Northlake 635(3)-LR 980617.CONCRETE COMPRr"3SIVE STRENGTH Date of Service: 05/I 9/1998 Report No.: Client No.: 52617000 Project No.: Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 981284 43-245~ Coppel] Belt Li~ Coppel] Services: Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples.** SLUMP: AIR: TEST METHOD: CO~rRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi @ 28 Days 5" max N/A ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 8:00 am BY: WEATHER CONDITIONS: Mild, s~ TEMPERATURE (F)-AIR 69 F ~ TRUCK NO: 84 1 TICK AIR CONTENT (%): N/A ur PLACEMENT LOCATION: Paving, north side of Building C SAMPLE LOCATION: 15'E of existing bldg., 10'S/N REPORT OF TESTS CYLINDER MEASURED MAXIMUM MARKED SLUMP DATE AGE LOAD SET NO. (inches) TESTED (days) (lbs. force) 1 1 6.50 05/26/1998 7 90870 1 2 6.50 05/26/1998 7 86220 Average I 3 6.50 06/16/1998 28 117460 1 4 6.50 06/16/1998 28 115710 Average A~ This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the ~ 01AK Page I of 5 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 .97 Report Date 06/17/1998 Business Center II ~e Rd. & Lakeshore Dr. Texas 'ed field test and cast BATCH TIME: 7:47 am ['erry L. Smith .nny .'ONCRETE: 76 F ~TNO: 712232 'IT WEIGHT (pcl): N/A 2CUMULATIVE YARDS: 60 COMPRESSIVE STRENGTH (psi) 3210 3050 3130 4150 4090 4120 FRACTURE TYPE ittcn approval of HBC Engineering, Inc. ,CONCRETE COMPR 3SIVE STRENGTH Date of Service: 05/19/1998 Report No.: 981284: Client No.: 52617000 Project No.: 43-2452 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Li~ Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi: compressive strength samples.** SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days 5" max N/A ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 8:50 am BY: WEATHER CONDITIONS: Mild, s TEMPERATURE (F) - AIR 71 F ( TRUCK NO: 1824 TICKI AIR CONTENT (%): N/A U~ PLACEMENT LOCATION: See page I SAMPLE LOCATION: 30'E/W, 15'N/S from existing paving REPORT OF TESTS CYLINDER MEASURED MAXIMUM MARKED SLUMP DATE AGE LOAD SET NO. (inches) TESTED (days) (lbs. force) 2 1 6.50 05/26/1998 7 78300 2 2 6.50 05/26/1998 7 79440 Average 2 3 6.50 06/16/1998 28 102680 2 4 6.50 06/16/1998 28 106780 Average A{ This report is exclusively for the use of the client indicated above and shall qot be reproduced except in full without the v 01AK Page 2 of 5 ENGINF_.ERII~, INC. 8901 Carpenter Frwy. Suite #100 Dallas, Texas 75247 Report Date 06/17/1998 -97 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 8:40 am ?erry L. Smith nny ONCRETE: 78 F :TNO: 712240 IT WEIGHT (pc0: N/A ~CUMULATIVE YARDS: 140 COMPRESSIVE STRENGTH (psi) 2770 2810 2790 3630 3780 3710 FRACTURE TYPE ' itten approval of HBC Engineering, Inc. · CONCRETE COMPRr"sSIVE STRENGTH Date of Service: 05/19/1998 Report No.: 981284: Client No.: 52617000 Project No.: 43-2452 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Lit Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples.** SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days 5" rnax N/A ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 10:15 am BY: WEATHER CONDITIONS: Mild, st TEMPERATURE (F)-AIR 70 F { TRUCK NO: 1805 TICKI AIR CONTENT (%): N/A u~ PLACEMENT LOCATION: See page I SAMPLE LOCATION: I O'S/N, 58'E/W CYLINDER MARKED SET NO. REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 3 1 6.50 05/26/1998 7 106040 3 2 6.50 05/26/1998 7 96680 Average 3 3 6.50 06/16/1998 28 142990 3 4 6.50 06/16/1998 28 144570 Average A~ This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the 01AK Page 3 of 5 ENGINEERING, 1NC. 8901 Carpenter Frwy., Suite gl00 Dallas, Texas 75247 -97 Report Date 06/17/1998 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 9:45 am ?erry L. Smith nny :ONCRETE: 76 F ~TNO: 712253 IT WEIGHT (pcf): N/A 7CUMULATIVE YARDS: 270 COMPRESSIVE STRENGTH (psi) 3750 3420 3590 5060 5110 5090 FRACTURE TYPE tten approval of HBC Engineering, Inc. · CONCRETE COMPR SIVE STRENGTH Date of Service: 05/19/t998 Report No.: 981284: Client No.: 52617000 Project No.: 43-2452 Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Coppell Belt Lir Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples.** SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days 5" max N/A ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 11:25 am BY: WEATHER CONDITIONS: Warm, TEMPERATURE (F}- AIR 73 F ( TRUCK NO: 846 TICK] AIR CONTENT (%): N/A v~ PLACEMENT LOCATION: See page I SAMPLE LOCATION: 70'E/W, 50'N/S from exist paving W CYLINDER MARKED SET NO. REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 4 I 5.50 05/26/1998 7 107370 4 2 5.50 05/26/1998 7 104320 Average 4 3 5.50 06/16/1998 28 153250 4 4 5.50 06/I 6/I 998 28 155490 Average Al This report is exclusively tbr the use of the client indicated above and shall not be reproduced except in full without the x 01AK Page 4 of 5 ENGINEERING, INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 06/17/1998 -97 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 1 1:04 am ?erry L. Smith unny iONCRETE: 81 F ;TNO: 712264 IT WEIGHT (pcf): N/A ~'CUMULATIVE YARDS: 380 COMPRESSIVE STRENGTH (psi) 3800 3690 3750 5420 5500 5460 FRACTURE TYPE itten approval of HBC Engineering, Inc. CONCRETE COMPRt' SIVE STRENGTH Date of Service: 05/19/1998 Report No.: 981284: Client No.: Client: Services: 52617000 Project No.: 43-245: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Lit Coppell Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples.** CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi @ 28 Days SLUMP: 5" Il'lax PROJECT DATA -97 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 06/17/1998 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast CONCRETE CLASS: 9351 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 12:05 pm aY: Terry L. Smith WEATHER CONDITIONS: Warm, ~unny / TEMPERATURE (F) - AIR 78 F (~ONCRETE: 88 TRUCK NO: 1805 TICKet NO: 712273 BATCH TIME: 1 1 '5 1 am F AIR: N/A TEST METHOD: ASTM C- 143 ASTM C- 172 ASTM C-39 SAMPLE LOCATION: CYLINDER MARKED SET NO. 5 1 5 2 5 3 5 4 AIR CONTENT (%): N/A PLACEMENT LOCATION: See page I From NEC of bldg. 65'W/E, 15'N/S REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 5.50 05/26/1998 5.50 05/26/1998 5.50 06/16/1998 5.50 06/16/1998 7 94430 7 88200 Average 28 136040 28 130980 Average Technician: Terry L. Smith Report Distribution: (1) Lincoln Property Company (1) Butler Construction (1) O'Brien & Associates (I) AECC, Inc. Ub A~ Started: 6:00 am Finished: 1:00 pm H~ ( I ) City of Coppell/BIdg. Insp. (I) City of Coppell/Constr. Insp. (I) Mullen & Powell Technistructures This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the w IT WEIGHT (pcf): N/A 7CUMULATIVE YARDS: 470 COMPRESSIVE STRENGTH (psi) 3340 3120 3230 4810 4630 4720 .~ Enginee Eugene Harbour Vice President FRACTURE TYPE :ittcn approval of HBC Engineering, Inc. 01AK Page 5 of 5 CONCRETE COMPtLr' , SIVE STRENGTH Date of Service: 05/19/1998 Report No.: 9812861 Client No.: 52617000 Project No.: 43-2452 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Li~ Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi: compressive strength samples.** CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLA~r: 16 SPECIFICATION REQUIREMENTS STRENGTH: SLUMP: AIR: TEST METHOD: 5000 psi ~ 28 Days ASTM C-143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9373 PLACEMENT DATE: 05/19/1998 TIME SAMPLED: 1:33 pm BY: WEATHER CONDITIONS: Hazy, TEMPERATURE (F) - AIR 76 F ~ TRUCK NO: 853 TICK] AIR CONTENT (%): N/A u~ PLACEMENT LOCATION: Column pad at north end SAMPLE LOCATION: Same CYLINDER MARKED SET NO. MEASURED SLUMP (inches) 1 1 4.50 1 2 4.50 1 3 4.50 1 4 4.50 REPORT OF TESTS MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) 05/26/1998 7 106460 05/26/1998 7 100080 Average 06/16/1998 28 140390 06/16/1998 28 130660 Average Technician: Terry L. Smith Report Distribution: (1) Lincoln Property Company (I) Butler Construction (I) O'Brien & Associates (I) AECC. Inc. Started: 1:00 pm Finished: 4:00 pm ~ (i) City of Coppell/BIdg. Insp. (1) City ofCoppell/Constr. Insp. (1) Mullen & Powell Technistructures This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the -97 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 06/17/1998 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 12:35 pm ?erry L. Smith arm iONCRETE: 83 F ~T NO: 112034 IT WEIGHT (pcf): N/A ,'CUMULATIVE YARDS: 28 COMPRESSIVE STRENGTH (psi) 3760 3540 3650 4960 4620 4790 FRACTURE TYPE Inc. Eugene Harbour Vice President w 'itten approval of HBC Engineering, Inc. 01AK Page I of I