Park West CC(1)-CS 890929The City With A Beautiful Future
September 29, 1989
Jeff Splawn
Director of Marketing
Hydromatic, Inc.
2663 Myrtle Springs
Dallas, Texas 75220
P.O. Box 478
Coppell, Texas 75019
214-462-0022
RE: Review for Approval the AMES Double Check Detector
Check Assembly for the Park West Commerce Center
Fire System
Dear Mr. Splawn:
After reviewing the material you have submitted regarding the above
reference device, I find the device to be acceptable and I approve
the installation of this device for the above referenced project.
Additionally, in order to gain approval for the use of this type
of fire line meter setting, the fire system shall be of the closed
interior sprinkler system type with alarm system connected to the
City of Coppell's Fire Department communications system and all
exterior on site fire hydrants shall be equipped with hydra storz
valves located on the 4 1/2" pumper nozzle of each fire hydrant.
If you have any questions regarding this matter, please contact me
at 462-8495.
SinCerely, ~ ~~,~
Utilities Superi~ndent
HLP/bb
xc: Steve Goram, Director of Public Works
Larry Davis, Public Works Inspector
James Rainey, Interim Fire Marshal
AMESDBCK.HLP
The Ames Company, founded in 1910, has
long been an industry leader in producing
fittings and valves for pipeline systems. All
Ames products are manufactured at their
60,000 sq.ft, facility in Woodland, California,
insuring quality control & prompt service.
DOUBLE CHECK
DETECTOR
CHECK ASSEMBLY
For Fire Protection Systems
DESCRIPTION
The Ames Double Check Detector
Check Valve protects the potable
water system by preventing back-
flow from fire protection systems.
The device also detects leaks or un-
authorized use of water from fire
protection lines.
OPERATION
In the incidence of minimal water flow,
the valve clapper remains closed so that
the water flows through the bypass Iccp.
When a major water flow is required, the
water pressure will fully open the clappers
to allow full water flow.
F EATU R ES
· Fabricated steel body provides a much
lighter weight unit than cast iron.
· Approved for mounting in horizontal or
vertical positions.
· Available with hot dip zinc galvanized
coating or fusion-bonded Ames Guard
epoxy coating.
· Prevents backflow from fire prevention
systems,
· OS&Y Gate valves are approved for fire
protection systems.
Ames Company, Inc. · 1485 Tanforan Avenue · P.O. Box 1387 · Woodland, California 95695 · (916) 666-2493
Ames DCDC -- WeightS & Dimensions (incheS) '
4" 51 33 25 121/2 I NPT 5 5/8 15 362 lbs. 126 lbs.
6" 66 45 323/3 17 11/2 NPT 6 11/16 17 549 lbs. 197 lbs.
8" 76 53 411/4 21 2 NPT 71/2 11/16 191/2 851 lbs. 317 lbs.
10" 833/~ 573/4 483/8 21 2 NPT 93/4 11/16 22 1278 lbs. 364 lbs.
with gates wlo gates
Additional Features
The Ames double check detector check assembly is
used to prevent backflow from fire protection lines into
the municipal water system. The assembly consists of two
independently operating, spring loaded check valves, two
UL listed OS&Y gate valves, and a bypass assembly.
The bYpass assembly consists of a meter which
registers in either gallons or cubic measurements, a
double check backflow preventer including shut-off valves
and required testcocks.
The Ames double check detector check'assembly is
manufactured for ease of installation, dependability,
durability, and in-line maintenance. The main bodies are
built from heavy-duty steel with a galvanized finish. All
internal parts are made from stainless steel to prevent
corrosion and are easily replaceable for service or repair.
USC
FCCCHR
Ames Company, Inc..
Flow Characteristics
14I
13'
12
11
.._ 10
m. 8
4
1
Flow (GPM)
'Developed by USC Foundalion for Cross Connection Control and Hydraulic Research
Other Specifications'
· Unit comes assembled with bypass which includes water
meter and backflow prevention assembly. Testcocks are
included.
· Rated working pressure 4", 6", 8" (175 PSI), 10" (150 PSI).
· Flange dimensions and holes in accordance with NASI
B16.5 Class 125.
· All internal metal parts are stainless steel with exception
of bronze seat ring,
· Body nameplate provides nominal size, direction of flow,
PSI rating and year of manufacture.