AGE 5 OF 8 ~ET NO. 5 97 BY: Phillip L. Forrest CONCRETE: 74 TICKET NO: 344159 UNIT WEIGHT(pcf): N/A :TURE TYPE REMARKS 1001 LW aq~gly only to the eamlole tatted and/m, if!Ii,eared, an~ a~e net ~r41caove m ~r~ q~,uu~ v, ~_.,,.7 ~ ___ ~ m lit I~edu~tl. Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPEC~RCATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM C31 SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 CYLINDER MARKED SET NO. 1 2 3 4 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) ADDITIONAL COMMENTS: Note: Technician: Phillip L. Technician PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18 TIME SAMPLED: 11: 30~v, TEMPERATURE (DegF) - AIR: 78 TRUCK NO: 731 MEASURED SLUMP (in.): 7.00 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: ~/7.8 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM COMPRESSIVE DATE AGE DIAMETER AREA TESTED (dew) {in.) (sq.in.) 4/25/97 ? 6.00 28.27 4/25/97 7 6.00 28.27 5/16/97 28 5/16/97 28 REPORT NO. 115568 PAGE 6 OF 8 SET NO. 6 BY: Phillip L. Forrest CONCRETE: 78 TICKET NO: 344166 LOAD STRENGTH {lbs. force) {psi) 101230 3580 105550 3730 Notified contractor of high slump on concrete. Forrest Report Of Tests Continued On Page 7 FRA :TURE TYPE CON CON REMARKS UNIT WEIGHT(pcf): N/A Ou~ letters and reports are for the exclUSWe uae of the client to whom they ate ed~.releld ~ Ihlll not bi rlxoducld, fu# without the eDprov,u of the teatir~ labor,tory. The we of ~ n~me mu~t recev.e..ow written aeM.oy.d..Ou~ ~ md repon~ 1001 LW apply only to ;he aample teeced end/or impectedo ~ are net ,ndlcetwe of the quartet ee of ~pazently identical er ~mi~ ~r ptoduc~. Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Continued) CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 CYLINDER MARKED DATE SET NO. TESTED PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 01: 12PM TEMPERATURE (DegF) - AIR: 81 TRUCK NO: 287 MEASURED SLUMP (in.): 6.00 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: G/6.5 tO 8.5 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYUNDERS MAXIMUM COMPRESSIVE AGE DIAMETER AREA LOAD STRENGTH (davsk (in.) (sa.in.) {lbs. force) 7 1 4/25/97 7 6.00 28.27 103270 3650 7 2 4/25/97 7 6.00 28.27 99510 3520 7 3 5/16/97 28 7 4 5/16/97 28 FRA( CONE CONE ADDITIONAL COMMENTS: Note: Notified contractor of high slump on concrete. Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 8 EPORT NO. 115568 ~GE 7 OF 8 ET NO. 7 ~7 ty: Phillip L. Forrest :ONCRETE: 82 'ICKET NO: 366919 JNIT WEIGHT{pcf): N/A FURE TYPE, , REMARKS futl without the appt oval of the re'mo lal~wato~'Y, ine ~ m.o~ff. ,?,-- 1001 LW apply i~'l~y TO th~ 8~ t~ti~d II~d/ol' il'll~'~Sd, ~ ~ rl~t indicative Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 4/18/97 CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 29 SPECIFICATION REQUIREMENTS STRENGTH: 4000psi @ 28 SLUMP: 5" METHOD OF TEST SAMPLING: ASTM C-172 MOLDING & CURING: ASTM C31 SLUMP: ASTM C143 TEMPERATURE: ASTM C-138 AIR CONTENT: N/A UNIT WEIGHT: N/A CAPPING/PADS: ASTM C617 TESTING: ASTM C39 DAYS CYLINDER MARKED SET NO. 1 2 3 4 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Cortt inued) Technician: Phillip L. Technician Report Distribution: {I! Lincoln P~ol~ly Ce. {1) BUTLER CONSTRUCTION INCORP. {1) BROCKETT-OA'VIS.ORAKF., INC. (I) THE CITY OF COPPELL {1) THE CITY OF COPPEI.L (1) O'BRIEN ASSOCIATES, INC. (1) A.E.C.C. 1001 LW PROJECT DATA MIX DESIGN NUMBER: 9349 DATE OF PLACEMENT: 4/18/ TIME SAMPLED: 02: 05PM TEMPERATURE (DegF) - AIR: 80 TRUCK NO: 297 MEASURED SLUMP (in.): 4.75 AIR CONTENT(%): N/A LOCATION OF PLACEMENT: H/6.3 to 6.5 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYENDERS MAXIMUM COMPRESSIVE DATE AGE TESTED (days) 4/25/97 7 4/25/97 7 5/16/97 28 5/16/97 28 Forrest REPORT NO. 115568 PAGE 8 OF 8 SET NO. 8 97 BY: Phillip L. =ONCRETE: 80 rlCKET NO: 366931 DIAMETER AREA LOAD STRENGTH (in.} (sq.in.) (lbs. force) (psi) 6.00 28.27 120570 4260 6.00 28.27 124990 4420 FRAC rURE TYPE CON~ CO1~ JNIT WEIGHT(peri: N/A REMARKS Forrest LABS / s. Ch.-. (___/ //Projgct Manager Our lettem and r~ ~e f~ ~ ~d~ ~ ~ ~ d~ to w~ ~ ~ ~ ~ ~ ~ ~ e~ in ~y o~y to t~ t~ t~ ~lor ~ct~, ~ ~e ~t i~lc~ of ~ q~M~ of ~ ~ ~ ~mil~.