Northlake 635(4)-LR000908 (2) GEO~'ECHNICALAND ~ R r"l I I F=~
ENVIRONMENTAL CONSULTANTS
REPORT OF WATER INJECTION OBSERVATION
Coppell Tech Center II
Lakeshore Drive and Crestside
Coppell, Texas
REPORTED TO: Bob Moore Construction Co. REPORT NO. 7
1110 N. Watson Road REPORT DATE: 09-08-00
Arlington, Texas 76011 REG PROJECT NO. 7044
ATTN: Mr. Ed T. McGuire TECHNICIAN: F. Thornton &
P. Olegario &
R. Hollings
PAGE: 1 of 1
CONTRACTOR: Bob Moore Construction Co.
On these dates a representative of Reed Engineering Group, Inc. observed water injection
operations on the referenced project. The injection operations proceeded in accordance
with project specifications unless otherwise noted.
Specification
InjeCtion Depth I Injection Spacing I Injection Pressure Injection Intervals
(ft) I (ft)I (psi) (in)
10 5 100-200 12-18
Equipment
Number of I Number of Probes I Length of Probes Probe Spacing
Rigs i (ea) I (ft) (ft)
3 4 13 5
Date I Area Injected (sq ft) I Average Pressure (psi) Pass No.
09-01-00 13,540 125 1
33,600 105 4
09-02-00 31,000 125 4
Surfactant added at regular intervals: Yes
Mail Submitted by:
Distribution: (1) Bob Moore Construction Co./
Mr. Ed T. McGuire REED ENGINEERING GROUP, INC.
(1) City of Coppell/Mr. Larry Davis
(1) City of Coppell/Mr. Lee Stone Original Signed By
(1) McHale Consulting Engineering/
Mr. Gary McHale James F. Phipps, P.E.
(1) CMC-Commercial Realty/ KNcg
Mr. Steve Huff
2424 STUTZ DR. · SUITE 400 · DALLAS, TX 75235 · TEL [214] 350 5600 · :AX [214] 350 0019