Meadows Addn 2-CS 930701,~ •~"1 ALBERT H. HALFF ASSOCIATES, INC. ENGINEERS • SCIENTISTS • SURVEYORS DALLAS • ARLINGTON • CHICAGO • FORT WORTH 8616 NORTHWEST PLAZA DRIVE • DALLAS. TEXAS 75225 214/739-0094 . FAX 2141739-0095 Jj]ly 1, 1993 AVO 12036 City of Coppell 255 Parkway Blvd. Coppell, Texas 75019 Attn: Mike Martin, Engineering Re: Meadows Subdivision Drainage Improvements -Stage II Dear Mike: As discussed in our June 17th meeting, Halff Associates is resubmitting t construction plans for final review (2 sets enclosed). Also enclosed , Construction Specifications and Contract Documents for review. These doci submitted previously, however, the format utilized is exactly the same as ~ Brooks Lane Spec books. Additions to this contract aze: • Bid Bond required • Performance, Payment and Maintenance Bonds required • Liquidated Damages increased to $240 per day We have also included the original "city review" set of the construction Halff Associates has addressed these comments as follows: Comment: Cover sheet "Use Revised Standazd Details" Response: Revised Standazd Details aze included Comment: Sheet DA-2 "Velocities too high in 36" RCP at proposed diversion" Response: System I - Line B lateral connection is relocated to enter in Line I-TB7. Comment: Sheet STM-1 "Can easements all be 20' " Response: An easement through Waterside Estates No. 15 was obtained platting process. TRANSPORTATION • WATER RESOURCES • LAND DEVELOPMENT • MUNICIPAL ENVIROI SURVEYING GLOBAL POSITIONING SYSTEM (G.P.S.) • REMOTE SENSING AND LANDSCAPE ARCHITECTURE • PLANNING above referenced two sets of the nts have not been Sandy Knoll and for your files. beginning of the the 48" RCP, Trunk during the • STRUCTURAL ~"`, ALBERT H. HALFF ASSOCIATES, INC. ENGINEERS • SCIENTISTS • SURVEYORS City of Coppell July 1, 1993 Page 2 '"~~ Comment: Sheet STM-1 "Change grass spec to 70% to 80°k height" Response: Changed Comment: Sheet STM-1 "Sanitary Sewer Crossings" Response: Halff Associates has performed additional surveying to n existing utilities where possible. See revised plans. Comment: Sheet STM-1 "Details for water main lowering crossings" Response: The detail for Water Main Lowering was on Sheet SD-8. SD-18 in the new details. Sanitary Sewer Crossings are sl coverage 1-1/2" in accurately locate sanitary sewer is shown on Sheet n on Sheet SD-20. Comment: Sheet STM-1 "Construct Junction Box" Response: A junction box is not recommended at this location due to a minimal cover of the existing storm sewer system, the associated head losses, d cost. Comment: Sheet STM-2 "Attach inlet extension to existing box " Response: Dowels into existing inlets have been added to the detail sho on sheet STM-2. In addition, Ha1ff Associates has changed the Diversion outfall pipe from a 54" RCP to a 5'x4' reinforced concrete box. This provides additional clearance for the 8 inch 'tary sewer line as well as increased capacity. The existing 36" RCP in Waterside Estates is al connected into the new system on Spyglass Drive. All crossings within approximately 2 f t vertically of the proposed storm sewer pipe are also shown with Ductile iron replacement pi as per the City of Coppell's standard details. However, please note that Dallas Water U ' 'ties is no longer replacing PVC pipe with ductile iron because of problems with corrosion. A copy of DWU's details for overcrossings is attached to this letter for your information. Mr. teve Hardy, DWU - Water Design, 948-4630 can be contacted for further information. ALBERT H. HALFF ASSOCIATES, INC. ENGINEERS • SCIENTISTS • SURVEYORS City of Coppell July 1, 1993 Page 3 '~"~ It should also be noted that a special junction box is required at the connec to the 5x4 reinforced concrete box. Design of this box is beyond the scopE may be possible to utilize the City's Standard Type B manhole with some revision could be performed "in house" when funding for the Stage II imp available. on of the 54" RCP of our contract. It codifications. This ~vements becomes Upon completion of this review, Halff Associates will provide originals of the Spec Book and Construction Plans to complete this contract. The original of the easement egal