Park West CC(7)-LR 990315CONCRETE COMPREoSIVE STRENGTH TES
Date of Service: 02/11/1999 Report No.:
Client No.: 71765000 Project No.:
Client: Prentiss Properties Limited, Inc. Project:
Attn: David Glass
3890 W. Northwest Hwy.
Dallas TX 75220
9904727
43-2170-98
Lakeview Center
Coppell, Texas
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Report Date
03/15/1999
Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
CONTRACTOR: Butler Construction
CONCRETE SUPPLIER: Pioneer
PLANT: 22
SPECIFICATION REQUIREMENTS
STRENGTm 4000 psi @ 28 Days
SLUMP: 3-5"
AIR: 4-6%
TEST METHOD: ASTM C- 143
ASTM C-172
ASTM C-39
SAMPLE LOCATION: SWC, Parking area, 25'NE NWC
PROJECT DATA
CONCRETE CLASS: 9351
PLACEMENT DATE: 02/11/1999 BATCI~ TIM~: 6:24am
TIME SAMPLED: 8:40am BY: Mike Odom
WEATHER CONDITIONS: Cloudy
TEMPERATURE (F) - AIR 65. F CONCRETE: 81. F
TRUCK NO: 844 TICKET NO: 193860
AIR CONTENT (%): 4.1 UNIT WEIGHT (pcf): N/A
PLACEMENT LOCATION:
SW covered parking between one wing and two wing
CYLINDER MF_~SURED
MARKED SLUMP
SET NO. (inches)
1 1 5.00
1 2 5.00
I 3 5.00
1 4 5.00
Sample Location: SW
10 Gallons of water
Technician: Mike Odom
Report Distribution:
(1) Prentiss Properties Limited, Inc.
(I) Alliance Architects, Inc.
(I) Halff Associates
(1) Mullen & Powe[I Teclmistructures, i
REPORT OF TESTS
DATE
TESTED
02/18/1999
02/18/1999
03/11/1999
03/11/1999
ACCUMULATIVE YARDS: 100
MAXIMUM COMPRESSIVE
AGE LOAD STRENGTH
(days) (lbs. force) (psi)
7 85550 3030
7 80280 2840
Average 2940
28 115830 4100
28 120330 4260
Average 4180
covered parking area, 225'
added by Potter Concrete.
Started: 8:00am
(1) Butler Construction
(l) City of Coppell
( 1 ) City of Coppell
NE from WC wing one cut to '100".
Finished: 10:00am