Loading...
WA9302-LR 960325 (2)'EOTECHNICAL E GEE Consultants, Inc. EI NVIRONMENTAL 10046 Monroe Drive · Dallas, Texas 75229 · (214) 352-5433 · Fax (214) 352-6972 GENERAL REPORT F~eport Date: March 25, 1996 SampleDate: February 28, 1996 Client: Cky of Coppell Report Number: 21 Project: 6.0 MG Water Storage Tank Project No. 95-196 Identification: Obtaining and Testing Drilled Concrete Cores Method of Test: ASTM C42 Test Date: March 8, 1996 F:esults: Specimen Number CWT-SC7 (Shotcrete) CWT-SC8 (Shotcrete) CWT-SC9 (Shotcrete) .= Avg. Estimated Length Avg. Nominal of Length of Maximum Un- Specimen Specimen Avg. Size of Cross- Corrected Corrected Before After Core Coarse Sectional Max. Compresslye Compressire Specimen Capping Capping Diameter Aggregate Area L/D Load Strength Strength # (in.) (in.) (in.) (in.) (sq.in.) Ratio (lbs) (PSI) (PSI) CWT-SC7 Not 3.96 2.70 Fine 5.73 1.47 39,600 6,910 6,620 Measured CWT-SC8 Not 3.83 2.69 Fine 5.68 1.42 54,000 9,510 9,050 Measured CWT-SC9 Not 3.73 2.69 Fine 5.68 1.39 57,400 10,110 9,590 t I Measured I I I I I i I 'l'~'pe of Fracture: Colic Age of Specimens: 9 Days Direction of Application of Load With respect to Horizontal Plane of' Concrete as Placed: Perpendicular 1~ 5oisturc Condition at Time of Testing: Air dried A~'erage Compressive Strength of Cor~s: 8,420 Above test result do meet ACt 318 requirements for 6,000 Ibs./sq.in. Cored by: L.D. Mr. Larry Davis - Ci,~, of Coppell Mr. Gary Hendticks - Shin~ek, Jacobs and Finklea ( }kll JellelY, al/d rcpln~ are t'tll' tile exclusive use ol the client Ill whotll they are addressed. The use of our nanle ~nust receive our prior writtell approval. Our leuel:, and repl~rt.~ apply only m the sample tested and/.r inspected, and are not necessarily indicative ol the quantities tff apparently identical or similar ph:dUCB