Loading...
Northlake 635(2)-LR 970306TECHNOLOGIES INC REPORT OF CONCRETE INSPECTION CLIENT: Lincoln Property Co. 500 N. AKARD, SUITE 3300 ATTN= LARRY MOON Dallas, TX 75201 PROJECT: COPPELL BUSINESS CENTER WRANGLER DR. & BELTLINE RD. COPPELL, TX PROJECT NO.: 0903 REPORT NO.: 1129¢ DATE OF SERVICE: AUTHORIZATION: REPORT DATE: 3/ SERVICES: Observe concrete mixture for consistency at placement loc required field tests, and prepare compressive strength s~ CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 22 BATCH PROPORTIONS Cement ASTM C-150 Coarse Aggr.: ASTM C-33 Fine Aggr.: ASTM C-33 Admix: ASTM C-494 Total Water: Water/Cement Ratio: 0.57 Lb/Lb PROJECT DATA CLASS OF CONCRETE: DESIGN MIX NUMBER: 93." REPORT OF INSPECTION 470 lbs. 1840 lbs. 1488 lbs. 14.1 cwt. 266.0 lbs. Slump Range (in.) 5.25-5.50 ~ Range of Fresh Concrete Wt./Cu. Ft. Air Temp. Range (F): 50-56 Weather Conditions: Cloudy - Placement Location: Building C panels #8, ~. 51, 52, 20, 42, 43, 44, panels $9, 11, 8, 7, 6, No. Cu. Yds. Placed:' 156 Technician: Phillip L. Foz Time-Started N/A SUMMARY OFINSPECTION: The technician observed the concrete mixture at placement concrete was checked for proper mixing, and a visual estim made. Also, the concrete was observed for workability, cot uniformity. Samples of concrete were obtained for the req~ and preparation of compressive strength specimens for laboz Technician time: See Report #112992 Test results appear on Report of Concrete Compressive Strer Technician: Phillip L. Forrest Technician Report Distribution: MAXIM TE( (1) Lincoln Proper~y Co. (1) A.E.C.C. (1) BUTLER CONSTRUCTXON X#CORP. (1) BROCKETT-DAVIS-DRAKE, X#C. (1) THE CXTY OF COPPELL Lawrence (1) THE CXTY OF COPPELL ,o%?i=RO'BRXEN ASSOCZATES, OW I~ters ~nd repo~t~ me for the ex~ive use of the cl ant to whom they mo addr---ee~l-- end ~nell not be repr~u¢ f~l without tm approval of the t~ting laboratory. The uae of o~name m~t receive ou~ wri~en ~prov~. ~ply only to the sarnpM t~t~ md/or i~ct~, m~l ere not i~icatJvo of the quantitie~ rn T. ch. ·Southwestem Labs ~5 Lone Star Dr. · P.O. Box 224227 Dallas, Texa~ 75222 Telephone: (214) 631-2700 FAX: (214) 920-1891 505034 6 /24/97 6/97 at/on, perform ,ec/mens. ir Content Range (%): 1.5-1.8 Coho. Temp. Range (F): 65-70 ~indy , 21, 22, 25, 49, 50, 45, 46, 47. Building B 5, 4, 2. o. Test Spec.: 8 rest topped N/A ocation. The .ts of slump was .sistency, and .ired field tests 'atory testing. .gth. H..SOUTHWESTERNLABS ~ Bracken, B.S. Ch.E. 