Park West CC(7)-LR 980918-IN-PLACE DENSITY ./' STING
8901 Carpenter Frwy. Suite #100
Dallas, Texas 75247
Date of Service:
Client No.:
Client:
09/10/1998
71765000
Prentiss Properties Limited, Inc.
Attn: David Glass
3860 W. Northwest Hwy.
Dallas TX 75220
Report No.: 9823919
Project No.: 43-2170-98
Project: Lakeview Center
Coppell, Texas
Report Date
09/18/1998
Services: In-place density testing.
CONTRACTOR: Butler Construction
PROJECT DATA
Laboratory Test Method: ASTM D-698
MOISTURE DENSITY RELATIONS:
MfD No.
Description
Field Test Method:
Maximum
Moisture % Density pcf
ASTM D-2922
ASTM D-3017
ASTM D-698
Project Requirements
Moisture Density
1
2
Lt. brown to tan sandy clay
w/gravel and limestone pieces
20.5 99.5
0.0 0.0
FIELD DENSITY TESTS
-1/+3% 95%
TEST
NO TEST LOCATION
M/D MOISTURE DRY DENSITY DENSITY
No. (%) (PC0 ('/. max)
48" Storm Drain
271 Line B at station 0+75, 3rd lift
272 Line B at station 1+90, 3rd lift
40" Storm Drain
273 Line B at station 2+90, 3rd lift
42" Storm Drain
274 Line B at station 3+50, 3rd lift
275 Line B at station 4+50, 3rd lift
276 Line B at station 5+50, 3rd lift
48" Storm Drain
277 Line B at station 0+50, 4 th lift
278 Line B at station 2+70, 4th lift
1 19.9 95.5 96
1 20.1 95.2 96
1 20.4 95.4 96
1 20.5 95.2 96
1 20.3 95.4 96
1 20.2 95.1 96
1 17.6' 88.7 89*
1 17.8' 88.5 89*
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc.
07TMP Page 1 of 2
,Report No.: 9823919 ~" ~ I'~
TEST MfD MOISTURE DRY DENSITY
NO TEST LOCATION No. (%) (pcf)
279
Line B at station 3+40, 4th lift 1 17.7' 88.6
An asterisk (*) appears next to test results which do NOT meet the project specifications.
DENSITY
(% max)
89*
Technician: Tex King
Report Distribution:
(1) Prentiss Properties Limited, Inc.
(1) Alliance Architects, Inc.
(1) HalffAssnciates
(1) Mullen & Pow¢ll Technistructures, I
(1) Butler Construction
(1) City of Coppell
(1) City of Coppell
~ ET, Inc.
Euge~e Harbour
Vice President
This t~eport is exclusively for the use of the client indicated above and shall not be ~'produced except in full without the written approval of HBC Engineering, Inc.
07TMP Page 2 of 2