Northlake 635(5)-LR000828CONCRETE COMPRE IVE STRENGTH
Date of Service: 07/26/2000
Client No.: 85229000
Client: Transwestem Property Company
Attn: James Gaspard
12221 Merit Drive, g450
Dallas TX 75251
Report No.: 0019415
Project No.: 94991457
ReImrt Date
08/2812000
Project:
Coppell Commerce Center
1234 Lakeshore (Bldg. B)
Coppell, Texas
Services: Obtain samples 'of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
STRENGTH:
SLUMP:
AIR:
TEST METHOD:
CO~rRACTOm Butler Construction
CONCRETE SUPPLIER: Pioneer
PLANT: 22
SPECIFICATION REQUIREMENTS
4000 psi @ 28 Days
5.0" Max
3-5%
ASTM C- 143
ASTM C- 172
ASTM C-39
PROJECT DATA
M~X ~.: 9351
PLACEMENT DATE: 07126/2000 BATCH TIME: 5:50am
TIME SAMPLED: 6:40am sY: Greg Dimock
WEATHER COIVOmoNs:
TEMPERATURE (F) - AIR
TRUCK~O: 1031
Am co~_.t~rr (,~): 4.3
Clear
79 F CONC~r~: 88
TIc~'r NO: 650776
UNIT WEIGffr (l~f): N/A
PLACEMENT LOCATION:
Sidewalks- W, N and E side of building A
Sampled from Iruck.
SAMPLE LOCATION:
100' N of SW corner of bldg. A
REPORT OF TESTS
ACCUMULATIV~ YARl~: 10
CYLINDER
MARKED
SET NO.
1 1
I 2
1 3
I 4
MEASURED MAXIMUM
SLUMP DATE AGE LOAD
(Inches) TESTED (days) Obs. for~)
6.25 08/02/2000 7 89770
6.25 08/02/2000 7 90740
Average
6.25 08/23/2000 28 118630
6.25 08/23/2000 28 122400
Average
COMPRESSIVE
STRENGTH
3170
3210
3190
4200
4330
4270
TYPE
Teclmkian: Greg Dimock
Report Dim-ibution:
(1) Transwestern Property Compauy
(1) O'Bdeu & Associates
(I) T~:hn~tures,
(1) Butl~ C~ou
Started: 5:00am
(1) City of Coppeil
(I) City of Coppell
Finished: 10:30am
Vice President
This report is exclusively for the use of rite client indicated above and sh~ll not be reproduced except in full without the wfit2n ~ of HBC Engineering. Inc.
0ILL Page I of 1