Northlake 635(4)-LR001201 GEOTECHNICAL AND
ENVIRONMENTAL CONSULTANTS
CONCRETE CYLINDER TEST REPORT
Coppell Tech Center II
1322 Crestside
Coppell, Texas
REPORTED TO:
Bob Moore Construction Co.
1110 N. Watson Road
Arlington, Texas 76011
ATTN: Mr. Ed T. McGuire
REPORT NO. 49
REG PROJECT NO. 7044
SAMPLE DATE: 12-01-00
TECHNICIAN: J. Stuart
CONTRACTOR: Bob Moore Construction Co.
Location of Sample
I Set Number I Location I Quantity Represented
1 Piers A-l, A-1.5 and A-2 10/10
Design Information
Is°urce °f C°ncrete ITXI Mix Identification 9505 I Specified Strength P's'i' I 3000
Test Results
No.Set CylinderlID
Date Tested Test lbs. Strength p.s.i. Strength p.s.i.
1 1797 12-08-00 7 83450 2950
1797 12-08-00 7 84600 2990
1797 12-29-00 28
1797 12-29-00 28
2970
Cylinder Data
Set J CylinderI Time of I Concrete J Air I Ticket
INo. ID Slump Sample Air Temp. Temp. Entrainment Number
I
1797 5.25 1:30PM 63 68 N/A 2787198
Mail
Distribution:
(1) Bob Moore Construction Co./
Mr. Ed T. McGuire
(1) City of Coppell/Mr. Larry Davis
(1) City of Coppell/Mr. Lee Stone
(1) McHale Consulting Engineering/
Mr. Gary McHale
(1) CMC-Commercial Realty/
Mr. Steve Huff
(1) AECC, Inc./Mr. Chad Stevens
Submitted by:
REED ENGINEERING GROUP, INC.
Original Signed By
Keith Atkins
KENje
2424 STUTZ DR. · SUITE 400 · DALLAS, TX 75235 · TEL [214] 350 5600 · FAX [214] 350 0019