Northlake 635(3)-LR 980813CONCRETE COMPR r' SIVE STRENGTH TE? Date of Service: 08/03/1998 Report No.: 982032 Client No.: 52617000 Project No.: 43-245~ Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppel! Belt Li~ Coppel Services: Obtain samples of fresh concrete at the placement locations, perform requi compressive strength samples. CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days SLUMP: 5" Aim N/A TEST METHOD: ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 08/03/199~ TIME SAMPLED: 8:49 am BY: WEATHER CONDITIONS: clear an TEMPERATURE (F)-AIR 92 F , TRUCK NO: 518 TICK AIR CONTENT (%): N/A ur PLACEMENT LOCATION: Paving of driveway on westside of property. SAMPLE LOCATION: 160' N and 8' W/see diagram CYLINDER MEASURED MARKED SLUMP SET NO. (inches) I I 6.75 1 2 6.75 I 3 6.75 I 4 6.75 REPORT OF TESTS MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) 08/10/1998 7 90190 08/10/1998 7 90120 Average 08/31/1998 28 08/31/1998 28 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 08/13/1998 .97 Business Center II te Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 8:34 am 2)anny Neu d hot ~ONCRETE: 93 F ET NO: 732828 tiT WEIGHT (pc0: N/A See attached diagram. ECUMULATIVE YARDS: 220 COMPRESSIVE STRENGTH (psi) 3190 3190 3190 FRACTURE TYPE Technician: Danny Neu Report Distribution: (I) Lincoln Property Company ( I } Butler Construction (1) O'Brien & Associates (1) AECC, Inc. Started: 8:00 am Finished: 10:30 ( I ) City of Coppell/BIdg. lnsp. (I) City of Coppcll/Constr. Insp. (I) Muller & Iowell Technistmctures This report is exclusively lbr thc usc of the client indicated above and shall not be reproduced except in tull without the Eugene Harbour Vice President ritten approval of HBC Engineering, Inc. 01AK Page ! of 1 CONCRETE COMPR SIVE STRENGTH Date of Service: 07/23/1998 Report No.: 981890.'. Client No.: 52617000 Project No.: 43-2452 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Lin Coppell Services: Obtain samples of fresh concrete at the placement locations, perform requi: compressive strength samples. PROJECT DATA CONTRACTOR: Butler Construction CONCRETE CLASS: 9349 CONCRETE SUPPLIER: Pioneer Concrete PLACEMENT DATE: 07/23/1998 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 08/13/1998 .97 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 8:43 am PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days SLUMP: 5" AIR: N/A TEST METHOD: ASTM C-143 ASTM C- 172 ASTM C-39 SAMPLE LOCATION: Southeast corner CYLINDER MARKED SET NO. MEASURED SLUMP (inches) I I 6.50 1 2 6.50 1 3 6.50 1 4 6.50 TIME SAMPLED: 9:00 am BY: ¥ince McManis WEATHER CONDITIONS: Warm, ~umid,'~ clear TEMPERATURE (F) - AIR 91 F (~ONCRETE: 82 TRUC~ NO: 858 TIC~kT NO: 729079 AIR CONTENT (%): N/A w PLACEMENT LOCATION: Building D interior leaveout along walls REPORT OF TESTS MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) 07/30/1998 7 105470 07/30/1998 7 100710 Average 08/20/1998 28 08/20/1998 28 F A IT WEIGHT (pcO: N/A UCUMULATIVE YARDS: COMPRESSIVE STRENGTH (psi) 3730 3560 3650 Technician: Vince McManis Report Distribution: ( I ) Lincoln Property Company (I) Butler Construction (I) O'Brien & Associates (I) AECC. Inc. Started: 8:00am Finished: 11:00 (1) City ofCoppell/Bldg, lnsp. (1) City ofCoppell/Constr. Insp. (1) Mullen & Powell Technistructures nc. Vice President 40 FRACTURE TYPE This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the v · itten approval of HBC Engineering, Inc. 01AK Page 1 of I CONCRETE COMPRr SIVE STRENGTHTM Date of Service: 07/14/1998 Client No.: 52617000 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Report No.: 98179~. Project No.: 43-24 Project: Copp¢ Belt Li Coppel Services: Obtain samples of fresh concrete at the placement locations, perform requ compressive strength samples. SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 935 1 PLACEMENT DATE: 07/14/199~ TIME SAMPLED: 6:05 am BY: WEATHER CONDITIONS: Partly { TEMPERATURE (F) - AIR 80 F TRUCK NO: 1883 TiCk AIR CONTENT (%): 4.5 U PLACEMENT LOCATION: Paving, parking on east side of Building A; ~ SAMPLE LOCATION: From NE corner, 3'W/4'S CYLINDER MARKED SET NO. REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) I 1 5.50 07/21/1998 7 82250 i 2 5.50 07/21/1998 7 81500 Average ! 