Northlake 635(3)-CS 971016he City With A Beautiful Future
Pat Acker, P.E.
Albert H. Halff Associates, Inc.
8616 Northwest Plaza Drive
Dallas, Texas 75225
Octobel
Replat of Northlake 635 Business Park Block B, Lot 1
Coppell Business Center II
Dear Mr. Acker:
The City of Coppell has received and reviewed the referenced plans and has the follo~
1. If public sidewalks are not to be constructed at this time then a note needs to
indicating that sidewalks adjacent to public right-of-way to be constructed at th
the City Engineer.
2. On the plat, a 20' drainage easement needs to be provided for the proposed 60"
3. On grading plans, indicate on plan if the elevations are top of proposed ground ot
4. On the paving plans, indicate the locations of proposed bollards adjacent to the
provide a detail.
5. Indicate on the plans if dimensions are to be measured to the back of curb.
6. All notes should be referenced to City of Coppell Subdivision Ordinance and I
7. On the curb sections 4-4 & 2-2, indicate what type of concrete finishing will be
the curb (see sheet G-2).
8. Darken the lines on the paving plan sheets.
9. The location of fire hydrants must be approved by the Fire Marshal.
10. Add additional water valves as indicated on sheets WS-1 & WS-2.
11. Add the additional items to the bubble notes as indicated on the sheets WS-1 &
12. Abandon sanitary sewer stubout shown on sheet WS-1 if this development is not l
13. Provide a profile of the proposed 8" sanitary sewer line on the southside of the d
utility crossings.
14. Make spelling corrections to the grade inlet notes on sheet STM-1.
15. Label all storm sewer lines in the plan views.
16. Provide railing for the driveways crossing over the proposed box culverts.
17. Profile the storm sewer lateral E-6 and D-6.
18. Turn the proposed storm sewer system pipes in the direction of the flow in the
19. Storm sewer line B appears to get shallow around Station 4+00.
20. Label the existing Reinforced Concrete Boxes adjacent to Belt Line Road.
There are various other minor comments throughout the plans. Once these comments
marked up plans along with two revised sets of plans should be resubmitted to the City
have any questions concerning these comments, please contact me at 304-3681.
Michael A. Martin, P.E.
Assistant City Engineer
P.O. Box 478
Coppell, Texas 75019
214-462-0022
16, 1997
ing comments to offer:
be provided on the plat
time when directed by
RCP.
top of proposed paving.
rainage channels. Also,
~tails.
done on the backside of
WS-2.
[oing to use the stub out.
~velopment and show all
:hannel.
lave been addressed, the