and plan view will also be provided upon approval (copy also enclosed). Please do not h sitate to call if you have any questions or comments. Yours very truly, ALBERT H. HALFF ASSOC: (JvK C~~~~ C ean Hansen, P.E. /mmh TES, INC. Enclosures CITY OF COPPELL /'~'` MEADOWS SUBDIVISION STAGE _.. DIVERSION AND INLET PHASE I DRAINAGE IMPROVEMENTS ~"-. ITEM NO. DESCRIPTION UNIT PLAN UAN UNIT PRICB TOTAL COST 1 MOBILIZATION AND BARRICADES LS 1 000 000 qi C 3 REMOVAL & DISPOSAL OF PVMT dt CURB SY 245 SS S1 4 21" CL III RCP LF 105 38 3990 5 6 " CL CP 36" CL III RCP LF 36 5 S60 160 7 48" CL III RCP LF 242 85 20 0 8 54" ~ ~ RCp LF 395 S 115 S45 425 9 CRUSHED STONE EMBEDMENT CY 110 5 4950 10 11 SELECT MA RIA B D NT ADD 6' EXT. TO EXIST. 8' CURB INLET EA 85 1 ~ S2 000 ~ S 000 12 ADD 6' EXT. TO EXLST. 10' CURB INLET EA 1 2000 000 13 14 C S U 0' T CONSTRUCT 12' CURB INLET EA 2 ~ S2 800 SS 600 15 ~ CONSTRUCT 14' RECESSED CURB INLET EA 2 S3 S6 400 1 17 C T. 8" TO 36" RCP CONNECT EXLST. 27" TO 27" RCP EA 1 1 3 5300 3~ 18 CAP EXIST. 27" RCP & REMOVE LINE EA 1 350 350 19 CONNECT EXIST. 36" TO 36" RCP EA 1 S300 5300 20 CAP EXIST. 48" RCP 8c REMOVE LINE EA 1 S350 $350 21 36" X 18" A R C CTION EA 5 22 36" X 21" FACTORY WYE CONNECTION EA 1 5450 5450 23 36" X 27" FACTORY WYE CONNECTION EA 1 50 450 24 25 CONNE O S CONSTRUCT 5'x 4' PRECAST REINF. CONC BOX LF 4 165 140 S23 100 26 CONSTRUCT 8'x 7.5' x 6.5' JUNCTION BOX EA 1 5000 5000 28 REPLACE 6" 3000 PSI REINF. CONCRETE PVMT. SY 220 35 '1700 " 3000 P L 0 30 CONSTRUCT SPECL4I. HEADWALL EA 1 SS SS 000 31 CONSTRUCT EMERGENCY OVERFLOW FLUME CY 22 3 6600 32 LOCATE. LOWER dt ENCASE WATER LINES EA 2 1 000 33 REPLACE SS LINES WITH D.L & ENCASE EA 4 S7 S3 000 34 REPAIR SIDEWALKS LANDSCAPING do GRASS LS 1 000 35 N S SU AL 191 5 109b CONTINGENCIES 519135 TOTAL io 4so lA ADDITIVE AL'1'r:KNA 1 ~J LOCATE LO ENCASE WATER SERV. LINES EA 2 1 000 1 g . A. . THLS STATEMENT WAS PREPARED UTII~ZII~IG STANDARD COST ESTIMATION PRACTICES. TT TS UNDERSTOOD AND AGREED THAT THLS IS AN ESTIMATE ONLY. AND THAT THB ENGINEER SHALL NOT BE LIABLE TO OWNER OR TO A THIRD PARTY FOR ANY FAII.URE TO ACCURATELY ESTIMATE THE COST OF THE PROJECT, OR ANY PART THEREOF. 07/02/93 Albert H. Halff Associates, Inc- LWV01203EQUATTRO~COST.WQ1 CITY OF COPPELL MEADOWS SUBDIVISION STAGE . DIVERSION AND INLET PHASE I DRAINAGE AZPROVEMENTS ~'F.1y1 NO. DESCRIPTION UNIT PLAN LAN UNTI' PRICE TOTAL COST 1 MOBIIIZATION AND BARRICADES ~ 1 000 000 w 3 REMOVAL 8c DISPOSAL OF PVMT 8c CURB SY 245 SS Si 4 21" CL III RCP LF 105 38 3 6 36" CL III RCP ~ ~ 160 7 48" CL III RCP LF 242 85 20 570 8 54" CL III RCP LF 395 5115 545 425 9 CRUSHED STONE EMBEDMENT' CY 110 5 950 S ~ ~ 11 ADD 6' EXT. TO EXIST. 8' CURB INLET EA 1 52000 S 000 12 ADD 6' EXT. TO EXIST. 10' CURB INLET EA 1 2000 000 S ' 14 CONSTRUCT 12' CURB INLET EA 2 S2 800 SS 600 15 CONSTRUCT 14' RECESSED CURB INLET EA 2 00 6400 1 C 8" CP EA 1 00 300 17 CONNECT EXIST. 27" T'O 27" RCP EA 1 5300 300 18 CAP EXIST. 27" RCP & REMOVE LINE EA 1 350 350 19 CONNECT EXIST. 36" T'O 36" RCP EA 1 5300 5300 ZO CAP EXIST. 48" RCP & REMOVE LINE EA 1 350 5350 2 "X1 O A 22 36" X 21" FACTORY WYE CONNECTION EA 1 5450 5450 23 36" X 27" FACTORY WYE CONNECTION EA 1 50 50 24 CO 1 25 CONSTRUCT 5'x 4' PRHCAST REINF. CONC BOX LF 166 140 23 100 26 CONSTRUCT 8'x 7.5' x 6.5' JUNCTION BOX EA 1 5000 5000 28 REPLACH 6" 3000 PSI REINF. CONCRETE PVMT. SY 220 35 700 0 0 30 CONSTRUCT SPECIAL HEADWALL EA 1 SS 000 SS 000 31 CONSTRUCT EMERGENCY OVERFLOW FLUME CY ~ ~ 6600 32 LOCATE. LOWER 8c ENCASE WATER LINES EA 2 1000 000 33 REPLACB SS LIlVES WITH D.L & ENCASE EA 4 5750 S3 000 34 REPAIR SIDEWALKS LANDSCAPING ~ GRASS LS 1 ~ 000 35 S 1 SUBTOTAL 1 1 45 1096 CONTZTiGENC]FsS 519135 ,rol,~ 10 480 ADD111V li AL"1 ~liiVA 115J 000 lA LOCATE LO fiNCASE WATER SERV. LINES EA 2 1000 0 1 THIS STATEMENT WAS PREPARED U1zI,iZITIG STANDARD COST ESTIMATION PRACTICBS. 1T LS UNDERSTOOD AND AGRBED THAT THIS LS AN ESTIMATE ONLY, AND THAT THH ENGINEER SHALL NOT BE LIABLE TO OWNER OR TO A THIItD PARTY FOR ANY FAILURE TO ACCURATELY ESTIMATE THE COST OF THE PROJECT, OR ANY PART THEREOF. 07/021'93 Alhcrt H. Halff Associates, Inc. L~AV012036~QUATTRO~COS'1'.WQI