Northlake 635(3)-LR 980715CONCRETE COMPRI"',SIVE STRENGTH TE?
Date of Service: 06/10/1998
Report No.: 981496~
Client No.: 52617000 Project No.: 43-2452
Client: Lincoln Property Company Project:
3300 Lincoln Plaza/Larry Moon
500 North Akard Street
Dallas TX 75201-3394
Coppell
Belt Lin
Coppell
Services: Obtain samples of fresh concrete at the placement locations, perform requi~
compressive strength samples.
SLUMP:
AIR:
TEST METHOD:
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer Concrete
PLANT: 16
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi ~ 28 Days
3-5%
ASTM C-143
ASTM C- 172
ASTM C-39
PROJECT DATA
CONCRETE CLASS: 9351
PLACEMENT DATE: 06/10/1998
TIME SAMPLED: 6:40 am BY:
WEATHER CONDITIONS: Partly
TEMPERATURE (F) - AIR 80 F
TRUCK NO: 769 TICK1
AIR CONTENT (%): 3.5
PLACEMENT LOCATION:
Paving, west side of Building C
SAMPLE LOCATION: 40'N/S, 50'E/W from SWC of Bldg. C
REPORT OF TESTS
CYLINDER MEASURED MAXIMUM
MARKED SLUMP DATE AGE LOAD
SET NO. (inches) TESTED (days) (lbs. force)
1 1 6.50 06/17/1998 7 121360
1 2 6.50 06/17/1998 7 116300
Average
1 3 6.50 07/08/1998 28 145210
1 4 6.50 07/08/1998 28 143770
Average
This report is exclusively lbr the use of the client indicated above and sball not be reproduced except in full without the v
01AK Page 1 of 4
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
.97
Report Date
07/15/1998
Business Center II
e Rd. & Lakeshone Dr.
Texas
ed field test and cast
BATCH TIME: N/A
'erry L. Smith
oudy
ONCRETE: 83 F
:TNO: 712562
IT WEIGHT (pcf}: N/A
~CUMULATIVE YARDS: 70
COMPRESSIVE
STRENGTH
(psi)
4290
4110
4200
5140
5080
5110
FRACTURE
TYPE
itten approval of HBC Engineering, inc.
CONCRETE COMPRf ,SIVE STRENGTH TE?
Date of Service: 06/10/1998 Report No.: 981496~
Client No.: 52617000 Project No.: 43-245~
Client: Lincoln Property Company Project:
3300 Lincoln Plaza/Larry Moon
500 North Akard Street
Dallas TX 75201-3394
Coppell
Belt Lit
Coppell
Services: Obtain samples of fresh concrete at the placement locations, perform requi
compressive strength samples.
SLUMP:
AIR:
TEST METHOD:
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer Concrete
PLANT: 16
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi ~ 28 Days
5"
3-5%
ASTM C-143
ASTM C- 172
ASTM C-39
PROJECT DATA
CONCRETE CLASS: 9351
PLACEMENT DATE: 06/10/1998
TIME SAMPLED: 7:56 am BY:
WEATHER CONDITIONS: Cloudy
TEMPERATURE (F)-AIR 81 F (
TRUCK NO: 769 TICK]
AIR CONTENT (%): 3.5 ub
PLACEMENT LOCATION:
See page I
SAMPLE LOCATION: 55'SAN, 25'E/W from SWC of Bldg. C
REPORT OF TESTS
CYLINDER MEASURED MAXIMUM
MARKED SLUMP DATE AGE LOAD
SET NO. (inches) TESTED (days) (lbs. force)
2 1 5.50 06/17/1998 7 140010
2 2 5.50 06/17/1998 7 136710
Average
2 3 5.50 07/08/1998 28 162550
2 4 5.50 07/08/1998 28 163770
Average
A~
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the ~
01AK Page 2 of 4
ENGINF_.ER]I~, INC.
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Report Date
07/15/1998
.97
Business Center II
e Rd. & Lakeshore Dr.
