Northlake 635(3)-LR 980808REPORT OF STRUCT"' RAL STEEL INSPECi" N Date of Service: 07/30/1998 Client No.: 52617000 Report No.: 9820291 Project No.: 43-2452 -97 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 08/08/1998 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Services: Structural steel inspection. Project: Coppell Belt Lit Coppell Business Center II e Rd. & Lakeshore Dr. Texas On this date, an HBC Engineering representative arrived at the above jobsite as scheduled for structural steel inspection on the roof dec visit was made to review roof deck attachment conditions. Observati follows: 1. Roof deck panels were welded to supports on 12-inch centers instead of the specified 6-inch centers for pin type fastnez Therefore, welds were not inspected (see General Note on Sl 2. Deck support angle butt splices were not welded at the vert: legs. 3. Deck angle was not welded to panel embeds at several locati¢ It should be noted that not all connections were accessible to coverage by deck. 4. Missing or misplaced side lap screws were marked with orange paint. 5. Damaged deck was marked for correction at two (2) locations along M line. (1) City ofCoppell/Bldg. Insp. (I) City ofCoppell/Constr. Insp. ( I ) Mullen & Powell Technistructures Technician: Ray Waldrop Report Distribution: ( I ) Lincoln Property Company (1) Butler Construction (I) O'Brien & Associates (I) AECC, luc. referenced A jobsite ons were as So This report is exclusively lbr tim use of the client indicated above and shall not be reproduced except in lull without the w c. al rl S. due .. E ng, Inc. aul D. Smith, P.E. :nior Project Engineer 'itten approval of HBC Engineering, inc. 99SS Page I of I