Park West CC(7)-LR 981110 IN-PLACE DENSITY '_;STING
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service:
Client No.:
Client:
10/26/1998
71765000
Prentiss Properties Limited, Inc.
Attn: DavidGlass
3860 W. Northwest Hwy.
Dallas TX 75220
Report No.: 9829771
Project No.: 43-2170-98
Project: Lakeview Center
Coppell, Texas
Report Date
11/10/1998
Services: In-place density testing.
CONTRACTOR: Butler Construction
PROJECT DATA
Laboratory Test Method: ASTM D-698
Field Test Method:
ASTM D-2922
ASTM D-3017
MOISTURE DENSITY RELATIONS:
M/D No.
Description
Maximum
Moisture % Density pcf
Project Requirements
Moisture Density
Reddish brown clayey sand
w/clay balls and gravel
11.5 123.5
FIELD DENSITY TESTS
-2/+2% 95%
TEST
NO
TEST LOCATION
M/D MOISTURE DRY DENSITY DENSITY
No. (%) (pcf) (% max)
447
448
449
450
451
452
453
454
455
456
457
458
SE Comer 60'W and 20'N
SE Comer 60'W and 80'N
SE Comer 60'W and 190'N
SE Comer 100'W and 210'N
SE Comer 100'W and 140'N
SE Comer 100'W and 70'N
SW Comer 40'N and 60'E
SW Comer 40'N and 100'E
SW Comer 40'N and 160'E
SW Comer 90'N and 200'E
SW Comer 90'N and 120'E
SW Comer 90'N and 60'E
1 12.1 119.9 97
1 11.9 119.7 97
1 12.0 120.3 97
1 12.3 120.2 97
1 12.0 119.9 97
1 12.4 120.0 97
1 12.1 120.4 98
I 12.3 120.5 98
1 11.9 120.3 97
1 12.1 119.9 97
1 11.7 120.0 97
1 12.0 120.2 97
07DG
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc.
Page 1 of 2
Report No.: 982977
TEST MfD MOISTURE
NO TEST LOCATION No. (%)
DRY DENSITY
(pcf)
459
SW Comer 140'N and 90'E 1 12.0
Test results on this report meet project specification.
119.9
Recheck Prior to Concrete Placement
DENSITY
(% max)
97
Technician: Tex King
Report Distribution:
(1) Prentiss Properties Limited, Inc.
(1) Alliance Architects, Inc.
(1) Halff Associates
(1) Mullen & Poweli Technistructures, I
(1) Butler Construction
(1) City of Coppell
(1) City of Coppell
H~ Engin~
Eugene Harbour
Vice President
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc.
07DG Page 2 of 2