Texas
ed field test and cast
BATCH TIME: 7:35 am
?erry L. Smith
:ONCRETE: 89 F
;T NO: N/A
IT WEIGHT (pcf): N/A
.'CUMULATIVE YARDS:
COMPRESSIVE
STRENGTH
(psi)
4950
4830
4890
5750
5790
5770
170
FRACTURE
TYPE
'itten approval of HBC Engineering, Inc.
CONCRETE COMPR r ,SIVE STRENGTH TE?
Date of Service: 06/10/1998
Report No.: 981496,
Client No.: 52617000
Project No.: 43-245~
Client: Lincoln Property Company Project:
3300 Lincoln Plaza/Larry Moon
500 North Akard Street
Dallas TX 75201-3394
Coppell
Belt Li~
Coppell
Services: Obtain samples of fresh concrete at the placement locations, perform requi
compressive strength samples.
SLUMP:
AIR:
TEST METHOD:
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer Concrete
PLANT: 16
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi ~ 28 Days
5"
3-5%
ASTM C- 143
ASTM C- 172
ASTM C-39
PROJECT DATA
CONCRETE CLASS: 9351
eLACEMENT DATE: 06/10/1998
TIME SAMPLED: 9:30 am BY:
WEATHER CONDITIONS: Cloudy
TEMPERATURE (F) - AIR 85 F
TRUCK NO: 763 TiCK
AIR CONTENT (%): 3.2
PLACEMENT LOCATION:
See page I
SAMPLE LOCATION: 80'S/N, 45'E/W from SWC of Bldg. C
CYLINDER
MARKED
SET NO.
REPORT OF TESTS
MEASURED MAXIMUM
SLUMP DATE AGE LOAD
(inches) TESTED (days) (lbs. force)
3 1 5.50 06/17/1998 7 139970
3 2 5.50 06/17/1998 7 134110
Average
3 3 5.50 07/08/1998 28 159650
3 4 5.50 07/08/1998 28 162000
Average
Al
This report is exclusively tbr the use oftbe client indicated above and shall not be reproduced except in full without the ~
01AK Page 3 of 4
8901 Carpenter Frwy., Suite gl00
Dallas, Texas 75247
,97
Report Date
07/15/1998
Business Center II
~e Rd. & Lakeshore Dr.
Texas
'ed field test and cast
BATCHTIME: 9:13 am
['erry L. Smith
:ONCRETE: 89
~TNO: 712584
IT WEIGHT (pcf): N/A
iCUMULATIVE YARDS: 280
COMPRESSIVE
STRENGTH
(psi)
4950
4740
4850
5650
5730
5690
FRACTURE
TYPE
itten approval of HBC Engineering, Inc.
CONCRETE COMPRI SIVE STRENGTH TE C" .
Date of Service: 06/10/1998
Report No.: 981490
Client No.:
Client:
Services:
52617000 Project No.: 43-2452
Lincoln Property Company
3300 Lincoln Plaza/Larry Moon
500 North Akard Street
Dallas TX 75201-3394
Project: Coppell
Belt Lie
Coppell
Obtain samples of fresh concrete at the placement locations, perform requi:
compressive strength samples.
PROJECT DATA
CONCRETE CLASS: 9351
PLACEMENT DATE: 06/10/1998
TIME SAMPLED: 10:55 am BY:
WEATHER CONDITIONS: Partly
TEMPERATURE (F) - AIR 88 F (
TRUCK NO: 845 TICK]
AIR CONTENT (%): 3.0
PLACEMENT LOCATION:
See page 1
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer Concrete
PLANT: 1 6
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi ~ 28 Days
SLUMP: 5"
AIR: 3-5%
TEST METHOD: ASTM C- 143
ASTM C- 172
ASTM C-39
SAMPLE LOCATION: 70'S, 65'E/W from SWC of Bldg. C
CYLINDER MEASURED
MARKED SLUMP DATE
SET NO. {inches} TESTED
4 1 5.75 06/17/1998
4 2 5.75 06/17/1998
4 3 5.75 07/08/1998
4 4 5.75 07/08/1998
REPORT OF TESTS
Technician: Terry L. Smith
Report Distribution:
(1) Lincoln Property Company
(I) Butler Construction
(I) O'Brien & Associates
(I) AECC, Inc.
