REPORT OF
STRUCTURAL STEEL INSPECTION
2424 Stutz, Suite 400
Dallas, TX 75235
ReportNo: 11533-8
Attention: Keith Atkins
Date of Service: 12-09-98
Page 1 of 1
Drawings utilized:
Locations/item inspected:
REPORT OF INSPECTION
Structural Drawings
nm,
Building 2, roof level framing between line A to E/1 to 7.
Discrepancies/comments:
* 1.) Column anchors, unable to inspect due to block outs being full of water.
*2.) Joist bridging not complete at side walls.
*3.) Perimeter deck support angle not complete at wall splices. 4.) Joist seat welds determined to be compliant.
5.) Joist girder seat welds at column cap plates and wall pockets determined to be compliant.
6.) Joist seat support lugs at tilt wall embed plates, welds determined to be compliant.
*7.) Joist seat bolted connections at expansion joint (line 7) not complete at slip side.
*Discrepancies