'oject Manager ~,d exce~ in er~ end re~ JlllJl¥ Maxi 25: TECHNOLOGIES INC REPORT OF CONCRETE COMPRESSIVE STRENGTH CLIENT: Lincoln Property Co. 500 N. AKARD, SUITE 3300 ATTN= LARRY MOON Dallas, TX 75201 PROJECT: COPPELL BUSINESS CENTER WRANGLER DR. & BELTLINE RD. COPPELL, TX PROJECT NO.: 0903 REPORT NO.: 11294 DATE OF SERVICE: AUTHORIZATION: REPORT DATE: 3/ SERVICES: Test compressive strength specimens prepared in conjunct1 inspection. CONTRACTOR: BUTLER CONSTRUCTION CONCRETE SUPPLIER: PIONEER PLANT: 22 SPECIFICATION REQUIREMENTS STRENGTH: 3000psi @ 28 DAYS SLUMP: 5" METHOD OF TEST: ASTM C-39 PROJECT DATA MiX DESIGN NUMBER: 933'~ DATE OF PLACEMENT: 2/3 TIME SAMPLED: 12; 20PM TEMPERATURE (OF) - AIR: 50 TRUCK NO: 497 AIR CONTENT(%): 1.5% LOCATION OF PLACEMENT: Panel ~9, and 11 CYLINDER MEASURED MARKED SLUMP DATE SET NO. {inches) TESTED I i 5.50 3/03/97 1 2 5.50 3/03/97 1 3 3/24/97 1 4 3/24/97 REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 ~YLINDERS MAXIMUM AGE {days) 7 7 28 28 DIAMETER AREA LOAD (in.} (sq.in.) {Ibs. force) 6.00 28.27 109390 6.00 28.27 106520 Technician: Phillip L. Forrest Technician Report Of Tests Continued On Page 2 1001 FR ~ Tech. · Southwestern Labs r5 Lone Star Dr. · P.O. Box 224227 Dallas. Texas 75222 Telephone: {214) 631-2700 FAX: (214) 920-1891 ~05034 6 /24/97 6/97 on with concrete 4/97 BY: Phillip L. Forrest CONCRETE: 657 TICKET NO: 341315 OMPRESSIVE STRENGTH (osil 3870 3770 REMARKS · . ~ and irepor~l ~oply only to the ~lmp~ faired incl/o~ inlpected, IrN:l are n~t indiclbvl of the qulnthill of ippl~'~ntly identical o~' imiilr I~rodu~. Lincoln Property Co. PROJECT NO. 0903605034 DATE OF SERVICE: 2/24/97 REPORT NO. PAGE 2 SET NO. 2 112946 REPORT OF CONCRETE COMPRESSIVE STRENGTH (Cont i nued) CONTRACTOR: BUTL~.R CONSTRUCTION CONCRETE SUPPLIER: P IONEm. R PLANT: 22 SPECIFICATION REQUIREMENTS STRENGTH: 300Ops£ @ 28 DAYS SLUMP: 5" METHOD OF TEST: ASTM C-39 PROJECT DATA MIX DESIGN NUMBER: DATE OF PLACEMENT: 2 TIME SAMPLED: Ol= 15PM TEMPERATURE ( I F) - AIR: TRUCK NO: 296 AIR CONTENT(%): I .8% LOCATION OF PLACEMENT: Panel #5 4/97 BY: Phillip L. Forrest CONCRETE: 65 TICKET NO: 341321 CYLINDER MEASURED MARKED SLUMP DATE SET NO, {inches) TESTED REPORT OF TESTS CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS MAXIMUM AGE DIAMETER AREA LOAD {days) (in.) (sq.in.) (lbs. force} 2 I 5.50 3/03/97 7 6.00 28.27 94020 2 2 5.50 3/03/97 7 6.00 28.27 90690 2 3 3/24/97 28 2 4 3/24/97 28 3320 3210 [SSIVE ;TH REMARKS Technician: Phillip L. Forrest Technician Report Distribution: MAXIM (1) Lincoln Property Co. (1) A.E.C.C. (1) BUTLER CONSTRUCTION INCORP. (1) BROCI(ETT-OAV[S-ORAKE, [NC. (1) THE CITY OF COPPELL (1) THE CITY OF COPPELL ASSOC[^TES. ,,C. Out letterl end re~ort~ Ire fo<, the exclusive u~l of the client to wi'~m they Ire eddrel~ed ~ ~h~l full without the abprovll of the testing laboratory. The ule of ourfllme muir race;vi our wrlt~l~l ~pty o~ly to the ~,arnple tamed IrlclJo~ ir~oected, and Ire not indicetive of the ClUantitiel oi ~ABS ,t B.S. Ch.E. .~ct Manager d ex=e~ in