Northlake 635(3)-LR 980731 CONCRETE COMPRr"sSIVE STRENGTH TEar Date of Service: 07/21/1998 Report No.: Client No.: 52617000 Project No.: Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 981866 43-245; Coppell Belt Lit Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples. SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi @ 28 Days 3-5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENX DATE: 07/21/1998 TIME SAMPLED: 12:00 pm WEATHER CONDITIONS: Clear, h TEMPERATURE (F)-AIR 98 F ( TRUCK NO: 857 TICK AIR CONTENT (%): 5.1 PLACEMENT LOCATION: Paving, Building D - southwest corner of bui! SAMPLE LOCATION: 70'E/12'S REPORT OF TESTS CYLINDER MEASURED MARKED SLUMP DATE SET NO. (inches) TESTED 1 I 6.50 07/28/1998 1 2 6.50 07/28/1998 MAXIMUM AGE LOAD (days) (lbs. force) 7 103250 7 106550 Average I 3 6.50 08/18/1998 28 ! 4 6.50 08/18/1998 28 This report is exclusively lbr the use of the client indicated above and shall uot be reproduced except in full without the 01AK Page I of 2 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 07/31/1998 -97 Business Center II te Rd. & Lakeshore Dr. Texas 'ed field test and cast BATCHTIME: I 1:10 am (eith Fowler >t :ONCRETE: 97 F ~T NO: 729064 IT WEIGHT (pcf): N/A ding A~2CUMULATIVE YARDS: 80 COMPRESSIVE STRENGTH (psi} 3650 3770 3710 FRACTURE TYPE itten approval of HBC Engineering, Inc. ,CONCRETE COMPR SIVE STRENGTH Date of Service: 07/21/1998 Report No.: Client No.: 52617000 Project No.: Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 No~h Akard Street Dallas TX 75201-3394 981866~ 43-2452 Coppell Belt Lin Coppell Services: Obtain samples of fi'esh concrete at the placement locations, perform requi~ compressive strength samples. SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTm 4000 psi ~ 28 Days 3-5" 3-6% ASTM C-143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 07/21 / 1998 TIME SAMPLED: 1:30 pm BY: WEATHER CONDITIONS: Partly TEMPERATURE (F) - AIR 103 F TRUCK NO: 857 TICKI AIR CONTENT (%): 5.0 UN PLACEMENT LOCATION: Paving, Building B - southeast approach SAMPLE LOCATION: South end of southeast approach CYLINDER MEASURED MARKED SLUMP SET NO. (inches) 2 1 5.50 2 2 5.50 2 3 5.50 2 4 5.50 REPORT OF TESTS MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) 07/28/1998 7 92690 07/28/1998 7 88820 Average 08/18/1998 28 08/18/1998 28 A( Technician: Keith Fowler Report Distribution: (1) Lincoln Property Company (1) Butler Construction ( I ) O'Brien & Associates (1) AECC, Inc. Started: 8:00 am Finished: 2:00 pm I-~ (1) City ofCoppell/Bldg, lusp. (1) City ofCoppell/Constr, lusp, (I) Mulleu & I)owell Technistructures This report is exclusively lbr the use of the client indicated above aud shall not be reproduced except in full without the ENGINEERING, INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 .97 Report Date O7/31/1998 Business Center II e Rd. & Lakeshore Dr. Texas 'ed field test and cast BATCH TIME: I 1:55 am ~eith Fowler oudy, hot ONCRETE: 98 V :TNO: 729068 IT WEIGHT (pcO: N/A :CUMULATIVE YARDS: COMPRESSIVE STRENGTH (psi) 3280 3140 3210 120 FRACTURE TYPE Eugene Harbour Vice President wi itten approval of HBC Engineering, Inc. 01AK Page 2 of 2