CONCRETE CYLINDER TEST REPORT
Daryl Flood Warehouse
Airline Road at Enterprise Road
Coppell, Texas
REPORTED TO:
Daryl Flood Warehouse-Movers, Inc.
2009 Country Club Drive
Carrollton, Texas 75006
ATTN: Mr. Daryl Flood
REPORT NO. 58
REG PROJECT NO. 6080
SAMPLE DATE: 03-08-00
TECHNICIAN: L, Walton
CONTRACTOR: McFadden & Miller, Inc.
Location of Sample
Set Number I Location
1
Slab Leave Out: 65'N, 55'W of SE Bldg. Corner
J Quantity Represented
10/40
Design Information
Source of Concrete
TXI
Mix Identification
47
Specified Strength p.s.i.
4000
Test Results
Set Cylinder J
No. ID Date Tested
Age @ Total Load
Test lbs.
Compressive J Average Strength
Strength p.s.i.I p.s.i.
3811 03-15-00 7
3811 04-05-00 28
3811 04-05-00 28
3811 Hold
98430 3480
Cylinder Data
Set Cylinder Time of
N1. ID Slump Sample
3811 5,00 10:30 AM
Concrete Air Ticket
Air Temp. Temp. Entrainment Number
70 68 N/A 1527531
Distribution:
(1) Daryl Flood Warehouse-Movers, Inc./
Mr. Daryl Flood
(1) McFadden & Miller, Inc./
Mr. Jon Jacobson
(1) Meinhardt & Quintana/
Mr. David Meinhardt
(1) Halff Associates/Mr. Patrick Acker
(1) City of Coppell/Mr. Larry Davis
(1) City of Coppell/Mr. Lee Stone
(1) Bihner Engineering/Mr. Yubo Chen
Submitted by:
REED ENGINEERING GROUP, INC.
Original Signed By
Keith Atkins
KEA/rt
2424 STUTZ DR. · SUITE 400 - DALLAS, TX 75235 · TEL [214] 350 5600 · FAX [214] 350 0019
GEOTECHNICAL AND G J==J I--I LJ F:~
ENVIRONHENTAL CONSULTANTS
REPORTED TO:
CONCRETE CYLINDER TEST REPORT
Daryl Flood Warehouse
Airline Road at Enterprise Road
Coppell, Texas
Daryl Flood Warehouse-Movers, Inc.
2009 Country Club Drive
Carrollton, Texas 75006
ATTN: Mr. Daryl Flood
REPORT NO. 58
REG PROJECT NO. 6080
SAMPLE DATE: 03-08-00
TECHNICIAN: L. Walton
CONTRACTOR: McFadden & Miller, Inc.
Location of Sample
Set Number J Location
Slab Leave Out: 65'N, 55'W of SE Bldg. Corner
J Quantity Represented
10/40
Design Information
Source of Concrete J
TXI
Mix Identification J
47
Specified Strength p.s.i.
4000
Test Results
Set Cylinder I
No. ID Date Tested
1 3811 03-15-00
3811 04-05-00
3811 04-05-00
3811 Hold
J Age @ Total Load
Test lbs.
Compressive J Average Strength
Strength p.s.i.J p.s.i.
7 98430 3480
28 140070 4950
28 147810 5230
5O9O
Cylinder Data
Set Cylinder I J Timeof I Concrete
N1. ID Slump Sample Air Temp. Temp.
3811 5.00 10:30 AM 70 68
JAir Ticket
Entrainment Number
N/A 1527531
Distribution:
(1) Daryl Flood Warehouse-Movers, Inc./
Mr. Daryl Flood
(1) McFadden & Miller, Inc./
Mr. Jon Jacobson
(1) Meinhardt & Quintana/
Mr. David Meinhardt
(1) Halff Associates/Mr. Patrick Acker
(1) City of Coppell/Mr. Larry Davis
(1) City of Coppell/Mr. Lee Stone
(1) Bihner Engineering/Mr. Yubo Chen
Submitted by:
REED ENGINEERING GROUP, INC.
Original Signed By
Keith Atkins
KENrt
2424 STUTZ DR. * SUITE 400 · DALLAS, TX 75235 * TEL [214] 350 5600 · FAX [214] 350 0019
CONTRA CT INSPECTION SER VICE, Inc.
4305 Glenwood Ct. Granbury, TX 76049 (817) 246-8096 FAX (817) 246-5889
REPORT OF
STRUCTURAL STEEL INSPECTION
Project:
CHent:
Daryl Flood Warehouse
Coppell, Texas
Reed Engineering Group
2424 Stutz, Suite 400
Report No: 16727-0
Attention: Keith Atkins
Date of Service: 03-08-00
Dallas, TX 75235 Page 1 of !
REPORT OF INSPECTION
Drawings utilized:
Structural Prints/SJI/AISC
Locations/item inspected: Grids A - J/! - 7
Grids A-J/l- 13 (anchor bolts)
Discrepancies/comments:
Inspection was conducted on the above referenced project in areas noted above with results
as follows:
1) Areas A through B/l-7, not complete at this time.
2) Area B-J/l-7 bearing of joist and girders comply.
3) Bridging installtion and welds comply - Area B-J/l-7.
4) Perimeter angle complies B J/l-1.
*5) Anchor bolts non-compliant for tensioning A-J/I-13.
6) Installation teflon slide pads comply to Detail S42-03.
Note - Water in some leave outs.
*Discrepancies.
Technician Contract ins~ecti;n ~ervice