Loading...
ST9801-LR000908illl eeml Gi. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: Project: Contractor: Reported To: 114A Job No.: 1520COP03 Coppell Road Pavement, at North Business Park Entrance - 7'E and 10'N of S.E. Corner Coppell Road Paving and Drainage Improvements Ed Bell Construction Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP090801 09/12/00 87540 4 3100 09/08/00 3500 psi@28 days 10 of 50 R. Yarbrough Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 90 ° F Mix 90 ° F Air Content 5.5 % Slump 1:35 PM Pick-Up Charge: Yes Lattimore - 42 N/A Ticket No.: 7092388 Unit Weight PCF 4-3/4 Inches Yield CF/CY City of Coppell - Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE Oi: THE QUALITY OF APPARENTLY IOENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 Report No.: Location: Project: Contractor: Reported To: CONCRETE COMPRESSION TEST REPORT 114 Job No.: 1520COP03 Coppell Road Pavement, at North Business Park Entrance - 7'E and 10'N of S.E. Corner Coppell Road Paving and Drainage Improvements Ed Bell Construction City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. Field Number: CP090802 Test Date: 09/15/00 Maximum Load, LBS: 98520 Age When Tested, Days: 7 Compressive Strength, PSI: 3480 Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 09/08/00 3500 psi @ 28 days 10 of 50 R. Yarbrough CP090803 CP090804 CP090805 10/06/00 10/06/00 HOLD 28 28 HOLD Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 90 ° F 1:35 PM Lattimore - 42 Mix 90 o F Air Content 5.5 % Slump 4-3/4 Inches Pick-Up Charge: Yes N/A Ticket No.: PCF Unit Weight 7092388 Yield CF/CY City of Coppell - Larry Davis -/ Sign Pa Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE'I'FERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH,