Oakbend Addn-CS 910423COPPELL PUBLIC WORKS MEMORANDUM HLP/dg OAKBND. HLP DATE: April 23, 1991 TO: Larry Davis, Construction Inspector FROM: Howard Pafford, Water Superintendent RE: Oakbend Addition Partial Walk Through Punchlist Field personnel have performed a partial walk through of the above referenced project and have found the following items to be deficient. 1. Branchwood Drive- Ail lots up to lot #3 need to have meter boxes cleaned out. 2. On all water services make sure setters are only 12" lower than the box lid. 3. Branchwood Drive - The sewer clean out in alley needs to be located. 4. Branchwood Drive - Need to check Fire Hydrant. 5. Paint all valve stack caps mainline (blue) and Fire Hydrant (red). 6. Oakbend Drive - (corner) Need nut extension on Fire Hydrant valve. 7. Oakbend Drive - In alley - clean out invert in manhole and clean out has no plug. 8. Oakbend Drive - Lot 74 center and grout manhole ring. 9. Sta. 6 + 75.00 - Clean out needs cap. 10. Oakbend Drive - Lot 21 Fire Hydrants needs lowering. 11. Make sure that all sanitary sewer lines down stream of this area are clean and free of debris. Please insure that these items are addressed before requesting a temporary release of lots for building. If you have any questions, please advise.