3 5.50 08/11/1998 28 116010 1 4 5.50 08/11/1998 28 110700 Average This report is exclusively tbr the use of the client indicated above and shall not be reproduced except in full without the 01AK Page I of 6 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 ~4 2-97 Report Date 08/13/1998 Business Center II e Rd. & Lakeshore Dr. I, Texas ired field test and cast BATCH TIME: 5:30 am Iack Farris Ioudy CONCRETE: 98 F ~.T NO: 728852 ~IT WEIGHT (PC0: N/A ce attached diagram CCUMULATIVE YARDS: 40 COMPRESSIVE STRENGTH (psi) 2910 2880 2900 4100 3910 4010 FRACTURE TYPE ritten approval of HBC Engineering, Inc. . CONCRETE COMP SIVE STRENGTH TE Ir' Date of Service: 07/14/1998 Report No.: Client No.: 52617000 Project No.: Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 98179~ 43-245 Coppel Belt Li Coppe] Services: Obtain samples of fresh concrete at the placement locations, perform requ compressive strength samples. SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTlt: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 07/14/1991 TIME SAMPLED: 7:35 am BY: WEATHER CONDITIONS: Partly TEMPERATURE (F) - AIR 82 F TRUCK NO: 8 5 3 AIR CONTENT (%): 5.0 U PLACEMENT LOCATION: See page I SAMPLE LOCATION: CYLINDER MARKED SET NO. From NW corner, 15 yds S, 3 yds E REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 2 1 5.25 07/21 / 1998 7 75430 2 2 5.25 07/2 ! / ! 998 7 81250 Average 2 3 5.25 08/1 !/1998 28 109810 2 4 5.25 08/11/1998 28 112780 Average 01AK This report is exclusively lbr tile use of the client indicated above and shall not be reproduced except in full without the Page 2 of 6 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 08/13/1998 2-97 Business Center II e Rd. & Lakeshore Dr. 1, Texas ired field test and cast BATCH TIME: 6:47 am [ack Farris unny CONCRETE: 98 F ]~T NO: 728862 ~IT WEIGHT (pcf): N/A CCUMULATIVE YARDS: 140 COMPRESSIVE STRENGTH (psi) 2670 2870 2770 3880 3990 3940 FRACTURE TYPE Tittcn approval of HBC Engineering, Inc. ,CONCRETE COMPRr' SIVE STRENGTH TE? . Date of Service: Client No.: Client: Services: 07/14/1998 52617000 Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Report No.: 98179~ Project No.: 43-245 Project: Coppel Belt Li Coppel Obtain samples of fresh concrete at the placement locations, perform requ compressive strength samples. SLUMP: AIR: TEST METltOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STgENGTU: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9351 PLACEMENT DATE: 07/14/1991 TIME SAMPLED: 9:19 am BY: WEAmER ~ONmTIONS: Partly TEMPERATURE (F) - AIR 88 F TRUCK NO: 1883 TI( AIR CONTENT (%): 5.0 PLACEMENT LOCATION: See page I SAMPLE LOCATION: F,'om SEC of paving. 5 yds W. 2' N CYLINDER MARKED SET NO. REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 3 I 6.00 07/21/i 998 7 83950 3 2 6.00 07/21 / 1998 7 84980 Average 3 3 6.00 08/11/1998 28 104150 3 4 6.00 08/1 !/1998 28 111160 Average This report is exclusively for thc usc of Ibc client indicated above and shall not be reproduced except in lull without tile OIAK Page 3 of 6 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 4 Report Date 08/13/1998 2-97 Business Center II te Rd. & Lakeshore Dr. I, Texas red field test and cast BATCH TIME: 8:00 am lack Farris unny 2ONCRETE: 98 F ETNO: 728873 U] qlT WEIGHT (pc0: N/A ^CCUMULATIVE YARDS: 240 COMPRESSIVE STRENGTH (psi) 2970 3010 2990 3680 3930 3810 FRACTURE TYPE ritten approval of HBC Engineering, Inc. · CONCRETE COMPRt SIVE STRENGTH Date of Service: 07/14/1998 Report No.: 981799 Client No.: 52617000 Project No.: 43-245', Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppel Belt Li~ Coppel Services: Obtain samples of fresh concrete at the placement locations, perform requ: compressive strength samples. SLUMP: AIR: TEST METHOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: ] 6 SPECIFICATION REQUIREMENTS STRENGTa: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 93 51 PLACEMENT DATE: 07/14/199~ TIME SAMPLED: I 1.'30 am BY: WEATHER CONDITIONS: Sunny TEMPERATURE (F)- AIR 90 F , TRUCK NO: 1883 TICk AIR CONTENT (%): 5.5 UI PLACEMENT LOCATION: Paving, parking on south side of Building A SAMPLE LOCATION: From SWC of bldg., 8 yds S, 4'E CYLINDER MARKED SET NO. REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 4 1 5.00 07/21 / 1998 7 56590 4 2 5.00 07/21/1998 7 84910 Average 4 3 5.00 08/i 1/1998 28 107920 4 4 5.00 08/! 1 / 1998 28 103880 Average Note: Trucks ran over the reinforcing steel, damaging it and also Reinforcing steel was not replaced. See attached diagram. This report is exclusively tbr the use of the client indicated above and shall not be reproduced except in lhll without the 01AK Page 4 of 6 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 4 Report Date 08/13/1998 >.-97 Business Center II ~e Rd. & Lakeshore Dr. Texas ed field test and cast BATCHTIME: 10:05 am Iack Farris 2ONCRETE: 95 ET NO: 728883 ~I1T WEIGHT (pcf): N/A CCUMULATIVE YARDS: 340 COMPRESSIVE STRENGTH (psi) 2000 3000 2500 3820 3670 3750 :he grade. FRACTURE TYPE 'ritten approval of HBC Engineering, Inc. . CONCRETE COMPRr"sSIVE STRENGTH Date of Service: 07/14/1998 Report No.: Client No.: 52617000 Project No.: Client: Lincoln Property Company Project: 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201~3394 981799 43 -245 Coppel Belt Li: Coppel Services: Obtain samples of fresh concrete at the placement locations, perform requ compressive strength samples. PROJECT DATA SLUMP: AIR: TEST METtlOD: CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer Concrete PLANT: I 6 SPECIFICATION REQUIREMENTS STRENGTlt: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 SAMPLE LOCATION: I:rom NWC of paving, 14 yds E, 4'S CYLINDER MARKED SET NO. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 4 Report Date 08/13/1998 ~.-97 Business Center II te Rd. & Lakeshore Dr. Texas ed field test and cast CONCRETE CLASS: 9351 PLACEMENT DATE: 07/14/199: TIME SAMPLED: 1:05 pm BY: WEATHER CONDITIONS: Partly unny TEMPERATURE (F)- AIR 100 F 2ONCRETE: 98 F TRUCKNO: 515 TI( ETNO: 728894 AIR CONTENT (%): 5.5 U1 ~IT WEIGHT (pc0: N/A PLACEMENT LOCATION: Paving, parking on south side of Building A REPORT OF TESTS MEASURED MAXIMUM SLUMP DATE AGE LOAD (inches) TESTED (days) (lbs. force) 5 1 5.75 07/21/1998 7 75340 5 2 5.75 07/21/1998 7 83200 Average 5 3 5.75 08/1 t/1998 28 103010 5 4 5.75 08/11/1998 28 109650 Average This report is exclusively lbr the usc of the client indicated above and shall not be reproduced except in full without the v BATCHT1ME: 12:08 pm lack Farris AUCUMULATIVE YARDS: 440 COMPRESSIVE STRENGTH (psi) 2660 2940 2800 3640 3880 3760 FRACTURE TYPE ritten approval of ItBC Engineering, Inc. 01AK Page 5 of 6 .CONCRETE COMPRr'SSIVE STRENGTH Date of Service: 07/14/1998 Client No.: 52617000 Client: SLUMP: AIR: TEST METllOD: Services: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Report No.: 981799 Project