MAXIMUM
AGE LOAD
(days) (lbs. force)
7 137210
7 139770
Average
28 159990
28 163440
Average
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
-97
Report Date
07/15/1998
Business Center II
e Rd. & Lakeshore Dr.
Texas
ed field test and cast
Started: 4:00 am Finished: 3:30 pm I-~
(1) City ofCoppcll/Bldg. Insp.
(1) City of Coppell/Constr. Insp.
(1) Mullen & Powell Technistructures
BATCHTIME: 10:30 am
'erry L. Smith
oudy
IONCRETE: 90 F
;TNO: 712593
IT WEIGHT (pcf): N/A
At
2CUMULATIVE YARDS: 370
COMPRESSIVE
STRENGTH
(psi)
This report is exclusively tbr the use of the client indicated above and shall not be reproduced except in full without the w
4850
4940
4900
5660
5780
5720
FRACTURE
TYPE
-~ Enginee~~.~
Eugene ~our
Vice President
'itten approval of HBC Engineering, Inc.
01AK Page 4 of 4
CONCRETE COMPR SIVE STRENGTH'.
Date of Service: 06/10/1998 Report No.: 981496~
Client No.: 52617000 Project No.: 43-2455
Client:
Lincoln Property Company
3300 Lincoln Plaza/Larry Moon
500 North Akard Street
Dallas TX 75201-3394
Project: Coppell
Belt Lit
Coppell
Services: Obtain samples of fresh concrete at the placement locations, perform requi
compressive strength samples.
SLUMP:
AIR:
TEST METHOD:
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer Concrete
PLANT: 16
SPECIFICATION REQUIREMENTS
STRENGTH: 3500 psi ~ 28 Days
5"
N/A
ASTM C- 143
ASTM C- 172
ASTM C-39
PROJECT DATA
CONCRETE CLASS: 9337
PLACEMENT DATE: 06/10/1998
TIME SAMPLED: 1:42 pm BY:
WEATHER CONDITIONS: Partly
TEMPERATURE (F) - AIR 91 F t
TRUCK NO: 845 TICK]
Am CONTENT (%): N/A o~
PLACEMENT LOCATION:
Columns 22, 23, 26
SAMPLE LOCATION: Column 22
CYLINDER MEASURED
MARKED SLUMP
SET NO. (inches)
I 1 5.50
I 2 5.50
I 3 5.50
I 4 5.50
Technician time on report
REPORT OF TESTS
DATE
TESTED
06/17/t 998
06/17/1998
07/08/1998
07/08/1998
9814966.
MAXIMUM
AGE LOAD
(days) (lbs. force)
7 88690
7 92460
Average
28 109300
28 113840
Average
At
Technician: Terry L. Smith
Report Distribution:
(I) Lincoln Property Company
(I) Butler Constructiou
(I) O'Brien & Associates
(1) AECC, Inc.
Started:
Finished:
(I) City ofCoppell/Bldg. Insp.
(I) City ofCoppell/Constr. Insp.
( 1 ) M ulleu & Powell Teclmistructures
ENGINEERING, INC.
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
iA Report Date
07/15/1998
-97
Business Center II
e Rd. & Lakeshore Dr.
Texas
ed field test and cast
BATCHTIME: 1:40 pm
?erry L. Smith
oudy
iONCRETE: 90 F
~TNO: 712601
IT WEIGHT (pcf): N/A
2CUMULATIVE YARDS: 60
COMPRESSIVE
STRENGTH
(psi)
3140
3270
3210
3870
4030
3950
ng, Inc.
FRACTURE
TYPE
Tiffs report is exclusively tbr the use of the client iudicated above and shall not be reproduced except in full without the w
Vice President
ittcn approval of HBC Engineering, Inc.
01AK Page I of I