No.: 43-2451 Project: Coppel Belt Li~ Coppel Obtain samples of fresh concrete at the placement locations, perform requ compressive strength samples. CONTRACTOR: Butler Construction CONCRETE SIJPPLIER: Pioneer Concrete PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi ~ 28 Days 5" 3-6% ASTM C- 143 ASTM C- 172 ASTM C-39 SAMPLE LOCATION: NWC of paving, 6 yds E, 8 yds S PROJECT DATA CONCRETE CLASS: PLACEMENT DATE: 9351 07/14/199~ TIME SAMPLED: 3:15 pm BY: WEATHER CONDITIONS: Sunny, TEMPERATURE (F) - AIR 101 TRUCK NO: 1 883 TICl4 AIR CONTENT (%): 5.0 PLACEMENT LOCATION: Paving, parking on south side of Building A REPORT OF TESTS A MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) CYLINDER MARKED SET NO. MEASURED SLUMP (inches) 6 1 5.25 6 2 5.25 6 3 5.25 6 4 5.25 Technician: .lack Farris Report Distribution: ( I ) Lincoln Properly Company (I) Butler Construction ( I ) O'Brien & Associates ( I ) AECC. Inc. 07/21/1998 7 99430 07/21 / 1998 7 96060 Average 08/I 1/1998 28 115490 08/I 1/1998 28 117950 Average Started: 4:00 am Finished: 4:00 pm I--~ ( I ) City of Coppell/Bldg. lnsp. ( I ) City of Coppell/Constr. lasp. (I) Mullcn & Powcll Tecbnistructures ENGINEERING, lNG. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 4 Report Date 08/13/1998 >.-97 Business Center II ~e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 2:05 pm Tbis report is exclusively tbr the use ol'the client indicated above and shall not be reproduced except in full without the lack Farris hot 2ONCRETE: 98 F ET NO: 728906 lit WEIGHT (pcf}: N/A ECUMULATIVE YARDS: 550 COMPRESSIVE STRENGTH (psi) 3520 3400 3460 4080 4170 4130 FRACTURE TYPE ~ Engine Eugene HaSCbour Vice President ritten approval of HBC Engineering, Inc. 01AK Page 6 of 6 CONCRETE COMPI:G' SIVE STRENGTH Date of Service: 08/04/1998 Report No.: 9820451 Client No.: 52617000 Project No.: 43-2455 Client: Lincoln Property Company 3300 Lincoln Plaza/Larry Moon 500 North Akard Street Dallas TX 75201-3394 Project: Coppell Belt Lit Coppell Services: Obtain salnples of fresh concrete at the placement locations, perform requi: compressive strength samples. CONTRACTOR: Butler Construction CONCRETE SUPPLIER: Pioneer PLANT: 16 SPECIFICATION REQUIREMENTS STRENGTlt: 4000 psi ~ 28 Days SLUMP: 5" Am: N/A 'rEST METHOD: ASTM C- 143 ASTM C- 172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9349 PLACEMENT DATE: 08/04/1998 TIME SAMP. LED: 6:36 am BY: WEATHER CONDITIONS: clear TEMPERATURE (F)- AIR 81 TRUCK NO: 802 TICKI AIR CONTENT (%): N/A u~ PLACEMENT LOCATION: Northwest building, paving: See attached dis border. SAMPLE LOCATION: NW building 120'S and YW CYLINDER MARKED SET NO. MEASURED SLUMP (iuches) 1 1 5.50 I 2 5.50 I 3 5.50 I 4 5.50 REPORT OF TESTS MAXIMUM DATE AGE LOAD TESTED (days) (lbs. force) 08/11/1998 7 116110 08/11/1998 7 113480 Average 09/01/1998 28 09/01/1998 28 ENGINEERII~, INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 -97 Report Date 08/13/1998 Business Center II e Rd. & Lakeshore Dr. Texas ed field test and cast BATCH TIME: 6:10 am )army Neu warm )NCRETE: 89 ~ :TNO: 732836 ITWEIGHT (pcf): N/A ram. West border (perimeter) and north CUMULATIVE YARDS: 20 COMPRESSIVE STRENGTH (psi) 4110 4010 4060 FRACTURE TYPE Technician: Danlly Neu Report Distribution: ( I ) Lincoln Properly Company ( I } Butler Cotlstructio~ (1) O'Bricn & Associates 11) AECC, hlc. Started: 5:30 am Finished: 10:00 ( I ) City ol'Coppell/Bldg, lusp. ( I ) City ol'Coppcll/Constr, lnsp. ( I ) Mullcn & Powell T¢cbnistructures ~E.~e~gi2~ur~ Vice President This report is exclusively lbr tbe usc of the client indicated above and shall not be reproduced except in full without the w; itten approval of HBC Engineering, Inc. 01AK Page I of I